| 1 | L1₹59.9 LAccepted-AOC | ₹59.9 L | L1 | Accepted-AOC Lowest Bid Accepted |
| 2 | L2₹1.0 Cr+₹41.7 L (69.7%)Rejected-Finance FLAT NO 304 SN TOWERS JAGANNADHAPURAM JUNCTION AKKAYYAPALEM VISAKHAPATNAM 530 016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | ₹1.0 Cr+₹41.7 L (69.7%) | L2 | Rejected-Finance Not Being Lowest Bidder |
| 3 | L3₹1.2 Cr+₹62.9 L (105.0%)Rejected-Finance | ₹1.2 Cr+₹62.9 L (105.0%) | L3 | Rejected-Finance Not Being Lowest Bidder |
| 4 | L4₹1.3 Cr+₹68.2 L (113.8%)Rejected-Finance | ₹1.3 Cr+₹68.2 L (113.8%) | L4 | Rejected-Finance Not Being Lowest Bidder |
| 5 | L5₹1.3 Cr+₹73.8 L (123.2%)Rejected-Finance 2ND FLOOR 9 EZRA STREET KOLKATA WEST BENGAL 700001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | ₹1.3 Cr+₹73.8 L (123.2%) | L5 | Rejected-Finance Not Being Lowest Bidder |
Tender Value
₹1.0 Cr
EMD Value
₹1.8 L
Closing Date
15 Apr 2024, 6:00 pmClosed
Col KK Srivastava, Commander Works Engineer
Commander Works Engineers, Station Road, Visakhapatnam - 530 004
Repair Maintenance to the 33 KV MRS Yards and other allied works at NAD, Eksila and Dolphin Hill Areas under GE Utility I, Visakhapatnam
2024_MES_644953_1
82426/E8
Open Tender
Civil Works
Item Rate
270 days
Visakhapatnam
Class B and Category b iii
9 documents required · 9 mandatory
₹1,000
Garrison Engineer Utility - I
₹1.8 L
Yes
15 May 2024
9 Mar 2024
17 Apr 2024
9 Mar 2024
15 Apr 2024
6 Apr 2024
9 Mar 2024 - 16 Mar 2024
Amount
M & L for dismantling the LT / HT Connections, Earthing, Control Cables carefully from the Transformer installed on Foundation of 33 KV MRS Yard at Dolphin Hill and Loading the 3.15 MVA capacity Transformer weighing minimum 10200 KG by using suitable Crane on to the Transporting Trolley Vehicle, Transporting the serviceable Transformer on Trolley Vehicle to Workshop from 33 KV MRS Yard at Dolphin Hill, Loading the 3.15 MVA Transformer by using suitable Crane on to the Transporting Trolley Vehicle after completion of Repairs at Workshop, Transporting the unserviceable Transformer on Trolley Vehicle to 33 KV MRS Yard at Dolphin Hill from Workshop and unloading and placing it on the Transformer Foundation carefully complete all as specified and as directed. Notes: [a] Cranes used for Loading, Unloading of Transformer on to the Transporting Trolley Vehicle and Transformer Foundation shall not be less than 20 Tons. [b] Any damage to insulators / bushes / windings etc. while in the custody of the contractor shall be made good at no extra cost to the Government. The serviceability of the transformer shall be checked and confirmed by the contractor before taking into his custody. [c] M & L for rewinding / re-insulation of HT / LT [Primary / Secondary] Coils, Bushes, Studs, Transformer Oil, Filtration of Oil, Cable Box, replacement of Buchholz Relay / MOG, repair / servicing of OLTC etc. will be measured and paid separately under relevant items of this BoQ.
M & L for carrying out following repairs in 3.15 MVA capacity Transformer at Dolphin Hill complete all as specified and as directed. [a] Draining out transformer in the suitable capacity of container / drums and keeping it in safe custody for reuse. [b] Opening top cover of the transformer by unscrewing nuts / bolts / washers etc. including disconnecting core assembly from HT / LT bushing and lifting the same gently with the help of crane and taking out from the shell [Container / Body] of the transformer. [c] Visual inspection of entire Core Assembly, Transformer Tank, Core Limbs, OLTC etc., locating the fault / damages. [d] Cleaning the transformer body from inside, removing deposited dirt / sludge / foreign particles etc. from the bottom / body of the transformer, cleaning with CTC and drying up the shell from inside before refilling with the Transformer Oil. [e] Cleaning and washing thoroughly core and serviceable windings of the transformer by hosing down with clean dry oil conforming to IS – 336, removing deposited dirt / sludge / foreign particles from the windings / core through inspection of windings, providing insulations to leads and terminals complete and re-assembling the core including newly winded coils etc.
[f] Heating / drying / baking complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc all as per IS. [g] Lifting and refixing core assembly inside the transformer shell gently and carefully connecting Primary / Secondary / Neutral Terminal Connections to the bushings assembly, fixing of Tap changer including tightening of nuts, bolts, washers of the core to reduce humming noise. [h] Refilling the filtered transformer oil in the shell of transformer complete. [i] Refixing the top cover including replacement of Cork Sheet / Gasket 8 mm thick tightening of nuts / bolts / washers etc. and replacement of Breather with Silica Gel. [j] Connecting Primary / Secondary / Neutral connections etc. [k] The inspection of transformer shall involve Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts, Checking all brazing, joints, Tap heads and connection joints, Checking all jumpers, terminations / connections inside the transformer and Checking the Bulcholtz Relay / Conservator MOG if any.
M & L for Painting of Transformer of 2.5 MVA / 3.15 MVA Capacity complete with Two Coats of Synthetic enamel paint externally and painting with a coat of Oil Resistant Paint inside the Transformer Shell complete all as specified and as directed.
M & L for Painting of Transformer of 5 MVA Capacity complete with Two Coats of Synthetic enamel paint externally and painting with a coat of Oil Resistant Paint inside the Transformer Shell complete all as specified and as directed.
M & L for overhauling OLTC of 33 KV / 11 KV Transformer of capacity 2500 KVA / 3150 KVA by draining out of Transformer Oil, dismantling of top cover, inspection of moving and fixed contacts of all Three Phases and checking the operation, cleaning and removal of contacts of all the Three Phases and checking the operation, cleaning and removal of all carbon particles, Checking the thickness of leads in the OLTC Board, Moving / Fixed Contacts, inspection of Transition Resistance and replacement of Gasket / Contacts etc., if found damaged, reassembling complete, Filling up of Oil, testing complete all as specified and as directed. Note: Spares will be measured and paid separately
M & L for overhauling OLTC of 33 KV / 11 KV Transformer of capacity 5000 KVA by draining out of Transformer Oil, dismantling of top cover, inspection of moving and fixed contacts of all Three Phases and checking the operation, cleaning and removal of contacts of all the Three Phases and checking the operation, cleaning and removal of all carbon particles, Checking the thickness of leads in the OLTC Board, Moving / Fixed Contacts, inspection of Transition Resistance and replacement of Gasket / Contacts etc., if found damaged, reassembling complete, Filling up of Oil, testing complete all as specified and as directed. Note: Spares will be measured and paid separately.
M & L for rewinding of HT Tap Winding for 33KV / 11KV [5 MVA/3.15 MVA/2.5 MVA] Power Transformer at Dolphin Hill /NAD / Eksila HV Coil [Primary Side] of any Capacity / Type by winding defective coils with new copper wire with Kraft Paper insulation as per IS of same gauge and size together with new insulated materials/bracings before placing in to the transformer and assembling the coil with new insulation materials, varnishing and fitting the coils in the chamber, testing and commissioning the transformer and recording the test results complete all as specified and as directed. Note: M & L for re-insulation of serviceable coils will be measured and paid separately under relevant items of this BoQ.
M & L for rewinding of HT Tap Winding for 33KV/11KV [5 MVA/3.15 MVA/2.5 MVA] Power Transformer at Dolphin Hill / NAD / Eksila LV Coil [Secondary Side] of any Capacity/Type by winding defective coils with new copper wire with Kraft Paper insulation as per IS of same gauge and size together with new insulated materials/bracings before placing in to the transformer and assembling the coil with new insulation materials, varnishing and fitting the coils in the chamber, testing and commissioning the transformer and recording the test results complete all as specified and as directed. Note: M & L for re-insulation of serviceable coils will be measured and paid separately under relevant items of this BoQ]
M & L for Filtration of Transformer Oil of transformers installed at various locations to achieve di-electric strength not less than 60 KV at 2.5mm gap as per relevant IS with Portable Filtration Plant, testing of the oil for the di-electric strength before filtration and after filtration complete all as specified and as directed.
Supply and topping up of Transformer Oil with di-electric strength not less than 60 KV in to the Conservator Tank / Body Tank of the Transformer etc. complete all as specified and as directed. Make: Power Oil / Transol / Sabitha Chemicals
M & L for Servicing of 33 KV PTs, Oil immersed, outdoor type of any description including replacement of bushing and top up of oil complete all as specified and as directed.
M & L for Servicing of CT's of 33 KV,Outdoor Type of any description including reconnecting, fault finding, rectification ,testing and replacement of bushing and top up of oil complete all as specified and as directed.
S & F in repairs HV porcelain bushing for transformers of capacity 5 MVA alongwith suitable length of brass/ copper bushing rods 33 KV as per existing model complete all as specified and as directed.
S & F in repairs HV porcelain bushing for transformers of capacity 3.15 MVA alongwith suitable length of brass/ copper bushing rods 33 KV as per existing model complete all as specified and as directed.
S & F in repairs HV porcelain bushing for transformers of capacity 2.5 MVA alongwith suitable length of brass/ copper bushing rods 33 KV as per existing model complete all as specified and as directed.
S & F in repairs LV porcelain bushing for transformers of capacity 5 MVA alongwith suitable length of brass/ copper bushing rods 33 KV with threading as per existing model complete all as specified and as directed.
S & F in repairs LV porcelain bushing for transformers of capacity 3.15 MVA alongwith suitable length of brass/ copper bushing rods 33 KV with threading as per existing model complete all as specified and as directed.
S & F in repairs LV porcelain bushing for transformers of capacity 2.5 MVA alongwith suitable length of brass/ copper bushing rods 33 KV with threading as per existing model complete all as specified and as directed.
S & F in repairs cast iron Radiator butterfly valves of suitable size flanged type with cap and sealing 'O' ring, operated with electric actuator, duly powder coated suitable for Power Transformers of any capacity/ make complete all as specified and as directed.
S & F Silica Gel into Breather of Transformers complete all as specified and as directed.
S & F WTI (Winding Tempreture Indicator) for 3.15 MVA Power Transformer suitable size all as per existing including dismantling of old unserviceable WTI complete all as specified and as directed.
S & F OTI (Oil Tempreture Indicator) for 3.15 MVA Power Transformer suitable size all as per existing including dismantling of old unserviceable OTI complete all as specified and as directed.
S & F SRC Gaskit for 3.15 MVA Power Transformer suitable size all as per existing including dismantling of old unserviceable Gaskit complete all as specified and as directed..
M & L for carrying out following repairs in 63KVA capacity Station Transformer at NAD complete all as specified and as directed. [a] Draining out transformer in the suitable capacity of container / drums and keeping it in safe custody for reuse. [b] Lifting, transporting & handling the transformer to the work shop and opening top cover of the transformer by unscrewing nuts / bolts / washers etc. including disconnecting core assembly from HT / LT bushing and lifting the same gently with the help of crane and taking out from the shell [Container / Body] of the transformer. [c] Visual inspection of entire Core Assembly, Transformer Tank, Core Limbs, OLTC etc., locating the fault / damages. [d] Cleaning the transformer body from inside, removing deposited dirt / sludge / foreign particles etc. from the bottom / body of the transformer, cleaning with CTC and drying up the shell from inside before refilling with the Transformer Oil. [e] Cleaning and washing thoroughly core and serviceable windings of the transformer by hosing down with clean dry oil conforming to IS – 336, removing deposited dirt / sludge / foreign particles from the windings / core through inspection of windings, providing insulations to leads and terminals complete and re-assembling the core including newly winded coils etc. [f] Heating / drying / baking complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc all as per IS.
[g] Lifting and refixing core assembly inside the transformer shell gently and carefully connecting Primary / Secondary / Neutral Terminal Connections to the bushings assembly, fixing of Tap changer including tightening of nuts, bolts, washers of the core to reduce humming noise. [h] Refilling the filtered transformer oil in the shell of transformer complete. [i] Refixing the top cover including replacement of Cork Sheet / Gasket 8 mm thick tightening of nuts / bolts / washers etc. and replacement of Breather with Silica Gel. [j] Lifting / Shifting to the place from where removed and re-installing the transformer including connecting Primary / Secondary / Neutral connections etc. [k] The inspection of transformer shall involve Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts, Checking all brazing, joints, Tap heads and connection joints, Checking all jumpers, terminations / connections inside the transformer and Checking the Bulcholtz Relay / Conservator MOG if any.
M & L for dismantling the LT / HT Connections, Earthing, Control Cables carefully from the Transformer installed on Foundation of 33 KV MRS Yard at NAD and Loading the 63KVA capacity Transformer weighing minimum 500 KG by using suitable Crane on to the Transporting Trolley Vehicle, Transporting the unserviceable Transformer on Trolley Vehicle to Workshop from 33 KV MRS Yard at NAD, Loading the 63 KVA Transformer by using suitable Crane on to the Transporting Trolley Vehicle after completion of Repairs at Workshop, Transporting the unserviceable Transformer on Trolley Vehicle to 33 KV MRS Yard at NAD from Workshop and unloading and placing it on the Transformer Foundation carefully complete all as specified and as directed. Notes: [a] Any damage to insulators / bushes / windings etc. while in the custody of the contractor shall be made good at no extra cost to the Government. The serviceability of the transformer shall be checked and confirmed by the contractor before taking into his custody. [b] M & L for rewinding / re-insulation of HT / LT [Primary / Secondary] Coils, Bushes, Studs, Transformer Oil, Filtration of Oil, Cable Box, replacement of Buchholz Relay / MOG, repair / servicing of OLTC etc. will be measured and paid separately under relevant items of this BoQ.
M & L for rewinding of HT/LT Tap Winding for 33KV/415 Volt [63 KVA] Station Transformer at NAD, HV Coil [Primary Side] of any Capacity / Type by winding defective coils with new copper wire with Kraft Paper insulation as per IS of same gauge and size together with new insulated materials/bracings before placing in to the transformer and assembling the coil with new insulation materials, varnishing and fitting the coils in the chamber, testing and commissioning the transformer and recording the test results complete all as specified and as directed. Note: M & L for re-insulation of serviceable coils will be measured and paid separately under relevant items
Supply, Install, Testing and commissioning of REF 615, Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 64R, 67, 67N, 27, 59, 59N, 25, 81U, 81O, df/dt, 95, Measurement for 3I, I0, 3U, U0, Kw, KVA, PF, Hz, Kwh, 12 DI + 10 DO, One front RJ45 Port, One Rear RS485 Port for Modbus Protocol, Draw out Type with CT Shorting feature, Small LCD Display feature including taking down old relay of any description complete all as specified and as directed. [Make: Model No. REF615 of ABB Make or its equivalent in Siemens]
Supply, Install, Testing and commissioning of ABB make RET 620/615, Transformer Protection and Control Relay, Protections 87T, 64R [High and Low Impedance], 50, 51, 50N, 51N, 67, 67N, 46, 49, 37, 24, 27, 59, 59N, 81U, 81O, df/dt, 95, Measurement for 3I, I0, 3U, U0, Kw, KVA, Kwh, PF, Hz, 8 DI + 13 DO, 2 RTD Inputs, 1 mA Input, One front RJ45 Port, One Rear RS485 Port for Modbus Protocol, Draw Out with CT Shorting feature including taking down old relay of any description complete all as specified and as directed. [Make: Model No. RET620/615 of ABB make or its equivalent in Siemens]
S & F in repairs Master Trip Relay operating volt 100/ 110 V DC complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs Auxiliary Relays 30Y type VAA for Transformer Protection complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs C.B. ON/OFF/TRIP/Trip Circuit Healthy and Unhealthy/Spring Charged complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs 8 Window Annunciator complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs T‐N‐C Switch [Breaker Control Switch] complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs Trip Circuit Healthy Push Button complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs Control Wiring, colour coded complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs Test Terminal Block complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
S & F in repairs Local Remote Switch complete all as specified and as directed. Make: ABB / Siemens / Schneider / L & T
M & L for carrying out following Onsite Tests for 33 / 11 KV Transformer of any capacity with required / suitable testing equipment by Qualified and Licensed Personal, Recording Test Results and submitted to GE to keep on record duly signed by all concerned complete all as specified and as directed: [a] IR Test [b] PI [c] Magnetic Balance Test [d] Ratio test [e] Di-electric Test of Oil [f] Short Circuit Test [g] Vector Group [h] Winding Resistance
M & L for inspecting, checking, servicing of 33 KV Lightening Arrestors by decarbonising of lighting arrestors, tightening all earthing connections and HV connections for proper contact, application of petroleum jelly to the electrical connections, replacement of corroded nuts and bolts etc. complete all as specified and as directed.
M & L for inspecting, checking, servicing of 33 KV Disc / Post Top Insulator including carrying out following activities complete all as specified and as directed: [a] Checking insulator for any cracks & pitting [b] Checking Interlocking Pins for corrosion and replacing if necessary, cleaning / decarbonising with CTC. [c] Replacing the corroded, rusted nuts & bolts of clamps of conductors if necessary. [d] Tightening of all supporting connections.
M & L for Repairing / Servicing of 33 KV / 110 V PT [Outdoor type] including carrying out following activities complete all as specified and as directed: [a] Checking PT Limb[Ceramic insulator] for any cracks, pitting and burns [b] Cleaning / Decarbonising with CTC [c] Replacing insulator oil with New Oil. [d] Carrying / conducting Ratio Test. [e] Tightening all Primary and Secondary connections. [f] Tightening and fixing basement Nuts & Bolts.
M & L for Servicing of 33 / 11 KV CT [Outdoor Type] by Checking CT Limb for any cracks, pitting and burns, Cleaning / Decarbonising the Limbs with CTC, Complete drain out of old insulating oil and filling new Insulator Oil, conducting Ratio Test and Tightening all Primary and Secondary connections complete all as specified and as directed.
M & L for repairing & servicing of 33 KV Gang Operated Air Break Isolator & Earth Switch including carrying out following activities complete all as specified and as directed: [a] Cleaning of contact for dust, oxidation & pitting with CTC. [b] Cleaning of all insulators with CTC and observing any cracks and carbon deposits / contents. [c] Repairing, adjusting the rotating arms for perfect operation including lubrication with Petroleum Jelly [d] Repairing / Replacement of Tension Spring in Fixed Contacts. [e] Lubricating of all moving parts for smooth operation. [f] Checking of Auxiliary Contacts and their Calibration [g] Applying Petroleum Jelly to all Electrical Contacts / Moving Contacts. [h] Tightening of all Electrical and Mechanical Connections. Note: The rate quoted is deemed to be inclusive of Consumables like nuts & bolts, washers, petroleum jelly, CTC, T & P etc. complete and necessary safety measures for working in 33 KV Yard.
Supplying, laying and testing XLPE insulated and PVC sheathed, FRLS, GI Strip / Wire armoured heavy duty cable, ISI marked with Multistranded Copper Conductor 1100 Volt grade of size 14 Core, 2.5 Sq.mm cross section suitable for earthed system, laying in trenches / duct / fixed to poles / drawn through pipes / sleeving through pipe in duct, including suitable size Double compression copper stainless steel cable gland, crimping type cable lugs, sockets etc. including taking down old Cables of any description complete all as specified and as directed.
S & F in repairs 33 KV Lightning Arrester of discharge capacity of 10 KA station class complete all as specified and as directed.
M & L for 20mm size coarse aggregates of broken stones or boulders, deposited, spread and levelled in uniform layers and required gradient complete all as specified and as directed.
M & L for cleaning and servicing of complete HT 33 / 11 KV structure by greasing, cleaning, servicing of jumpers, re-jumpering wherever required, tightening of nuts & bolts etc. including painting with two coats of aluminium paint over a coat of zinc chrome primer on all steel surfaces from main receiving point to distribution bus bar bay structures up to transformers inside MRS complete all as specified and as directed.
M & L for Repairs / Servicing of 36 KV Outdoor VCBs of Schneider [Areva] make with mechanism and comprising of the following complete all as specified and as directed: [a] Cleaning of Vacuum Interrupter Limbs for Dust, Oxidising and Decarbonising with CTC. [b] Repair / Servicing of Spring Loaded Operating Mechanism [c] Repair / Servicing of Spring Charging Motor [d] Checking, repairing & servicing of Gearbox, Auxiliary Switches, Spring, Limit Switch etc. complete [e] Checking & Repairing Electrical and Mechanical Operations [f] Checking & Repairing Remote Closing and Tripping of VCB from 33KV Control Panel. [g] Lubrication all Moving Parts with Petroleum Jelly & cleaning all Bushing Insulators with CTC [h] Tightening of all Mechanical Connections of Mechanism [i] Tightening of all HV and LV Connection of VCB. Note: Spares required for Servicing / Repairing of 36 KV Circuit Breaker shall be measured and separately at supply only rates under respective items of this BoQ.
Supply only following spares suitable for 36 KV Outdoor Vacuum Circuit Breaker complete all as specified and as directed.
Release Lever[MVIE00123-02] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Handle Block Assembly [MVIE00137-01] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Spring Charging Motor [VDRE00100-06] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Motor Cut-off Switch [MVIE00016-01] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Main Drive Shaft Assembly [MVIE00062-01] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Rachet Wheel [[MVIJ00020-01] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Motor Cut Off Lever Assembly [MVIE00173-01] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Auxiliary Switch 6NO + 6NC [MVIG00242-01] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Trip Coil [ECO27SOG83800FN] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
Closing Coil [ECO27SN117900FN] suitable for 36 KV Outdoor VCBs of Schneider [Areva] make complete all as specified and as directed.
M & L for Control Wiring up to Control Chamber with 1 Core, 2.5 Sq.mm Multistranded Copper Conductor cable with proper ferules & appropriate Lugs including taking down old Wiring of any description complete all as specified and as directed.
Taking down HT Switchgear [Vacuum Circuit Breaker] at NAD old Sub Station, NAD Map & Dolphin Hill Map Sub Station of capacity 11 KV 250 / 350 MVA for carrying out following Repairs, Overhauling, Servicing, Preventive Maintenance and refixing the same after Repairs / Overhauling complete all as specified and as directed: [a] Tripping off the breaker, lowering the breaker with raising / lowering handle and pulling out the breaker complete from the panel along with the trolley for servicing / inspection / overhauling. [b] Servicing / Inspecting / checking of Automatic Safety Shutter operation for serviceability and replacement of spares if required. [c] Servicing / Inspecting / checking of circuit spout and circuit spout connections for RYB Phases and replacement of spares if required. [d] Dismantling and checking of Crossbar Assembly, fixed contacts and current carrying parts of the breaker, trolley, insulated assembly and checking lamination with clamps, epoxy spout, isolator assembly etc. [e] Setting, reassembling, cleaning, adjustment of fixed contacts, main contact, arcing contacts and chamber baffle pot assembly, moving contact for proper setting of auxiliary contacts operating mechanism. [f] Servicing / Inspecting / checking of Secondary Sockets / Busbar Earthing Plugs / Earthing Sockets and replacement of spares if required. [g] Checking, setting and adjustment of lowering and raising operation of the Breaker Trolley. [h] Decarbonising of Busbar and connected items
[i] Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating and closing of shutter gear, isolation resistance of trolley of with vacuum interrupter assembly. [j] The inspection of HT switch gear shall involve Inspection of Truck & Hoist Assembly, Tank Assembly & Barriers, Assembly & components of Solenoid Assembly, Assembly & components of Dependent Mechanism, Assembly & components of Spring Box Mechanism, Motor Mechanism Spring Charge Assembly and Assembly of Trip Unit & related components [k] The servicing includes busbar duct chamber, cable alleys and connecting accessories. [l] The rate quoted shall be deemed to be include for necessary T & P, nuts, bolts, washers, gasket, insulation tape, compound, painting of VCB Panels with approved colour including lettering details all as per existing etc. to put in to the VCBs and Panels in serviceable condition, testing and commissioning all as specified and as directed. [m] Major spares like Breaker Bushings, Vacuum Interrupter Assembly, Busbar Spout, Busbar Spout Connections, Circuit Spout / Circuit Spout Connections / Buffer Fixed Contacts, Moving Contacts, Tank Assembly / Barriers, Solenoid Spares, Dependent / Spring Mechanism / Motor Mechanism, Trip Unit etc. will be measured and paid separately at supply only rates under relevant items of this BoQ. However the rate quoted shall be deemed to be include for any other minor spares requires replacement. [n] The servicing shall be carried out by Authorised Service Centre as approved by GE.
Supply only following spares suitable for 400 to 800 Amps, 250 MVA to 450 MVA HT Switchgear VCB's and 11 KV HT Panel complete all as specified and as directed.
CTs Ratio: 150-75 / 5+5A, Core 1: 15 VA CL-0.5, Core - 2: 15 VA CL -5P 10, STC: 40 KA for 1 Sec B.1/L: 12 KV / 28 KV/ 75 KV, Mould: GWP6/1, IS 2705, Secondary ON P2 Side [VCB Panel : 35087011327/02/1]
PVC insulated, unsheathed Multistranded Flexible Copper Conductor Cable of size 1.5 Sq.mm, FRLS, ISI marked, 1100 Volt Grade.
PVC insulated, unsheathed Multistranded Flexible Copper Conductor Cable of size 2.5 Sq.mm, FRLS, ISI marked, 1100 Volt Grade.
Shunt Trip Coil 110 Volts DC / 220 Volts DC
Isolating Contact Flat type
Breaker Control Switch
Busbar Spout
Circuit Spout
Control Circuit Fuses 2 Amps to 63 Amps
HRC Fuse [PT HT Side]
PT Plug Contact
Multi Function Meter, Digital Type [Displaying A, V, PF, Hz, KVA, KW, KVAR, KWH, KVARH etc. Class 1.0 / 0.5]
VCB Buffers
110 Volts DC Closing Coil Assembly
Push to Trip Knob Red Assembly
Push to Trip Knob Green Assembly
Ratchet Wheel
Rack/ Rack out Handle- Motor spring charging handle
Limit Switch 1NO + 1NC – Service / Test Position
Bus bar support Insulator for VCB Panel
Tripping Coil 110 Volts DC [PC VCB Spares]
Spring Charging Motor with Gearbox Universal Motor with Gearbox 230 AC / DC [Magna Make]110V AC / DC [PC VCB spares]
Rectifiers suitable for Areva VCB's for Spring Charging Motor
Vacuum Interrupter Type VG2
Epoxy Body
Drive Beam
Thermostate for Spare Heater
Dismantling Existing earthing and providing new Maintenance Free Chemical Earthing complete with 40mm X 3000mm Advance Chemical Earthing Pipe with [Strip in pipe Technology] with 50 KG of Backfill Compound buried directly in ground [Rocky Soil] with earth pit not less than 2.25 m deep below ground level with top edge of Plate not less than 1.50 m below normal ground level connected to existing Copper Earth Strip by means of Stainless Steel bolts, nuts, check nuts and washers all as per IS – 3043 including testing on completion complete all as specified and as directed. The earth resistance shall be measured using fall of potential method as per Para 37 of IS – 3043 & combined resistance should be less than 1 Ohms. Note: The unit rate quoted shall be deemed to include for PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS handle 12mm dia, earth work excavation, return filling, removal of surplus soil etc. complete all as specified and as directed.
S & F in repairs Space Heater in HT VCB, 11 KV suitable for operation on 220 Volts, AC Supply complete with necessary wiring and control cable with Toggle Switch complete all as specified and as directed.
M & L for inspection, testing, fault detection and Servicing of 11 KV , 1450 KVAR APFC capacitor bank at NAD by authorised technician of OEM on site including replacing minor spare items complete all as specified and as directed. Note:-(i)Cost of visit of technician is deemed to be included in the quoted rate. (ii)Major spares required for repairs to APFC Panel shall be measured and paid separately at supply only rates.
Supply only 80.06 KVAR, Externally Fused Capacitor Unit complete all as specified and as directed.
Supply only 11 KV, Series Reactor Air core Dry type , Class F Aluminium wound , 1Ph , 0.2% complete all as specified and as directed.
Supply only 11 KV, 400A, 10KA for 1 Sec, 3 Phase Vacuum Contactor complete all as specified and as directed.
Supply only 11 KV/110V-190V, 50-50VA, 3 Ph, Resin Cast RVT complete all as specified and as directed.
Supply only 11 KV HT HRC fuses of suitable current rating complete all as specified and as directed.
Supply only APFC Relay(RS485/232 Communication port) complete all as specified and as directed.
Supply only PVC insulated sheathed multistranded Copper conductor cable 1100 V, Single Core 4 Sqmm as in control wiring from APFC relay to capacitor bank unit all as per OEM specification all complete as directed.
Supply only PVC insulated sheathed multistranded Copper conductor cable 1100 V, Single Core 2.5 Sqmm as in control wiring from APFC relay to capacitor bank unit all as per OEM specification all complete as directed.
Supply only Multi Function Meter complete all as specified and as directed.
Supply only 50mm x 6mm Aluminium Insulated Bus bar limb complete all as specified and as directed.
Supply only Sunthetic resin cast Insulated of Bus bar complete all as specified and as directed.
Supply only of Silicon-Coat 570 RTV Silicone High Voltage Insulator coating solution total 11 KV Indoor VCB panel (6.8 Kg coating materials per panel) complete all as specified and as directed.
Inpection, testing servicing and overhauling of Factory made 11KV ,630 Amps, 21 KA for 3 Second SF 6 insulated motorized, outdoor RMU consistng of 2 Nos VCB Incoming and 4 Nos VCBs outgoing including replacing of minor spares complete all as specified and as directed. Note:-Major items are paid separately at Supply only rates.
Supply only Trip coil from RMU of suitable make complete all as specified and as directed.
Supply only Closing coil from RMU suitable make complete all as specified and as directed.
Supply only Isolator Switch position indicator from RMU suitable make complete all as specified and as directed.
Supply only Lithium battries for RMU suitable make complete all as specified and as directed.
Supply only Plug in type bushings 630 Amps of RMU suitable make complete all as specified and as directed.
Supply only VPIS (Voltage presence indicator system) standard 3.3 to 7.6 KV from RMU of suitable make complete all as specified and as directed.
S & F in repairs Drive Mechanism of RMU complete all as specified and as directed.
M & L for transporating of 5 way RMU of any description and type from sub station to workshop (OEM Factory) including Top up of of SF6 gas and one coat of Synthetic enamel painting complete all as specified and as directed.
M & L for transporating of 6 way RMU of any description and type from sub station to workshop (OEM Factory) including Top up of of SF6 gas and one coat of Synthetic enamel painting complete all as specified and as directed.
MURALI KRISHNA ASSOCIATES
Venkateswara Electricals
K KUMAR RAJA PROJECTS P LIMITED
surendra infrastructure pvt ltd
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .