Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.9 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹19.1 L+₹2.2 L (13.0%)Rejected-Finance A 8 SAKHARAM GANESH DAUSKAR SARANI KOLKATA 700 025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L2 | Rejected-Finance L2 | |
| 3 | L3₹19.1 L+₹2.2 L (13.1%)Rejected-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L3 | Rejected-Finance L3 | |
| 4 | L4₹26.0 L+₹9.1 L (53.7%)Rejected-Finance 86 TOLLYGUNGE CIRCULAR ROAD KOLKATA WEST BENGAL 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | L4 | Rejected-Finance L4 |
Tender Value
Refer Docs
EMD Value
₹33,722
Closing Date
20 Oct 2022, 3:00 pmClosed
MD,WBMSCL
Swasthya Sathi GN-29, Sector-V, Salt Lake, Kolkata 700 091
SITC of Air Conditioning System for Salboni SSH, Paschim Medinipur- at Blood Bank.
2022_WBMSC_412629_1
WBMSCL/NIT- 442/2022, Dated 29/09/2022
Open Tender
Electrical Work/ Equipment
Item Rate
45 days
Salboni SSH
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹33,722
7 Dec 2022
30 Sept 2022
21 Oct 2022
30 Sept 2022
20 Oct 2022
30 Sept 2022
Amount
OUTDOOR UNIT: Supply Installation,Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume aircooled Outdoor units suitable for cooling and heating ,having all hermetically seale dinverter type Scroll Compressor(s), minimum two compressors for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc.complete as required.The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature with out tripping.The unit shall be suitable to work on 400V+/-10%, 3Phase, 50Hz AC power supply.The unit shall be filled with first charge of the refrigerant and ready for use as required.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5)
INDOOR UNIT: Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV / VRF CassetteType Indoor ceiling mounted unit equipped with synthetic washable mediapre-filter, fan section with low noise fan/dynamically balanced blower, multi speed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drainpump, grill, necessary supports, vibration isolation, cord less remote controletc. ,suitable for operationon single phase 230V±10% ,50Hz AC supply, complete with all power/communication cable etc.- as required.The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System.The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree CD Band 19 Degree CWB temperature.
SITC of 5 star 1.5TR split type Air Condition with 230 V / 50 Hz / Single Phase power supply complete with indoor,outdoor and other all necessory accessories as required. Run with R410A refrigerent,Air Volume (CFM) Indoor Unit(Low/Mid/High/SHi)-Cooling-331/428/524/620(min.),Air Volume (CFM) Indoor Unit(Low/Mid/High/SHi)-Heating-311/428/524/620(min.), (Make- Mitsubishi: MSZ-HP18VA) or equivalent of O-General)
COPEER REFRIGERANT PIPING: Supply, Installation, testing and commissioning including accumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system ,complete with fittings (including Multikit etc.), with suitable adjustable ring type hanger supports with suitable GI Tray, jointing/brazing including accessories, insulated with XPLE Class - O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines,all accessories as per specifications etc. as required :
6.4mmdia(OD)(Softdrawn)withtubethickness1.2mmwith19mmthick insulation
9.5mmdia(OD)(Softdrawn)withtubethickness1.2mmwith19mmthick insulation
12.7mmdia(OD)(Softdrawn)withtubethickness1.2mmwith19mm thick insulation
15.86mmdia(OD)(Softdrawn)withtubethickness1.2mmwith19mm thick insulation
19mmdia(OD)(Harddrawn)withtubethickness1.2mmwith19mmthick insulation
22.2mmdia(OD)(Harddrawn)withtubethickness1.2mmwith19mm thick insulation
25.4mmdia(OD)(Harddrawn)withtubethickness1.2mmwith19mm thick insulation
28.58mmdia(OD)(Harddrawn)withtubethickness1.2mmwith19mm thick insulation
Design, enngineering,fabrication supplying installing testing and commissioning of structural steel supports painting and fixing as necessory in all respect.
MAXCOOL REFRIGERATION CO.
SKY DECORATIONS PRIVATE LIMITED
Lyric International
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .