Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.4 LAccepted-AOC D NO 35 14 13 1 R P PETA KANCHARAPALEM VISAKHAPATNAM 530 008 | VISAKHAPATANAM | ANDHRA PRADESH | 530008 | L1 | Accepted-AOC LOWEST TENDER | |
| 2 | L2₹33.1 L+₹1.4 L (4.51%)Rejected-Finance | L2 | Rejected-Finance NOT TENDER | |
| 3 | L3₹33.8 L+₹2.1 L (6.62%)Rejected-Finance D NO 38 22 40 NEAR LAKSHMI NARASHIMA THEATER 104 AREA VISAKHAPATNAM 530007 | VISAKHAPATANAM | ANDHRA PRADESH | 530007 | L3 | Rejected-Finance NOT TENDER | |
| 4 | L4₹34.0 L+₹2.3 L (7.34%)Rejected-Finance 66 6 410 1 MULAGANDA HOUSING COLONY GAJUWAKA DEPOT VISAKHAPATNAM 530026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | L4 | Rejected-Finance NOT TENDER | |
| 5 | L5₹41.0 L+₹9.3 L (29.4%)Rejected-Finance ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | BAPATLA | ANDHRA PRADESH | 504214 | L5 | Rejected-Finance NOT TENDER |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
16 Jun 2023, 6:00 pmClosed
Garrison Engineer Utility-II
Garrison Engineer Utility-II 104 Area Industrial Estate Post Visakhapatnam -530 007
REPAIRS AND UPKEEPING OF WATER SUPPLY/ FIRE FIGHTING INSTALLATIONS INCLUDING CHLORINATION PLANTS AT NAVAL BASE AREA UNDER GE (U-II), VISAKHAPATNAM
2023_MES_593611_2
8910
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer Utility-II Visakhapatnam
Class D
7 documents required · 7 mandatory
₹500
Garrison Engineer Utility-II
₹92,000
Yes
13 Jul 2023
26 May 2023
17 Jun 2023
26 May 2023
16 Jun 2023
4 Jun 2023
Amount
Material and labour for maintaining of potable /fresh water to achieve chlorination level by keeping concentrated efforts as per standard water quality specifications of maintaining PPM, PH, TDS levels, by checking time to time with standard testing equipments/lab test items if any daily before pumping of water to users from sump/OHTs to building OH tanks through raising mains etc. by adding chlorination granuals, chlorine gas etc. as required for disinfection of water as per standard at site as under :-
(a) ppm at sump level to pumping water to building OH tank - 2ppm, (b) pH value - 6.5 to 8.5, TDS- 300ppm (c) Ensuring water is to be free from E.coli and thermotolerant coliform bacteria and it shall not be detectable in any 100ml of sample water.
Notes :- The item rate is inclusive of following :-
(a) The contrator or his rep is responsible for maintaining quality of drinking water as specified above and to adopt latest standard of water treatment for providing specified potable water. (b) Contractor or his rep has to attend daily at all pump houses once in a day to check all the water parameters and sign in the register being maintained with pump house staff. (c) Register should be maintained daily and daily record of the same should be endorsed from users/MES rep at pump house, concerned Engineer-in-Charge as well as concerned medical team of respective unit daily. (d) Lab test shall be carried out once in a month from locally available Govt approved lab for (i) PPM, (ii) TDS, (iii) pH value and E-Coil or thermotolerent Coliform bacteria. test report be rendered and a record of the same to be submitted to department once in a month or whenever required or directed by the users and department depend upon the situation/quality of water.
(e) The rate quoted is deemed to be inclusive of adding required chemicals like soda ash etc., to maintain pH value and TDS as and when required.
(f) Required quantity of chlorine gas/ chlorine granuals/ bleaching powder required to be used at pump houses regularly. The amount/quantity of mixing chemicals, gas etc.,would be vary as per the quality of receiving water from time to time to bring the required ppm once checked before pumping the water from sump to OHT of user building. The necessary mixing up of granuals/bleaching powder for maintaining standard water and for superchlorination the existing staff/ manpower at pump houses shall be utilized if necessary. Note: Supply only chlorine gas, bleaching powder, Alum shall be measured and paid seperately under relevant items of schedule
The above specified job shall be carried out at each pump house as under :-
(a) Nausenabaugh Main pump house (02 Places), (b) MES Key pers PH, NSB, (c) INS Circars (d) Naval Park & Amzari Park, (e) INS Sathavahana,(f) MWC,(g) SMHQ, (h) INS Virbahu, (j) MMT (E) - 14 Nos.
M & L for seven stage cleaning and sterilization of inside the RCC/Steel, underground / semi-underground,/ over head / Sedimentation / clear water sumps of capacity UG sump reservior 2.0 lakh gallons through bacteriological treatment by using TERBAC G5 / Inchor-5 / NB-10 / , TERBAC-G-65 / Inoxi-60 / NB-69 and ULTRA VOILET RAY complete all as specified and as directed. Make : Rays cleantech / Inus watertech / Satya enterprises equivalent steps for seven stages are as under :- First Stage is to drain out the water by using exit valve or high capacity dewatering system. Second Stage is cleaning all the algae formation inside the tank by using TERBAC-G10 a laboratory tested branded chemical of the company and scrubbing the walls of the tanks. Third Stage is fresh water cleaning by high speed jet pump. Fourth Stage and first bacteria screening is decertification by using TERBAC-G5 a Govt laboratary certified branded halogen compound.
Fifth Stage is cleaning the floor of water tank by industrial vaccum cleaner. Sixth Stage is the second bacteria screening and sterilizing method by using ultra voilet ray within the tank and kills all suspended bacteria. Seventh stage of cleaning and third bacteria screening is to sterlize the floor of the water tank by using laboratory certified, branded strong oxidizing agent TERBAC-G65 / Inoxi-60 / NB-69. Note : Work will be carried through specialized agency from one of the above given makes. (a) Company will submit Govt laboratory test certificate of TERBAC-G5, TERBAC-G65, fix the sticker mentioning the date of cleaning & name of site and also provide, certificate confirming the completion of sterlization of watr tanks mentioning the name of station and date of cleaning. All the cleaning & sterlization staffs should be under accidental insurance coverage.
All as per item No.2 above but UG/Semi UG sump of capacity 1.60 / 1.50 Lakhs gallons
All as per item No.2 above but UG/Semi UG sump of capacity 0.75 Lakhs gallons
All as per item No.2 above but OH tank of capacity 1.25 Lakhs gallons
All as per item No.2 above but OH tank of capacity 1.00 Lakhs gallons
All as per item No.2 above but UG/Semi UG sump of capacity 0.60 Lakhs gallons
All as per item No.2 above but UG/Semi UG sump of capacity 0.50 Lakhs gallons
All as per item No.2 above but UG/Semi UG sump 0.20 Lakhs gallons
All as per item No.2 above but UG/Semi UG sump 0.10 Lakhs gallons
All as per item No.2 above but of static water tank of capacity 0.05 to 0.060 lakh gallons
All as per item No.2 above but of static water tank of capacity 0.25 to 0.50 lakh gallons
Supply only chlorine gas in 100 Kgs cylinders to gravity feed gaseous chloronome plant all as directed. Note :- Testing the cylinder and repairs to outlet valve of cylinders will be the responsibility of the contractors and cost for applying mineral jelly to parts etc, deemed to be included in the cost quoted by the contractor.
Supply only White Alum (crystal type)
Supply and replace spare parts for chloronorm plant gravity feed as per sample including the taking down the unserviceable spare parts of the Chloronation plant complete all as directed
Panel connecting copper tube set
Pressure releasing valve (diaphram primary)
Primary filter PV 01
Supply and replace copper battery terminals all as directed by Engr-in-charge.
Supply, install, testing and commissioning of 12V, 180 AH Battery with inbuilt charger type maintenance free battery including terminal clamps, copper lead of suitable size / length, battery stand including taking down unserviceable one from the DG Set complete all as directed. Make:- Exide, Amco, Nicco, Amaron or as approved by GE
Supply and replacement of fire hydrant landing valve gun metal, type 'B' (Double head outlet) of 63 mm bore conforming to IS-5290 complete all as specified and directed.
Supply and replacement of fire hydrant landing valve gun metal, type A (Single head outlet) of 63 mm bore conforming to IS-5290 complete all as specified and directed.
Supply and replacement of gun metal fire brigade inlet connection 4 way with 4 Nos 63mm mmale coupling, NRV, rubber blank cap with chain confirming to IS 904 including with accessories suitable for 150 mm dia pipe complete all as specified and directed.
Supply and replacement 63 mm dia canvas pipe 15 metre long hose pipe confirming to IS 636 complete with male and female coupling and drum made out of MS sheet confirming to IS 903 complete all as specified and directed
S & F Hose Reel Drum Full Swing of not less than 20 mm bore and 30 m long as per IS – 884 complete with control and branch pipe, Gun Metal Nozzle of Suitable dia fitted for hose reel confirming to IS – 444/IS:12585 Tyoe-II including taking down existing Hose Reel Drum of any description complete all as specified and as directed.
M&L for drilling and welding for connection to 4 inches hydrant line by using 20mm GI nipples, Elbow and 20 mm gate valve for the provision of connecting rubber hose complete all as specified and directed.
Supply and replacement of ABS plastic 3/4" shut off nozzle suitable for 19/20mm hose complete all as specified and directed
Supply and replacement male coupling of 63 mm size with provision of 20mm hose reel (19/20mm size) connection suitable to fix fire hydrant landing valve gun metal type "B" ( Double headed) complete all as specified and directed
Repair/ servicing of any type water level indicator by replacing wornout central movement plate, counter weight, centre diving wheels etc., ncesaary required parts at site for fully operational, replacement of front glass with PVC/rubber gasket and applying two coats of synthetic enamel paint over a coat of primer complete all as specified and as directed.
Supply & replacement of water level indicator, 36" dia as per IS and including numbering with radium stickering, heavy duty float, counter weight, heavy duty driving gear nylon wire fitted in all in GI housing, cutting the RCC slab and making good the slab, painting the exposed surface with two coats of synthetic enamel over a coat of red oxide primer complete all as specified and directed by Engr-in-Charge. Note: Make of water level indicator shall be got approved by GE before procurement.
Supply and replace Pressure gauge dial of 6" dia, 0-20 kgs/cm2 ratings suitable to the existing water pipe lines including suitable fixing lines with necessary fixing arrangement complete all as specified.
Supply and replace Pressure gauge dial of 6" dia, 0-10 kgs/cm2 ratings suitable to the existing water pipe lines including suitable fixing lines with necessary fixing arrangement complete all as specified.
Supply and replace CI foot valve flanged type of size 200 mm with necessary rubber gasket, bolts, nuts and washers complete all specified and directed by Engineer-in-charge.
All as per item No.30 above but of 150mm bore
All as per item No.30 above but of 100mm bore
All as per item No.30 above but of 80mm bore
Labour only for cutting/ cleaning of bushes/plants/ grass inside and surrounding area of plant / equipment / installations installations including disposal the material up to a distance not execeding 50 m complete all as specified and directed by Engineer-in-Charge.
M& L for servicing of LT panels of any size by cleaning the panel, bus bar chamber with CTC solution, and welding the door using arc welding and fixing hinges, necessary nut and bolts, washers and made it completely functional for open/ close including painting of panel by spraying with two coats of epoxy based paint over a coat of red oxide primer, after cleaning of rusty panel surface both inside/ outside by emery paper and necessary preparation of smooth surface suitable for painting and including checking of incoming and outgoing connections, Re-fixing of existing ACBs & MCCBs, testing & commissioning, connected PCC & frame works, rewiring of control and power wiring with suitable size of FRLS copper cable but not less than 1.5 Sqmm, replacing of various unserviceable ON/ OFF switches, lugs etc making the panel fully functional Complete all as specified and as directed.
Supply and replace industril corrsion proof LED street light fitting of 50 Watt capacity with IP66 protection inlcuding electronic driver and accessories suitable for pole dia upto 40 mm including GI bracket made of 40 mm gia Gi pipe light grade of length not less than 1.2 metre bend to shape as reuired including connecting up with twin core ywisted flexible copper conductor cable with suitable size, necessary MS clamps, bolts, nuts, duly painted with 2 coats of synthetic enamel paint over a coat of primer complete all as directed by Engineer-in-charge. Make: CAT No. SLE UL 50W IP 66 LXN of Surya Roshini or its equivalent in Philips/ Havells India Ltd/ Wipro/ GE/ Bajaj.
Dismantling the old unservicable sign board and M&L for Fully retro reflective sign board (both side written) made out of 18 gauge CRCA sheet (1200mm x 900mm) with 40mm dia stainless steel square/round tube 1.6 mm thick having entire surface of both sides fully bounded with retro reflective sheeting of HTP grade Tape having pressure sensitive adhesive boards and messages as indicated cut out back ground in blue /green and matter in white color tape having two stainless steel posts 3.0 metre long of 65 mm dia circular tube 1.6 mm thick embedded in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) bed block of size 300mmx300mmx600mm depth including necessary earth work, excavation complete all as specified and as directed
Supply only Chlorine 56 %-70 % (Calcium based granular disinfectant for water treatment more stable for water treatment than chlorine gas and stronger than bleaching powder and sodium hypochlorite) in 45 Kg drums for maintaning residual chlorine between 1 to 2 PPM at supply and 0.5 ppm at User end, complete all as specified and as directed . Make: As approved by E-in-C's branch or as approved by GE.
SAI INFRAS
AYYAPPA CONSTRUCTIONS
GVR CONSTRUCTIONS
M/S SRI VENKATA BHAVANI CONSTRUCTIONS
SREE GAYATRI INFRA
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .