Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | First₹45.2 LAccepted-AOC | ₹45.2 L | First | Accepted-AOC Responsive |
| 2 | Second₹45.4 LRejected-AOC T STATE BANJARAWALA DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹45.4 L | Second | Rejected-AOC Non- Responsive |
| 3 | Rejected-Technical | - | - | Rejected-Technical Non-Responsive |
| Sl No | Description | Qty | Unit | SAINKO SYSTEMS L1 | SHREE BALAJI ASSOCIATES L2 |
|---|---|---|---|---|---|
| 1.00 | Supplying,of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : (a) Horizontal type, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration padsCapacity 2850 LPM 70 m Head at 7.0 Kg/cm2 delivery pressure for Fire Hydrant Network. | 1 | Set | 4,28,000 ₹4.3 L | 4,30,000 ₹4.3 L |
| 2.00 | Supplying,of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.Suitable HP, water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.Capacity 2850 LPM 70 m Head at 7.0 Kg/cm2 delivery pressure for Fire Hydrant & Sprinkler Network. | 1 | Set | 6,48,000 ₹6.5 L | 6,50,000 ₹6.5 L |
| 3.00 | Supplying, of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads Capacity 180 LPM 70 m Head at 7.0 Kg/cm2 (Jockey Pump). | 1 | Set | 1,05,000 ₹1.1 L | 1,08,000 ₹1.1 L |
| 4.00 | Designing, Supply, of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification (INCOMER & METERING) 400A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Bus Bar 500Amps (OUTGOING) (a) MAIN FIRE PUMP- 125 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets (b) JOCKEY PUMP 63 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets (c) DIESEL ENGINE CONTROL Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter | 1 | Set | 2,55,000 ₹2.5 L | 2,60,000 ₹2.6 L |
| 5.00 | Supplying,of 0 to 12 Kg/ cm2 ON/OFF pressure switch in delivery line of pump along with control wiring for auto starting and auto stopping of hydrant and jockey pumps. | 3 | Each | 1,560 ₹4,680 | 1,550 ₹4,650 |
| 6.00 | Supply, of hydrants all complete as required and as approved M.S. fire hose cabinet (750x600x250) made out of 16 gauge M.S. sheet capable of accommodating hose pipes, fitings & accessories. The box shall have a front glass door with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) - for external hydrant. | 30 | Each | 6,000 ₹1.8 L | 6,100 ₹1.8 L |
| 7.00 | 63mm dia single outlet SS landing valve IS marked with suitable size bolts, nuts, washers and gaskets. | 30 | Each | 6,400 ₹1.9 L | 6,500 ₹1.9 L |
| 8.00 | 63mm reinforced rubber hoses (RRL) with male and female SS coupling, IS marked- 15 m long | 60 | Each | 4,550 ₹2.7 L | 4,600 ₹2.8 L |
| 9.00 | Supply of ss orifice plates in pipelines to reduce pressure from 8 kg. to 3.5 kg/sq.cm. | 30 | Each | 1,360 ₹40,800 | 1,350 ₹40,500 |
| 10.00 | Providing of fire brigade inlet connection (fire department connection) consisting of 4 Nos. 63 mm dia instantaneous inlet arranged on a 50 mm dia header, 4 way 15 mm dia | 1 | Set | 50,000 ₹50,000 | 51,000 ₹51,000 |
Tender Value
₹45.5 L
EMD Value
₹91,000
Closing Date
16 Sept 2025, 3:00 pmClosed
Project Manager
BRIDCUL Office, Rautela Colony, Mukhani Haldwani
SUPPLY WORK OF FIRE FIGHTING SYSTEM FOR LEESA DEPO HANUMAN GARI, GOLAPAR, KATHGODAM, DISTRICT- NAINITAL
2025_BRID3_86822_1
BRIDCUL/HLD/01/2025-26
Open Tender
Electrical Works
150 days
GOLAPAR, KATHGODAM
Please refer Tender documents.
3 documents required · 3 mandatory
₹4,130
Project Manager
₹91,000
BRIDCUL Office, Rautela Colony, Mukhani Haldwani
9 Dec 2025
2 Sept 2025
16 Sept 2025
2 Sept 2025
16 Sept 2025
10 Sept 2025
8 Sept 2025
Amount
Supplying,of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : (a) Horizontal type, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration padsCapacity 2850 LPM 70 m Head at 7.0 Kg/cm2 delivery pressure for Fire Hydrant Network.
Supplying,of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.Suitable HP, water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.Capacity 2850 LPM 70 m Head at 7.0 Kg/cm2 delivery pressure for Fire Hydrant & Sprinkler Network.
Supplying, of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads Capacity 180 LPM 70 m Head at 7.0 Kg/cm2 (Jockey Pump).
Supplying,of 0 to 12 Kg/ cm2 ON/OFF pressure switch in delivery line of pump along with control wiring for auto starting and auto stopping of hydrant and jockey pumps.
Supply, of hydrants all complete as required and as approved M.S. fire hose cabinet (750x600x250) made out of 16 gauge M.S. sheet capable of accommodating hose pipes, fitings & accessories. The box shall have a front glass door with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) - for external hydrant.
63mm dia single outlet SS landing valve IS marked with suitable size bolts, nuts, washers and gaskets.
63mm reinforced rubber hoses (RRL) with male and female SS coupling, IS marked- 15 m long
Supply of ss orifice plates in pipelines to reduce pressure from 8 kg. to 3.5 kg/sq.cm.
Providing of fire brigade inlet connection (fire department connection) consisting of 4 Nos. 63 mm dia instantaneous inlet arranged on a 50 mm dia header, 4 way 15 mm dia
Supply of Butterfly Valves of rating PN 1.6 with mating flanges generally as specified all complete. 150 nominal bore
Supply of Butterfly Valves of rating PN 1.6 with mating flanges generally as specified all complete. 100 nominal bore
80 nominal boreSupply of Butterfly Valves of rating PN 1.6 with mating flanges generally as specified all complete.
Providing of cast iron non-return valve of rating PN 1.6 dule ISI marked with flanges generally as specified complete 150 nominal bore
Providing of cast iron non-return valve of rating PN 1.6 dule ISI marked with flanges generally as specified complete 200 nominal bore
Supply,of double flanged 'Y' strainers with M.S. body and SS 40-grade mesh strainer. generally as specified complete 80 mm nominal bore
Supply,of double flanged 'Y' strainers with M.S. body and SS 40-grade mesh strainer. as specified complete 150 nominal bore
Supply, of Pressure vessels 450mm diameter and 1000mm high fabricated from 8-10mm M.S. plate with accessories inside painting with epoxy paint and outside with enamel.
Providing, of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.8 Kg/cm2 and test pressure 14 Kg/cm2 for :- 150 mm dia
Providing, of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.8 Kg/cm2 and test pressure 14 Kg/cm2 for :- 80 mm dia
Supply of tripple purpose nozzles made of ss capable of jet and spray operation with instaneous type 63 mm dia coupling complete
Supply of Foam monitor 63 mm dia flow 1750 to 4000 lpm fitted on pipe line at designated locations. Complete
Supply of mobile foam unit Trolley : Steel EPE Powder Coating Tank : Fibre Glass or Stainless Steel Inductor : 0% - 6% at 225 Lt/Min Foam Branchpipe : Aluminum Alloy Male Instantaneous Connection to BS 336 Hose : One/Two length of 63mm X 15 meter Fire Hose. capacity 100 lits of low expansion foam
SHREE BALAJI ASSOCIATES (BID ID -397677)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid