| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.0 LAccepted-Finance 72 546A ERATHARA H LIBERTY LANE KALOOR PO KOCHI 682 017 | KOCHI | ERNAKULAM | KERALA | 682017 | L1 | Accepted-Finance Admitted Found Reasonable for Acceptance | |
| 2 | L2₹9.2 L+₹1.2 L (14.7%)Rejected-Finance JOY VILA MRA 230 MOOLAVILKOM JUNCTION VANCHIYOOR TRIVANDRUM 695 035 | TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695035 | L2 | Rejected-Finance Rejected L1 being accepted |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
23 Sept 2022, 6:00 pmClosed
GE Army Trivandrum
Office of Garrison Engineer Army, Thirumala Post, Trivandrum-06
As per tender documents
2022_MES_547953_1
GE (ARMY) TVM 9481/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Trivandrum
As per NIT
8 documents required · 8 mandatory
₹500
GE Army Trivandrum
₹20,000
Yes
10 Oct 2022
26 Aug 2022
30 Sept 2022
27 Aug 2022
23 Sept 2022
9 Sept 2022
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials and making good disturbed surfaces of walls, floors, etc.complete all as directed
M & L Point wiring complete for One light point controlled by one switch with 1.5 sqmm single core PVC insulated unsheathed FRLS cable 1100 volts grade with multi stranded, copper conductor in and including non-metalic PVC conduit incl accessories totally concealed in wall, ceiling/roof etc., with modular metal flush boxes of suitable size & modules, concealed in walls with modular white plated cover as top cover fixed with screws for housing switches, socket outlets, fan regulators etc, including provn of 1.5 sqmm nominal cross sectional area, PVC insulated, FRLS, unsheathed, 1100 volt grade, multistranded single core green colour copper conductor for earth continuity connected to earth dolly all as directed NOTE: Cost of modular metal flush boxes with a coat of synthetic enamel paint over a coat of red oxide to steel surface to avoid rust, concealed in wall with suitable white cover plate for mounting switch/sockets, regulator, bell push etc and Cost of cutting chases & making good to distrubed surface with cement mortar, if required any shall be deemed to be included in the quoted rate
All as per ser item No. 2 here-in-before but for One fan/exhaust fan point controlled by one way switch and regulator
All as per ser item No. 2 here-in-before but for One bell/buzzer point controlled by one bell push button independent.
All as per ser item No. 2 here-in-before but for one 5 Amps outlet on same board with other switches/sockets
All as per ser item No. 2 here-in-before but for one 5 Amps socket outlet on independent board.
All as per ser item No. 2 here-in-before but point wiring with 4.0 Sqmm FRLS cable and 4.0 sqmm cable earth continuity wire for one 3 pin socket outlet,15 Amps on independent board.
S&F modular switch 1 way 6A, 240 volts, 1 module complete all as directed
S&F modular switch 1 way 16A, 240 volts, 1 module complete all as directed
S&F modular bell push, one way, 6A/10A, 240 Volts, 1 module complete all as directed
S&F modular fan step regulator, 2 module, 240 Volts, 50 Hz, suitable for ceiling fan of any sweep all as directed
S&F modular socket, 6A, 240 volts, 3 pin combined 2 module, ISI marked flush type all as directed
S&F modular socket, 6A/16A, 240 volts, 2/3 pin combined 2 module flush type all as specified and directed
S&F ceiling rose surface PVC/Polycarbonate, isolated body with face Bakelite 65x50 mm three terminal complete all as specified
S&F Lamp holder angular type, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as directed Make: Anchor/ Havells/Legrand/Cona/Crabtree
S&F buzzer, Ding Dong, AC, 240 Volts, single pole all as directed
M&L for distribution board, vertical, made out of sheet metal enclosure (CRCA sheet) dust and vermin proof, double door, VTPN 6 way, 415 volts grade with insulated rated bus bar with nickel plated brass, isolated neutral bar and door earthing, earth bar IP- 43 protection with poly urithene (PU) gasketing, IK-08 Mechanical impact resistance, door earthing flush to wall, including testing suitable for fixing MCCB, MCB TP/SPN/SP etc, including taking down existing unserviceable one and removing from site complete all as specified and directed Make: Indoasian/L&T/ABB/Havells/Siemens/Schneider/Legrand
All as per ser item No. 17 here-in-before but for VTPN 4 way
S&F in replacement of MCCB triple pole and neutral (four pole) 100 Amp, 415 volts, 50 Hz, having thermal setting range 70% to 100% and adjustable magnetic setting and breaking capacity 25 KA including making incoming and outgoing connections complete all as specified and directed
M&L for distribution board made out of sheet metal enclosure (CRCA sheet) dust and vermin proof, double door, TPN 4 way, 415 volts grade with 200 Amps insulated rated bus bar with nickel plated brass, isolated neutral bar and door earthing, earth bar IP- 43 protection with poly urithene (PU) gasketing, IK-08 Mechanical impact resistance, door earthing flush to wall, including testing suitable for fixing MCB SPN, SP etc, including taking down existing unserviceable one and removing from site complete all as specified and directed
All as per ser item No. 20 here-in-before but for SPN 12, 240 volts grade with 200 Amps insulated rated busbar
S&F sheet steel metal enclosure single pole & neutral with a 2 pin and earth plug and socket complete with one single pole MCB SP 20 Amp, 240 volts complete all as specified and directed.
S & F MCB single pole 5 to 32 Amps, 240 volt, 10 KA, C curve, ISI marked as per IS/IEC-60898-1 2002 including sliding bottom clamp, integrated label holder, sliding shutters, biconnect lower terminals with IP-20 protection complete with connection, testing including taking down old unsv one from the site complete all as directed
All as per ser item No. 23 here-in-before but for MCB single pole and neutral 32 Amps complete all as specified and directed
All as per ser item No. 23 here-in-before but for MCB triple pole 63 Amps complete all as specified and directed
All as per ser item No. 23 here-in-before but for MCB triple pole and neutral 40 to 63 Amps complete all as specified and directed
Supply and fixing sub main wiring with 4 runs of 6.0 sqmm single core, multi-stranded PVC insulated, FRLS unsheathed cable 1100 Volts grade with copper conductor drawn through and including concealed non metalic PVC FRLS conduit, medium grade, ISI marked, 20/25mm bore with conduit fittings and accessories concealed in wall/ceiling/floor including 2 runs run of 6.0 Sqmm multistranded PVC insulated FRLS, copper conductor cable as earth continuity conductor and connecting to common earth dolly complete. NOTE: Four runs of 6.0 sqmm copper cable and two run of 6.0 sq mm copper cable alongwith non metallic PVC conduit/conduit accessories will be measured as one unit length
All as per ser item No. 27 here-in-before but for sub main wiring with 2 run of 6 sqmm & 1 run of 6 sqmm as earth wire
All as per ser item No. 27 here-in-before but for sub main wiring with 2 run of 4 sqmm & 1 run of 4 sqmm as earth wire
S&F LED lights fitting 1x 20W, 220V, AC decorative box type with driver, double sided connection, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, including taking down existing unserviceable one and removing from site complete all as specified and directed. NOTE: LED tube light and LED batten fittings should be two different items. Make: Havells / Philips/Bajaj/Wipro/Osram/CG
S&F LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
Supply and fixing LED light fitting round shape 12 watt 220 volts AC surface/recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers,suitable for roof/ceiling including connecting up with three core flexible copper conductor cable of suitable size complete.all as specified and directed.
Taking down carefully existing serviceable Ceiling fan/Wall mounted fan, ceiling cable end, etc., removing the fan for keeping in safe custody, re- hanging the ceiling fan with down rod after rewiring including clamps, hooks, holdfasteners etc and connecting up, including making electric connection from ceiling rose or connector to fan complete all as directed
Taking down carefully existing serviceable exhaust fan, ceiling cable end, etc., removing the fan for keeping in safe custody, re-fixing the exhaust fan connecting up after rewiring, including making electric connection from ceiling rose/connector to fan complete all as directed
Taking down carefully existing serviceable Geysers of capacity 25 ltrs, ceiling cable end, etc., removing the geyser for keeping in safe custody and refixing geyser with provn of new suitable MS bolts, grouted to wall and connecting up with flexible copper conductor cable & making good to the disturbed surface complete all as directed
M&L for Earthing complete in replacement with galvanised iron mild steel earth plate electrode 60 cm x 60 cm x 6.3mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to glavanised earthwire 4mm diameter by means of GI Bolts, Nuts, check nuts and washers including earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 type B-1) cover slab 50 mm thick with 8 mm CTD bars reinforcement both ways at 140 mm centre to centre with two handles, 20 mm dia GI pipe medium grade for watering pipe , wire mesh, funnel and providing charcoal or coke and salt in alternative layers of 15 cm and 15 mm dia light grade GI pipe for protection of earth wire from earth plate to MCB DB including necessary earth work in soft/loose soil, returning, refilling and removing of surplus soil to a distance not exceeding 50 mtr and testing on completion complete all as shown in electrical plate No-3 of SSR Part I as specified and directed.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .