Loading…
Loading…
Tender Value
₹21.9 L
EMD Value
₹22,000
Closing Date
6 Aug 2026, 4:00 pm
Executive Engineer, Electric (R&B) Division, Rajkot
A&A to Arm. Al Cable, Pole Box, ELCB and Other Necessary Items in Various Hostel Building and Resident Quarters in Rajkot City.
327607
05 of 2026-27
Open
Electrical Works
Works
Rajkot
8 documents required · 8 mandatory
₹900
Executive Engineer, Electric (R&B) Division, Rajkot.
₹22,000
24 Jul 2026
24 Jul 2026
24 Jul 2026
6 Aug 2026
24 Jul 2026
Name of work: A&A to Arm.Al Cable , Pole Box , ELCB and Other Necessary Iteams in Various Hostel Building and
Resident Quarters in Rajkot City .
Item Quantities estimated but Item of work Tendered Rate Total amount
Item Quantities estimated but Item of work Tendered Rate Total amount
No. may be more or less according to
Qty. Unit estiamted
Replacing Old & u/s by Supplying & erecting approved make
SMC press moulded composite FRP. loop-in, loop-out
approx. 2mm thick box complete with Bakelite connector strip
5way(3P+N+E),DIN rail for mounting mob & hinged doors as
1 750.00 Ea per requirement having locking arrangements with mounting 515.10
clamp with nuts, bolts & washers suitable for erection on pole
with cable clamps& earth bolt of following size of box.(B)
250mm x 200mm x 100mm [deep]
Replacing Old & u/s by Supplying and erecting B class
galvanised iron pipe 32 mm outside dia 45 cm long duly
welded on 20 cm x 20 cm x 3 mm thick M.S. base plate,
erected on wall or corner for mounting street light luminaire
with necessary hardware materials duly painted.
Providing and erecting ISI mark Medium class RIGID PVC
PIPES of following size complete to be erected on/in wall or
ceiling erected with necessary PVC fittings & Junction boxes
fixed with adhesive solution & Clamps with following dia of
pipes, in approved manner as directed (a)20 mm
Supplying and erecting LED street light / Flood light fittings
with High power White LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency more than 130 lm/w
and corrosion free High pressure die cast aluminum housing
with smooth finish powder coated and heat sink extruded
aluminium with diffuser and Polycarbonate optics/ lenses, with
toughened glass with company mark/name engraved or
4 embossed 160 to 270 V,Power Factor more than 0.95, THD < 0.00
10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45,
Luminaire efficacy> 100 lumens/watt . LED driver efficiency >
85 %.( fittings required LM-79 & LM-80 certificates)(NOTE:
Below description have shown ranges of Wattage capacity of
LED fittings.The Engineer incharge may select any wattage
capacity between the ranges shown.)
(A) Street Light (IP-65), Surge protection -4KV integral and
,Light must have 440VAC line supply with over-voltage
protection.(iii) 60 - 89 watts Cat-lll
Replacing Old & u/s by providing and erecting Miniature
circuit breaker single pole 0.5A to 2A system and having
5 750.00 Ea breaking capacity 10 KA to be erected in existing box. 297.95
confirming to IS 8828/1996 with ISI Mark Cat.III
Replacing Old & u/s by Providing and erecting FRLS-XLPE
(IS:7098)(I)-88 ISI armoured cable multistrand / Solid
Aluminium conductor for 1.1 kV. to be laid on wall with
6 1300.00 Mtr necessary clamps or in existing trench / pipe of following size 151.50
of cables (B) 4 core 6 Sq. mm
Replacing Old & u/s by Providing and erecting FRLS-
XLPE(IS:7098)(I)-88 ISI armoured cable Aluminium
conductor for 1.1 kV. to be laid on wall with necessary
7 1600.00 Mtr clamps or in existing trench / pipe of following size of cables. 112.11
(B) 2 core 6 Sq. mm
Item Quantities estimated but Item of work Tendered Rate Total amount
Item Quantities estimated but Item of work Tendered Rate Total amount
No. may be more or less according to
Qty. Unit estiamted
Making trench in Hard Murrum / Tar Road of suitable width of
90 cm or required depth for laying any size of cable or
8 300.00 Mtr locating the fault all over the run and back filling the same 74.74
and making the surface as normal ground.
(B) If additional machinery like hammer driller or JCB use
Providing & laying approved make ISI marked HDPE 6Kg /
cm2 (Class-3) as per IS:4984:1995 PE-80 to be erected at
road crossing on or floor as directed for laying of cable. The
pipes as following size of dia & weight per 6 mtr.(A) 40 mm
Providing and erecting Approved make RCCBs conforming to
IS: 12640 and having sensitivity of 30 mA and Short Circuit
withstand capacity of 10 KA and suitable for operation on
phase and neutral 415V,50Hz. having characteristic of quick
action & tripping with all advance feature & do not
incorporate any electronic component for following Max.
rating erected as directed.(i) 25 Amps.FP Cat. III
Replacing Old & u/s by Providing & erecting 415V MCB Four
Pole Switch for Lighting Load (B curve) having 10KA
11 20.00 Ea breaking capacity & confirms to IS :8828 in existing box 637.31
having following capacity (a) 6 to 32 Amp. Cat.III
Replacing Old & u/s by Supplying and erecting Flexible PVC
insulated multi strand multi core 1.1 kV grade ISI marked
12 1500.00 Mtr copper wires of following size to be erected as directed.(e) 58.58
1.50 Sq.mm 3 core round PVC sheathed
Note:- The Credit of dismentalled materials for Rs.38004.00 shall be recovered from the First R.A. bill payable to the contrator
and there after the dismentalled materials shall be the property of the contractor.
I/We am/are willing to carry out the work at__________________% above/below (in
figures)_____________________________________percent Above / below (in words) the estimated rates mentioned above amount of
my\our tender works out as under :-
Estimated amount put to Tender Rs. _________
Deduct________% below Rs. _________
Net Amount Rs. _________
Estimated amount put to Tender Rs. _________
Net Amount Rs. _________
A I/We hereby declare that I/we have visited the site and fully acquainted my self / our selves with the local
situation regarding material,labour and other factors pertaining to the work before submitting this tender.
B I/We hereby declare that I/we carefully studied the conditions of contract, detailed technical specifications
and other tender documents of this work and agree to execute the same accordingly.
C Any Excess in Tender Item/Extra Item if Needs to be Execute. Contractors has to carry out work on the
instruction of Competant Authority on Tender Submitted rate,No Excuse will be Accepted.Hence Contractor
are Requested to quote the rate considering this condition.
Item Quantities estimated but Item of work Tendered Rate Total amount
Item Quantities estimated but Item of work Tendered Rate Total amount
No. may be more or less according to
Qty. Unit estiamted
D Contractor are requested to quote the Tender by considering that payment will be made after availibility of
grant.Contractor has to start the work immediately after issue of Work Order and as per instruction of Engineer-
in-Charge irrespective of availibility of grant.
E "This estimate has been prepared on the new SOR wich is exclusive of GST hence GST additional will be paid
to the agency as per existing guidelines."
(Signature of the Contractor)
Note 1 Please strike out whichever is not applicable.
2 In the case of tendered amount being quoted incorrectly the quoted pered percentage Below/Above will be
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
ONLINE_NOTICE(R-2)(dn) RJT.pdf
ANNEXURE-A (4) (1).pdf
DM.pdf
MAKE FOR ELECTRICAL ITEM (4).pdf
SCH-B 3.pdf
SPECIAL CONDITION1.pdf
SBD.docx
DOCX
Contractor_Registration_Paripatra__1_.pdf
EMD GR.pdf
GR for Extra Item.pdf
GR for single Tender.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].