Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.1 LAccepted-AOC COLLEGE CHOWMUHANI JIRANIA WEST TRIPURA | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹34.4 L+₹4.2 L (14.0%)Rejected-Finance AMARPUR GOMATI TRIPURA | AMARPUR | GOMATI | TRIPURA | L2 | Rejected-Finance L2 | |
| 3 | L3₹38.3 L+₹8.1 L (26.9%)Rejected-Finance POST OFFICE ROAD DHARMANAGAR DHARMANAGAR NORTH TRIPURA | NORTH TRIPURA | TRIPURA | 799250 | L3 | Rejected-Finance L3 | |
| 4 | L4₹39.7 L+₹9.5 L (31.6%)Rejected-Finance | L4 | Rejected-Finance L4 |
Tender Value
₹39.5 L
EMD Value
₹79,033
Closing Date
17 Apr 2025, 3:00 pmClosed
DGM
O/o the Dy. General Manager, ED- Khowai, Officetilla, Khowai
Installation of new 11KV Feeder (VIP Feeder) and extension of HT/LT line in/c construction of 2X200 KVA Sub- Station for providing 3-Phase, 4-wire new service connection to newly constructed VIP Residential Complex Building at Dhalabil Colony within
2025_POWER_60214_1
DGM/ED-KH/2024-25/06, Dt. 27.03.2025
Open Tender
Electrical Works
Turn-key
60 days
Dhalabil, Khowai
As per NIT
2 documents required · 2 mandatory
₹5,000
₹79,033
Khowai
15 May 2025
10 Apr 2025
17 Apr 2025
10 Apr 2025
17 Apr 2025
11 Apr 2025
10 Apr 2025 - 11 Apr 2025
11 Apr 2025
Amount
Supply of the following
ACSR Weasal (6/1/2.59mm)
PVC CABLES (SINGLE CORE) 120 mm2
XLPE CABLE (HT) 3Cx120 sq. mm
LT AERIAL BUNCHED CABLE 3x50+1x16+1x35 sq.mm
ACCESSORIES OF LT AERIAL BUNCHED CABLE IPC Main 16-95 Sq. mm & Tap 4 to 35(50) Sq. mm
ACCESSORIES OF LT AERIAL BUNCHED CABLE -Eye Hook
ACCESSORIES OF LT AERIAL BUNCHED CABLE - Pole clamp (25/50 mm)
Rewireable Porcelain Cut out 200 Amp
11KV Polymer composite 45 KN Disc Insulator
11KV Polymer Pin Insulator
11 KV Stay insulator
11KV Disc fittings Up to 7/3.8mm, 2-U Bolt type
Stay set complete
GI Stay wire stranded stay wire 7-4mm
NUTS AND BOLTS (Assorted)
DANGER PLATE H.T.
DANGER PLATE L.T.
LUGS 120 mm2 - 12
GI Stay clamp 50x6mm
Suspension clamp Assembly with straps & buckle (25-50 mm)
Dead end clamp Assembly with straps & buckle (25-50 mm)
11 KV Gang Operated Switch (Porcelin type)
11 KV Drop out Switch (Porcelin)
11 KV Covered Conductor (70 SQMM)
11KV VCB Panel rated Voltage 11KV-12KV, Rated Current 630A 800 1250 A, Nos of Pole 3 Poles, Frequency 50Hz with supply of power pack battery
9 Mtr long Steel Tubular Pole 410 SP 28, Top & Middle pole painted with red oxide primer and bottom section Hot Dip Galvanised
8 Mtr long Steel Tubular Pole 410 SP 15, Top & Middle pole painted with red oxide primer and bottom section Hot Dip Galvanised
Aluminium Lugs 70mm sq
Aluminium Lugs 95mm sq
Aluminium Lugs 120mm sq
Aluminium Lugs 185 sq mm
Distribution Box 3 phase
MS Channel(100x50x50x6mm)
MS Channel(75x40x40x6mm)
MS Angle(65x65x6mm)
GI Strip 25x3mm for DTR Earthing
PVC Sleeves
Erection
Erection of 9 mtrs length of Steel Tubular POLE at any kind of soil , including excavation of earth, refilling the pit with soil upto the ground level, ramming and making complete in all respect.
Erection of 8.0mtrs length of Steel Tubular POLE at any kind of soil , including excavation of earth, refilling the pit with soil upto the ground level, ramming and making complete in all respect.
Erection of Stay set direct in earth complete with 19mm x 1800 mm long stay rod, anchor plate of size 300 x 300 x 8 mm ,thimble, turn buckle, 7/3.15 mm dia G.I Standed stay wire and stain insulator etc. with Supply of M.S.Clamp,Nuts & Bolts etc. as required. and making complete in all respect
Erection of M. S. Angle Cross-Arm, 1.5 to 2.5 Mtr. Long 65x65x6mm (Excluding the cost of Bracket Clamp, Nuts & Bolts)
Erection of M. S. Channel Cross-Arm, 0.3 to 2.8 Mtr. Long 75x40x40x6mm (Excluding the cost of Bracket Clamp, Nuts & Bolts)
Erection of M. S. Channel Cross-Arm, 2.8 Mtr. Long 100x50x50x6mm (Excluding the cost of Bracket Clamp, Nuts & Bolts)
Erection of 11KV Pin insulator along with Pin.
Erection of 11KV Single Disc insulator set along with necessary fittings
Earthing with G.I pipe 2.5mtr. Long and 40mm dia, including excavation, refilling with alternate layer of salt & Charcoal as per drawing (excluding supply of G.I.Pipe, Salt & Charcoal, Gi wire, nuts &boIts, etc. as required)
Laying of 8 SWG GI wire at 300mm below the ground level for earthing of Sub-Station equipments from the earth electrode
Erection of DANGER PLATE on OH lines (11KV/415VoIts)
Fabrication of Cross-Arms by MS Channel/MS Angle as per specification
Laying and Stringing of 1KM (Single Conductor) ACSR 6/1/2.59 mm dia WEASEL including hoisting and binding etc. Complete as required.
Erection of 9KV, 5KA single pole metal oxide gapless type LA, including necessary connection complete as per technical specification
Erection of 11KV DOF unit set of three nos. including necessary connection complete as per technical specification. (Excluding the cost of back clamp, Nuts & Bolts)
Erection of 11KV 200 Amp. GOS unit set of three nos. including necessary connection complete as per technical specification.(Excluding the cost of back cIamp,Nuts & Bolts)
Installation/Positioning of 11/0.430KV,3-Phase 200KVA to 250KVA of Distribution Transformer on Pole with necessary connections & fitting fixing of all allied accessories components as required for making complete in all respect for energizing.
Carriage of 11/0.430, 3-Phase 200KVA/250KVA by Mechanical Transport from the Site / Store/ Worshop to working site Vis-a-vis including loading, unloading and placing on base, as required,b) Beyond 25 KM upto the lead of 50KM From MMD Store to Sub Division Store
Fitting-Fixing of Service main 1/3Phase distribution Box of 1.1 KV grade on PCC/Steel Pole with the help Pole brackets or Steel Straps & buckIes as per direction of Engineer-In-Charge.
Supplying and Making Indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as requiredUp to 150sqmm
Fixing of cut out (Set of 3nos)on wooden plank (preferably korai wood) of size 24"x10"x1.5"&cable connection with termination by lugs/thimbels) complete (i/c. supply of wooden plank, screws & M.S. clamp excluding cost of thimble)
Supply of febricated clamps of assorted size of MS flat (50x 6mm) with double coat of red oxide primer coating.
Supply of 2.5mtr. Long, 40mm dia G.I.Pipe, Make: TATA / JINDAL)
Supply of 60Kg Salt & 55Kg Charcoal ( For 1 Pit).
Positioning of cable drum, removing of cable from drum and laying, hoisting & drawing of AB Cable 3X50+1x16+1x35 sqmm as per direction of Engineer-In-charge.
Erection & Fitting-Fixing of Insulated suspention Clamp including Pole clamp, Eye hook for cable massenger of 1.1 KV grade on PCC/Steel Pole with the help Pole brackets or Steel Straps &buckIes asper direction of Engineering In-Charge.
Grouting of Steel Tubular PCC Pole of ratio 1:2:4 (1cement:2 riversand:4 Jhama brick Aggregate of 20mm. Nominal size) including supply of cement, sand and brick aggregate. Complete with excavation, refilling of each, ramming along with centering and shuttering as required
Maintaining adequate clearance from overhead live conductors by Trimming of tree branches for Way Leaves
Erection & Fitting-Fixing of Insulated Dead end enchoring Clamp including Pole clamp, Eye hook for cable massenger of 1.1 KV grade on PCC/Steel Pole with the help Pole brackets or Steel Straps &buckIes asper direction of Engineering In-Charge.
Supplying and Making Outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as requiredUp to 150sqmm
11KV VCB panel for outgoing feeder complete - For replacment / Extension in existing 11 kV feeder panel incuding fitting and fixing, cable terminations, bus extensions, adopter panel (if required) and including all accessories complete.R&M of 33/11kV SS
Civil work for construction of Transformer base and Fencing of Hard drawn steel wire fabric as per requirement and direction of Engg. In Charge
Stringing of 11KV Covered Conductor 70 sqmm (all 3 phases) as per specification and approved drawings, stringing of covered conductors at proper tension/ sag, fitting and fixing of all accesories Piercing Connectors , Jointing Sleeves, insulator binding using approved Non-metallic helical ties, jumpering, connections to other lines etc. complete in all respect.
Laying of PVC insulated and PVCsheathed / XLPE power cable of 11KV grade (120 Sq mm) in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Trench size: Width: 350 mm, Height: 1200 mm / Sand (Cushioning): Height: 250 mm, Width: 350 mm / Protection: Double layer bricks
UTTAM NAG (BID ID -172867)
NIKHIL DAS (BID ID -172962)
Dilip Kumar Kar (BID ID -172900)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .