Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | As L1₹5.9 LAccepted-AOC 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | As L1 | Accepted-AOC L1 | |
| 2 | As L3Rejected-Finance | As L3 | Rejected-Finance As L3 | |
| 3 | As L2Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | As L2 | Rejected-Finance As L2 | |
| 4 | Rejected-Technical | - | Rejected-Technical Insufficient valid documents |
Tender Value
₹7.8 L
EMD Value
₹15,639
Closing Date
24 Jul 2018, 9:00 amClosed
Executive Engineer PWD BDN ELEC DIVN
Room no 1081st fl purta bhawan salt lake kolkata
Electrical works in relation to shifting of office premises of the Dept of FPI and H WB mayukh Bidhannagar Kol 91 to Benfish Tower Sec V Salt lake City Kol 91 SITC of Fire Detection system
2018_WBPWD_181497_1
WBPWD/EE/BED/15/e-IT of 2018_19/2nd call
Open Tender
ELECTRICAL WORKS M/R
Item Rate
20 days
Mayukh Bhavan
Please refer Tender documents.
4 documents required · 4 mandatory
₹15,639
Yes
29 Sept 2021
13 Jul 2018
26 Jul 2018
19 Jul 2018
24 Jul 2018
19 Jul 2018
Amount
Supply, Installation,Testing & Commisioning of EN-54 standard, VDS/LPCB Approved Microprocessor based 2 Loops expandable up to minimum 4 Loops, fire alarm control panel fully networkable with each loop capable of taking atleast 125 devices and each loop should be connected to a dedicated loop card (even if a loop card supports multiple loop the panel should be provided with 2 nos loop cards and should have provision for accomodating total 4 nos loop card), 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have in built rectifier, provision for external & internal printer (if required),Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, having minimum 1000 event memory, integral SMF lead acid batteries with sealed cells of 24 V / 12 V with integral battery charger complete as required and as per specification. (Approved Make: Honeywell / Bosch / Secutron / Siemens)
Supply, installation, testing & commissioning of EN-54 Standard, VDS/LPCB approved Addressable Multi-Sensor Detector (optical smoke as well as heat) with inbuilt / additional Isolator and integral LED status indicator with 360 degree viewing angle. Detector shall communicate 3 danger levels for differentiated alarm activation and high tolerance to dust,dirt, temperature fluctuations and air currents. Detector should have unquie address for communication and assigned through panel with Mounting Base as required with the protection category of IP40. (Approved Make: Honeywell / Bosch / Secutron / Siemens)
Supply, installation, testing & commissioning of EN-54 Standard, VDS/LPCB approved Intelligent Analog Addressable Heat Detector (Static + ROR) with inbuilt / additional Isolator and integral LED status indicator with 360 degree viewing angle. Detector shall communicate 3 danger levels for differentiated alarm activation. Detector should have unquie address for communication and assigned through panel with Mounting Base as required with the protection category of IP40. (Approved Make: Honeywell / Bosch / Secutron / Siemens)
Supply, Installation, Testing & Commissioning of Response Indicator, with all other accessories. (Approved Make: Honeywell / Bosch / Secutron / Siemens)
Supply, installation, testing & commissioning of EN-54 Standard, VDS/LPCB approved Inteliigent addressable manual call point with inbuilt / additional Isolator suitable for flush or surface mounting, call point shall include test key feature without removing the glass. Also should have protection category of IP44 and extra acceesories as required. (Approved Make: Honeywell / Bosch / Secutron / Siemens)
Supply, installation, testing & commissioning of EN-54 Standard, VDS/LPCB approved Addressable One input & One output module with inbuilt / additional isolator and shall have the LED indication for Normal, Fault, test, and activation.The module shall have the option for configuration as fail safe operation. (Approved Make: Honeywell / Bosch / Secutron / Siemens)
Supply & Drawing of 2 Core 1.5 sq.mm FRLS shielded copper Cable. (Make. Finolex / Technoflex / MEM/KEI)
Supply & Laying of 20 mm FR PVC rigid conduit pipe on the surface of the wall. (Make: Precisson / Prestoplast Medium).
L.W.C. must be quoted manually @1% on the total quoted value else the total quoted rate shall be treated incl. LWC as per rule. N.B. Rate should be quoted inclusive of GST.
GLYPTIC
B.K. MUKHERJEE AND ASSOCIATES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .