Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.2 LAccepted-AOC | L1 | Accepted-AOC being the lowest | |
| 2 | L2₹24.0 L+₹3.6 L (17.5%)Rejected-Finance D NO 9 947 66 DOCTORS COLONY SHIVAJI PLEM VISAKHAPATNAM 530017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | L2 | Rejected-Finance not lowest | |
| 3 | L3₹27.9 L+₹7.5 L (36.7%)Rejected-Finance D NO 65 6 500 2 MULAGADA COLONY HIMACHALNAGAR GAJUWAKA VISAKHAPATNAM 530 026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | L3 | Rejected-Finance not lowest |
Tender Value
₹27.5 L
EMD Value
₹55,020
Closing Date
17 Sept 2024, 6:00 pmClosed
CWE NO 2 VISAKHAPATNAM
CWE NO 2 VISAKHAPATNAM, HQ CE N COMPLEX, RAILWAY STATION ROAD, VISAKHAPATNAM - 530004
REPAIRS / MAINTENANCE OF VARIOUS CHILLER UNITS OF CENTRALISED AC PLANTS OF MAKE CARRIER IN NAVAL STATION, BHEEMUNIPATNAM
2024_MES_666594_1
82671
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE P NAVY KALINGA
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE P NAVY KALINGA
₹55,020
Yes
17 Feb 2025
18 Jul 2024
21 Sept 2024
18 Jul 2024
17 Sept 2024
1 Aug 2024
18 Jul 2024 - 1 Aug 2024
Amount
M&L carrying out servicing, testing of compressors, condensors and chiller system of capacity 3x120 TR AC plant and panels, model 30XA, make Carrier in P-168 and including panel maintenance, re-assembling the compressor in all respects, refixing the same in its original position, reconnecting all disconnected lines and including Leak test, pressure, nitrogen test, vacuuming etc, to make system functional complete all as per manufactureres instruction and as directed by Engr-in-charge.
Note: The quoted rate is deemed to be include for the following:- (i) Necessary T&P, MS Nuts, bolts, washers, gaskets, ladders, lubricants, waste cotton, filter drier core, transportaion etc. (ii) New spare parts required for replacing old parts shall be measured and paid separately against ‘Supply only’ under Sl. item Nos. 1.03 to 1.15 here-in-after.
(iii) Any minor spares / parts /accessories not covered in the Schedule "A" but required for completion of job shall be provided by the contractor. (iv) Renewal of control wiring in the system/ panel. (v) Servicing shall be carried out through OEM or his authorised agency only and test report shall be submitted in duplicate.
Supply only Control panel door hinges (XA left and right)
Supply only External oil filter,Carrier part No.2015970
Supply only Temp. Sensor,Carrier part No.2008536
Supply only Flow Switch,Carrier part No.2015971
Supply only Flow Switch cable (30XW), Carrier part No.2025823
Supply only electrical card carrier part no 2010891.
Supply only card display Carrier part No.2010892
Supply only Pressure Sensor,Carrier part No.2010882
Supply only contactor 25 amps from the existing panel.
Supply only refrigerants gas R-134a
Supply only contactor 3TF51,Carrier part No.2018571
Supply loading and unloading solenoid valve
Supply only unloader solenoid coil
M&L carrying out servicing, testing of compressors, condensors and chiller system of capacity 3x180 TR AC plant and panels, model 30XW0652 Make Carrier in Hanger (1 to 6) and including panel maintenance, re-assembling the compressor in all respects, refixing the same in its original position, reconnecting all disconnected lines and including Leak test, pressure, nitrogen test, vacuuming etc, to make system functional complete all as per manufactureres instruction and as directed by Engr-in-charge.
Note: The quoted rate is deemed to be include for the following:- (i) Necessary T&P, MS Nuts, bolts, washers, gaskets, ladders, lubricants, waste cotton, filter drier core, transportaion etc. (ii) New spare parts required for replacing old parts shall be measured and paid separately against ‘Supply only’ under Sl. item Nos 2.03 to 2.06 here-in-after.
(iii) Any minor spares / parts /accessories not covered in the Schedule "A" but required for completion of job shall be provided by the contractor. (iv) Renewal of control wiring in the system/ panel. (v) Servicing shall be carried out through OEM or his authorised agency only and test report shall be submitted in duplicate.
Supply only MCCB 3 pole 63 amps as per exising pannel.
Supply only contactor set for 3 pole TC contactor AC3, 25 Amps
Supply of flow switch
Supply only temp sensor as existing .
M&L carrying out servicing, testing of compressors, condensors and chiller system of capacity 3x60 TR AC plant and panels, model 30XW0262, make Carrier in Hanger (7&8) and including panel maintenance, re-assembling the compressor in all respects, refixing the same in its original position, reconnecting all disconnected lines and including Leak test, pressure, nitrogen test, vacuuming etc, to make system functional complete all as per manufactureres instruction and as directed by Engr-in-charge.
Note: The quoted rate is deemed to be include for the following:- (i) Necessary T&P, MS Nuts, bolts, washers, gaskets, ladders, lubricants, waste cotton, filter drier core, transportaion etc. (ii) New spare parts required for replacing old parts shall be measured and paid separately against ‘Supply only’ under Sl. item Nos. 3.03 to 3.05 here-in-after.
(iii) Any minor spares / parts /accessories not covered in the Schedule "A" but required for completion of job shall be provided by the contractor. (iv) Renewal of control wiring in the system/ panel. (v) Servicing shall be carried out through OEM or his authorised agency only and test report shall be submitted in duplicate.
Supply only system manager (4.3" pic 6 control) carrier part no- 2041965
Supply only Refrigerants gas R-134a
Supply only temp sensor as existing .
M&L carrying out servicing, testing of compressors, condensors and chiller system of capacity 3x80 TR AC plant and panels, model 30XW0312, make Carrier in hanger (19 & 20) and including panel maintenance, re-assembling the compressor in all respects, refixing the same in its original position, reconnecting all disconnected lines and including Leak test, pressure, nitrogen test, vacuuming etc, to make system functional complete all as per manufactureres instruction and as directed by Engr-in-charge.
Note: The quoted rate is deemed to be include for the following:- (i) Necessary T&P, MS Nuts, bolts, washers, gaskets, ladders, lubricants, waste cotton, filter drier core, transportaion etc. (ii) New spare parts required for replacing old parts shall be measured and paid separately against ‘Supply only’ under Sl. item Nos. 4.03 to 4.04 here-in-after.
(iii) Any minor spares / parts /accessories not covered in the Schedule "A" but required for completion of job shall be provided by the contractor. (iv) Renewal of control wiring in the system/ panel. (v) Servicing shall be carried out through OEM or his authorised agency only and test report shall be submitted in duplicate.
Supply only contactor 3 pole 3RT5044.
Supply only temp sensor
M&L carrying out servicing, testing of compressors, condensors and chiller system of capacity 3x65 TR AC plant and panels, model 30XW0312, make Carrier in Magazine P-243 at NADand including panel maintenance, re-assembling the compressor in all respects, refixing the same in its original position, reconnecting all disconnected lines and including Leak test, pressure, nitrogen test, vacuuming etc, to make system functional complete all as per manufactureres instruction and as directed by Engr-in-charge.
Note: The quoted rate is deemed to be include for the following:- (i) Necessary T&P, MS Nuts, bolts, washers, gaskets, ladders, lubricants, waste cotton, filter drier core, transportaion etc. (ii) New spare parts required for replacing old parts shall be measured and paid separately against ‘Supply only’ under Sl. item Nos. 5.03 to 5.05 here-in-after.
(iii) Any minor spares / parts /accessories not covered in the Schedule "A" but required for completion of job shall be provided by the contractor. (iv) Renewal of control wiring in the system/ panel. (v) Servicing shall be carried out through OEM or his authorised agency only and test report shall be submitted in duplicate.
Supply only flow switch.
Supply only flow switch cable
Supply of contactor 3 pole 3RT5044
M&L carrying out servicing, testing of compressors, condensors and chiller system of capacity 3x65 TR AC plant and panels, model 30XW0312, make Carrier in Magazine P-245 at NAD and including panel maintenance, re-assembling the compressor in all respects, refixing the same in its original position, reconnecting all disconnected lines and including Leak test, pressure, nitrogen test, vacuuming etc, to make system functional complete all as per manufactureres instruction and as directed by Engr-in-charge.
Note: The quoted rate is deemed to be include for the following:- (i) Necessary T&P, MS Nuts, bolts, washers, gaskets, ladders, lubricants, waste cotton, filter drier core, transportaion etc. (ii) New spare parts required for replacing old parts shall be measured and paid separately against ‘Supply only’ under Sl. item Nos. 6.03 to 6.04 here-in-after.
(iii) Any minor spares / parts /accessories not covered in the Schedule "A" but required for completion of job shall be provided by the contractor. (iv) Renewal of control wiring in the system/ panel. (v) Servicing shall be carried out through OEM or his authorised agency only and test report shall be submitted in duplicate.
Supply only flow switch .
Supply only pressure sensor .
M&L carrying out servicing, testing of compressors, condensors and chiller system of capacity 3x90 TR AC plant and panels, model 30XW0312, make Carrier in Magazine 244 at NAD and including panel maintenance, re-assembling the compressor in all respects, refixing the same in its original position, reconnecting all disconnected lines and including Leak test, pressure, nitrogen test, vacuuming etc, to make system functional complete all as per manufactureres instruction and as directed by Engr-in-charge.
Note: The quoted rate is deemed to be include for the following:- (i) Necessary T&P, MS Nuts, bolts, washers, gaskets, ladders, lubricants, waste cotton, filter drier core, transportaion etc. (ii) New spare parts required for replacing old parts shall be measured and paid separately against ‘Supply only’ under Sl. item Nos. 7.03 to 7.05 here-in-after.
(iii) Any minor spares / parts /accessories not covered in the Schedule "A" but required for completion of job shall be provided by the contractor. (iv) Renewal of control wiring in the system/ panel. (v) Servicing shall be carried out through OEM or his authorised agency only and test report shall be submitted in duplicate.
Supply only flow switch cable
Supply only temp sensor
Supply only pressure Sensor
M&L carrying out the descaling of the shell & tube condensers by isolation of each condenser by providing of dummy plate for inlet & outlet connection and seperation of condenser from water circulation without disturbing the operation of the AC plant, carrying out the descaling by circulation of the diluted scale removing agent organic compound type chemical of RA III / chemtex Brand at the appropriate ratio depend upon as recommended by manufacturer and the scale deposit inside copper tube by forced circulation and opening the end covers, mechanical brushing the copper tubes with nylon brushes of various size to remove complete scale, de-greasing with caustic soda solution and flushing out with fresh water, refixing all disconnected pipes lines, end covers with new rubber gasket and opening water line valves and checking of water leakages, apply grease to all M S bolts & nuts and put the condensers of the following capacities in operational condition complete all as specified and directed :-
65 TR Capacity
70 TR Capacity
80 TR Capacity
90 TR Capacity
180 TR Capacity
SRIVALLI ENGINEERS (BID ID -3087951)
ANAND ENTERPRISES AND ENGINEERS (BID ID -3098055)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .