Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Technically not qualified |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
25 Mar 2023, 6:00 pmClosed
Manager Projects
KEL Kochi
Construction of KUFOS Staff quarters 2nd to 6th floor - Electrical Works
2022_KEL_539537_4
KRO/ BDC/1280/2022
Open Tender
Electrical Works
Item Rate
720 days
KEL Kochi
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,900
₹50,000
Yes
25 Apr 2023
17 Mar 2023
27 Mar 2023
17 Mar 2023
25 Mar 2023
17 Mar 2023
17 Mar 2023 - 24 Mar 2023
Amount
ELECTRIFICATION WORKS
od262568/2022_2023 : DG SET<br>Installation, Testing and Commissioning of 200KVA, 3 Phase 415V, 0.8 power factor, comprising of diesel engine, fuel tank, alternator, base plate radiator, control panel with MCCB starting equipment exciter, home silencer and all necessary accessories etc. complete as required.(Including Acoustic Enclosure). This scope also includes the testing of Energy Meter, CTs, Relays etc and obtaining test certificate from KSEB / Electrical Inspectorate. (*All Statutory fees should be remitted by the Client / Consumer or it should be reimbursed on the submission of supporting documents).<br>
od262569/2022_2023 : SWITCH BOARDS<br>SB - 1 (EB Supply)<br>Supply, installation, testing & commissioning of cubicle type Switch Board Panel suitable for 415 V, 3 Phase, 4 wire, 50 Hz AC supply system having sufficient front surface area fabricated in compartmentalised design from CRCA sheet <br>steel of 2mm thick for frame work and covers, 3mm thick for gland, plates cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 800Amps capacity extensible type TPN Aluminum alloy bus <br>bars of high conductivity, DMC / SMC / FRP bus bar supports, with short circuit withstand capacity of 31 MVAfor 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in<br>transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 6 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AL. bus bars and control<br>wiring with 1.5 sq. mm. PVC insulated FRLSH copper conductor cables, cable alleys etc. The panel shall conformto Electrical Inspectorate & KSEB standards and it shall only be manufactured after getting approval from Electrical<br>Electrical Inspectorate, KSEB and the consultant.<br>Busbar<br>1 Runs of 63 x 10mm AL.Busbar for each Phase<br>1 Runs of 40 x 10mm AL.Busbar for Neutral<br>Incomer<br>1 Nos - 400A 36kA 4P Microprocessor based MCCB with ROM, Spreader & Shunt Release 1 Set - RYB Indication lamps with Control MCBs <br>3 Nos - 400/5A CL:1, 10VA CT<br>1 Nos - 400/5A CL:1, 10VA CT with control wiring for adding APFC Panel in Future<br>1 Nos - Digital Multifunction Meter measuring V, A, F, KWH, KVA, PF with Control MCBs<br>1 Nos - Earth Leakage Relay with CBCT<br>Surge Protection Device<br>1 Nos - 8 Module DIN Rail Mounting Type 1 + Type 2 /Class 1 + class II 100kA SPD on the incoming side of EB Supply with all necessary accessories etc. complete as as required. The connections to RYB Phases, Neutral and<br>Earth shall be done using 16 Sq.mm FRLSH Single Core Flexible Copper Conductor Cables with less than 0.45m in length.<br>Outgoings <br>1 Nos - 250A 25kA 4P Thermal magnetic type MCCB having 70 to 100% setting provision with ROM, Spreader,Digital Multifunction Meter measuring V, A, F, KWH, KVA, PF with Control MCBs and CTs 2 Nos - 200A 25kA 4P Thermal magnetic type MCCB having 70 to 100% setting provision with ROM, Spreader,<br>Digital Multifunction Meter measuring V, A, F, KWH, KVA, PF with Control MCBs and CTs<br>3 Nos - 160A 25kA 4P Thermal magnetic type MCCB having 70 to 100% setting provision with ROM, Spreader,Digital Multifunction Meter measuring V, A, F, KWH,KVA, PF with Control MCBs and CTs.<br>
od262570/2022_2023 : SB - 2 (DG Supply)<br>Supply, installation, testing & commissioning of cubicle typeSwitch Board Panel suitable for 415 V, 3 Phase, 4 wire, 50 Hz AC supply system having sufficient front surface area fabricated in compartmentalised design from CRCA sheet <br>steel of 2mm thick for frame work and covers, 3mm thick for gland, plates cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 800 Amps capacity extensible type TPN Aluminum alloy bus <br>bars of high conductivity, DMC / SMC / FRP bus bar supports, with short circuit withstand capacity of 31 MVAfor 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in<br>transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 6 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AL. bus bars and control<br>wiring with 1.5 sq. mm. PVC insulated FRLSH copper conductor cables, cable alleys etc. The panel shall conform to Electrical Inspectorate & KSEB standards and it shall only be manufactured after getting approval from Electrical<br>Inspectorate, KSEB and the consultant.<br>Busbar<br>1 Runs of 63 x 10mm AL.Busbar for each Phase<br>1 Runs of 40 x 10mm AL.Busbar for Neutral<br>Incomer<br>1 Nos - 400A 36kA 4P Microprocessor based MCCB with <br>ROM, Spreader & Shunt Release1 Set - RYB Indication lamps with Control MCBs <br>3 Nos - 400/5A CL:1, 10VA CT<br>1 Nos - Digital Multifunction Meter measuring V, A, F, <br>KWH, KVA, PF with Control MCBs<br>1 Nos - Earth Leakage Relay with CBCT<br>Surge Protection Device<br>1 Nos - 8 Module DIN Rail Mounting Type 1 + Type 2 /Class 1 + class II 100kA SPD on the incoming side of DG<br>Supply with all necessary accessories etc. complete as as required. The connections to RYB Phases, Neutral and Earth shall be done using 16 Sq.mm FRLSH Single Core Flexible Copper Conductor Cables with less than 0.45m in<br>length.<br>Outgoings <br>1 Nos - 200A 25kA 4P Thermal magnetic type MCCB having 70 to 100% setting provision with ROM, Spreader,Digital Multifunction Meter measuring V, A, F, KWH, KVA, PF with Control MCBs and CTs1 Nos - 160A 25kA 4P Thermal magnetic type MCCB having 70 to 100% setting provision with ROM, Spreader,<br>Digital Multifunction Meter measuring V, A, F, KWH, KVA, PF with Control MCBs and CTs.2 Nos - 125A 25kA 4P Thermal magnetic type MCCB having 70 to 100% setting provision with ROM, Spreader,Digital Multifunction Meter measuring V, A, F, KWH, KVA, PF with Control MCBs and CTs 2 Nos - 100A 25kA 4P Thermal magnetic type MCCB having 70 to 100% setting provision with ROM, Spreader,<br>Digital Multifunction Meter measuring V, A, F, KWH, KVA, PF with Control MCBs and CTs.<br>
od262572/2022_2023 : METERING PANEL<br>MP - 1<br>Supply, installation, testing & commissioning of cubicle typeMetering Panel suitable for 415 V, 3 Phase, 4 wire, 50 Hz AC supply system having sufficient front surface area fabricated in compartmentalised design from CRCA sheet <br>steel of 2mm thick for frame work and covers, 3mm thick for gland, plates cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 400 Amps capacity extensible type TPN Aluminum alloy bus <br>bars of high conductivity, DMC / SMC / FRP bus bar supports, with short circuit withstand capacity of 31 MVAfor 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 6 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AL. bus bars and control<br>wiring with 1.5 sq. mm. PVC insulated FRLSH copper conductor cables, cable alleys etc. The panel shall conformto Electrical Inspectorate & KSEB standards and it shall only be manufactured after getting approval from Electrical<br>Inspectorate, KSEB and the consultant.<br>Busbar<br>1 Runs of 25 x 10mm AL.Busbar for each Phase<br>1 Runs of 25 x 10mm AL.Busbar for Neutral<br>There shall be KSEB Sealing Provision of Busbar Chamber.<br>Incomer <br>1 Nos - 160 4P Isolator<br>1 Set - RYB Indication lamps with Control MCBs There shall be KSEB Sealing Provision of Incomer Isolator Compartment.<br>Surge Protection Device<br>1 Nos - 4 Module DIN Rail Mounting Type 1 + Type 2 /Class 1 + class II 100kA SPD on the incoming supply side with all necessary accessories etc. complete as required. The connections to RYB Phases, Neutral and Earth shall be done using 10 Sq.mm FRLSH Single Core Flexible Copper Conductor Cables with less than 0.45m in length.<br>Outgoing Compartment - 1<br>7 Nos - Provision for fixing Three Phase Energy Meter There shall be KSEB Sealing Provision of Metering Compartment Door.<br>Outgoing Compartment - 2<br>21 Nos - 63A Bakelite Fuse Unit with HRC Fuse of suitable rating<br>7 Nos - 63A Neutral Link<br>7 Nos - 40A 4P C Curve MCB<br>7 Nos - ACCL <br>Wiring <br>All wiring and connections shall be done from Busbar to Energy Meters, From Energy Meters to Fuses & Neutral Links, From Fuses & Neutral Links to MCBs, From MCBs to ACCL etc. using 6.0 Sq.mm FRLS Single Core Flexible Copper conductor cables. <br>ACCL Specification<br>45A Micro Controller based full load changeover system (EB to DG & DG to EB) in Metal Enclosure with 1 Nos 45A 4P Power Contactor (AC1) in EB Side and 1 Nos 45A 4P contactor (AC1) in DG Side, 2 Nos 10A Auxiliary Contacts for contactor interlocking, 100A Elmex connectors for making connections in EB Side, DG Side and load etc. complete as required. All the internal wirings shall be done using 6.0 Sq.mm Single Core Flexible Copper conductor cables. <br>
od262573/2022_2023 : MP - 2<br>Supply, installation, testing & commissioning of cubicle typeMetering Panel suitable for 415 V, 3 Phase, 4 wire, 50 Hz AC supply system having sufficient front surface area fabricated in compartmentalised design from CRCA sheet <br>steel of 2mm thick for frame work and covers, 3mm thick for gland, plates cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 400 Amps capacity extensible type TPN Aluminum alloy bus bars of high conductivity, DMC / SMC / FRP bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 6 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AL. bus bars and control wiring with 1.5 sq. mm. PVC insulated FRLSH copper conductor cables, cable alleys etc. The panel shall conform to Electrical Inspectorate & KSEB standards and it shall only be manufactured after getting approval from ElectricalInspectorate, KSEB and the consultant.<br>Busbar<br>1 Runs of 25 x 10mm AL.Busbar for each Phase<br>1 Runs of 25 x 10mm AL.Busbar for Neutral<br>There shall be KSEB Sealing Provision of Busbar Chamber.<br>Incomer <br>1 Nos - 160 4P Isolator<br>1 Set - RYB Indication lamps with Control MCBs <br>There shall be KSEB Sealing Provision of Incomer Isolator<br>Compartment.<br>Surge Protection Device<br>1 Nos - 4 Module DIN Rail Mounting Type 1 + Type 2 /Class 1 + class II 100kA SPD on the incoming supply side with all necessary accessories etc. complete as required. The connections to RYB Phases, Neutral and Earth shall be done using 10 Sq.mm FRLSH Single Core Flexible Copper Conductor Cables with less than 0.45m in length.<br>Outgoing Compartment - 1<br>7 Nos - Provision for fixing Three Phase Energy Meter There shall be KSEB Sealing Provision of Metering Compartment Door.<br>Outgoing Compartment - 2<br>21 Nos - 63A Bakelite Fuse Unit with HRC Fuse of suitablerating<br>7 Nos - 63A Neutral Link<br>7 Nos - 40A 4P C Curve MCB<br>7 Nos - ACCL <br>Wiring <br>All wiring and connections shall be done from Busbar to Energy Meters, From Energy Meters to Fuses & Neutral Links, From Fuses & Neutral Links to MCBs, From MCBs to ACCL etc. using 6.0 Sq.mm FRLS Single Core Flexible <br>Copper conductor cables. <br>ACCL Specification<br>45A Micro Controller based full load changeover system (EB to DG & DG to EB) in Metal Enclosure with 1 Nos 45A 4P Power Contactor (AC1) in EB Side and 1 Nos 45A 4P contactor (AC1) in DG Side, 2 Nos 10A Auxiliary Contacts for contactor interlocking, 100A Elmex connectors for making connections in EB Side, DG Side and load etc. complete as required. All the internal wirings shall be done using 6.0 Sq.mm Single Core Flexible Copper conductor cables. <br>
od263829/2022_2023 : 400A TP MCCB WITH CONTACTOR<br>Supply and installation of 400A TP Microprocessor based MCCB with 400A 4P Power Contactor (AC3) with all its accessories in the existing MSB Panel Board complete with connections using additional bus bars with sleeves, nut bolt and spring washers etc. complete as required after the dismantling of existing 200A TPN FN Isolator. The scope also includes the complete control wiring to contactor so as to ensure that the supply is ON when there is EB Supply only.<br>
od263830/2022_2023 : DISTRIBUTION BOARD<br>Supply and fixing of following ways surface / recess mounting, vertical type, 415 V, TPN MCCB distribution board of sheet steel, dust protected, duly powder coated, inclusive of 200A tinned copper bus bar, common neutral<br>link, earth bar, din bar for mounting MCBs (But without MCBs and incomer) as required.<br>8 Way , Double Door.
od263831/2022_2023 : DISTRIBUTION BOARD<br>Supply and fixing of following ways surface / recess mounting, vertical type, 415 V, TPN MCCB distribution board of sheet steel, dust protected, duly powder coated, inclusive of 200A tinned copper bus bar, common neutral <br>link, earth bar, din bar for mounting MCBs (But without MCBs and incomer) as required.<br>6 Way , Double Door.
2.5.2 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 way (4 + 24), Double door
od262852/2022_2023 : Supply and fixing of following ways surface / recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder coated, inclusive of 200A tinned copper bus bar, common neutral link, <br>earth bar, din bar for mounting MCBs (But without MCBs and incomer) as required.<br>6 Way (8 + 18), Double Door.<br>
2.4.1 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (4 + 12), Double door
2.4.2 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)6 way (4 + 18), Double door
2.3.4 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
od264088/2022_2023 : MCCB<br>Supply and fixing following rating and breaking capacity and pole MCCB with thermal magnetic release having 70 to 100%setting provision and terminal spreaders in the distribution board including making connections, etc. complete as required.<br>100A 25kA 4P MCCB.<br>
2.15.1 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
od264510/2022_2023 : RCCB<br>Supply and fixing following rating, four pole, (three phase and neutral), 415V, Residual Current Circuit Breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>63A 100mA .
od264511/2022_2023 : RCCB<br>Supply and fixing following rating, four pole, (three phase and neutral), 415V, Residual Current Circuit Breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. <br>40A 100mA .<br>
2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.14.2 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.3 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.3 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
od268256/2022_2023 : MCB<br>Supply and fixing 5A to 32A rating, 240/415V, 10kA, "C " Curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc as required.<br>40A to 63A Triple Pole.
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.12.2 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
od265005/2022_2023 : JUNCTION BOXES<br>Supply, installation, testing and commisioning of IP65 thermoplastic fire retardant and weather proof junction boxes with bakelite connectors and/or having provision for fixing 4 Pole MCBs/Isolators and glanding cables.<br>
od265006/2022_2023 : METAL ENCLOSURE<br>Supply and fixing Sheet Steel enclosure on surface / recess having provision to fix MCB/Isolator complete with connections, testing and commmissioning etc. as required.<br>4 Way.
od265007/2022_2023 : METAL ENCLOSURE<br>Supply and fixing Sheet Steel enclosure on surface / recesshaving provision to fix MCB/Isolator complete with connections, testing and commmissioning etc. as required.<br>2 Way.
2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.13.3 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
od265200/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 400 Sq.mm Al. cable.
od265201/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 300 Sq.mm Al. cable.
od265202/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 240 Sq.mm Al. cable.
od265203/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 185 Sq.mm Al. cable.
od265204/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 150 Sq.mm Al. cable
od265205/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 120 Sq.mm Al. cable.
od265206/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 95 Sq.mm Al. cable
od265207/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 70 Sq.mm Al. cable.
od265208/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 50 Sq.mm Al. cable.
od265209/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>3.5C x 35 Sq.mm Al. cable.
od265210/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>4C x 25 Sq.mm Al. cable.
od265211/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>4C x 16 Sq.mm Al. cable.
od265212/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>4C x 10 Sq.mm Al. cable
od265213/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>4C x 6 Sq.mm Al. cable.
od265214/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>4C x 2.5sq.mm Copper Armoured cable
od265008/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses,<br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>2C x 2.5sq.mm Copper Armoured cable.
od265009/2022_2023 : Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches,clamping in built up trenches, trays, racks, risers, trusses, <br>walls etc using heavy duty Aluminium Flat or heavy duty GIspacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>4C x 1.5sq.mm Copper Armoured cable<br>
od265010/2022_2023 : LT CABLES<br>Supply, laying, testing and commissioning of PVC 1.1 KV grade XLPE insulated armoured Aluminium cables of the following sizes and laying in earth excavated trenches, clamping in built up trenches, trays, racks, risers, trusses, <br>walls etc using heavy duty Aluminium Flat or heavy duty GI spacer saddles of which spacing of clamps not exceeding 40cm and pulling through pipes including all minor civil works.<br>2C x 1.5sq.mm Copper Armoured cable.<br>
9.1.21 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.23 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.24 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.25 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
9.1.26 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
9.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.29 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.30 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
9.1.31 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.34 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
od265469/2022_2023 : Supply and making end termination with brass compression gland and alluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE Aluminium conductor cable of 1.1 KV grade as required.<br>4C x 6 Sq.mm Al. cable.
od265470/2022_2023 : Supply and making end termination with brass compressiongland and alluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE Aluminium conductor cable of 1.1 KV grade as required.<br>2C x 1.5sq.mm Copper Armoured cable.<br>
od268177/2022_2023 : GLAND EARTHING<br>Supply and providing gland earthing using Aluminium or Copper strip / shim / wire using copper sockets etc. complete as required conforming to Electrical Inspectorate Standards.<br>3.5C x 400 Sq.mm Al. cable.<br>
od268178/2022_2023 : 3.5C x 240 Sq.mm Al. cable.
od268179/2022_2023 : 3.5C x 120 Sq.mm Al. cable.
od268180/2022_2023 : 3.5C x 50 Sq.mm Al. cable
od268181/2022_2023 : 4C x 6 Sq.mm Al. cable.
od268182/2022_2023 : 4C x 2.5sq.mm Copper Armoured cable.
od265704/2022_2023 : EARTHING<br>Supply and providing earthing with CI earth plate 1200mm x1200mm x12.6mm thick electrode including accessories,and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long<br>etc. with charcoal/coke and salt as required conforming to relevant IS and Electrical Inspectorate standards etc.<br>
od265705/2022_2023 : Supply and providing earthing with CI earth plate 600mm x 600mm x 6mm thick electrode including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long<br>etc. with charcoal/coke and salt as required conforming to relevant IS and Electrical Inspectorate standards etc.<br>
od265706/2022_2023 : Supply and providing the earth conductors of the following sizes and laying in earth excavated trenches, clamping in built up trenches , walls, trays, racks, risers, trusses, etc using heavy duty Aluminium Flat or heavy duty GI spacer<br>saddles of which spacing of clamps not exceeding 90cm without making holes in the earthing conductor and pulling through pipes including all minor civil works. All the joints should be properly tinned and connections should only be<br>done using SS Nut and Bolts with double washers etc as required.<br>25 x 6 mm Copper Strip.
od265707/2022_2023 : Supply and providing the earth conductors of the following sizes and laying in earth excavated trenches, clamping in built up trenches , walls, trays, racks, risers, trusses, etc using heavy duty Aluminium Flat or heavy duty GI spacer<br>saddles of which spacing of clamps not exceeding 90cm without making holes in the earthing conductor and pulling through pipes including all minor civil works. All the joints should be properly tinned and connections should only be<br>done using SS Nut and Bolts with double washers etc as required.<br>25 x 3 mm Copper Strip.
od265708/2022_2023 : Supply and providing the earth conductors of the following sizes and laying in earth excavated trenches, clamping in built up trenches , walls, trays, racks, risers, trusses, etc using heavy duty Aluminium Flat or heavy duty GI spacer<br>saddles of which spacing of clamps not exceeding 90cm without making holes in the earthing conductor and pulling through pipes including all minor civil works. All the joints should be properly tinned and connections should only be<br>done using SS Nut and Bolts with double washers etc as required.<br>8 SWG Copper Wire.
od265709/2022_2023 : Supply and providing the earth conductors of the following sizes and laying in earth excavated trenches, clamping in built up trenches , walls, trays, racks, risers, trusses, etc using heavy duty Aluminium Flat or heavy duty GI spacer <br>saddles of which spacing of clamps not exceeding 90cm without making holes in the earthing conductor and pulling through pipes including all minor civil works. All the joints should be properly tinned and connections should only be<br>done using SS Nut and Bolts with double washers etc as required.<br>10 SWG Copper Wire.<br>
od265748/2022_2023 : MS STRUCTURALS<br>Supply, fabrication and installation of cable tray and supports using M.S angles and plates of adequate size painted with one coat of Zinc chromate primer and two coats of black enamel paint.<br>
od265749/2022_2023 : Supply, fabrication and installation of Panel Board mountingsupports using C Channels of adequate size painted with two two coat of Zinc chromate primer and two coats of black enamel paint.<br>
od265750/2022_2023 : Supply, fabrication and installation of checkered plates of 6mm thickness to use above the cable trenches duly supported with channels and duly painted with two coat of Zinc chromate primer and two coats of black enamel paint. <br>and as required.<br>
od268146/2022_2023 : CABLE ROUTE MARKER <br>Supply and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted / welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long with painting and fixing the same in ground at 5 meter<br>interval with cement concrete in M.15 Grade (1:2:4) etc. complete as required.<br>
od268147/2022_2023 : PIPES FOR CABLE PROTECTION<br>Supply and laying of the following size medium class GI pipe in ground/wall/ceiling complete with fittings.<br>50mm dia<br>
od268148/2022_2023 : Supply and laying of the following size medium class GI<br>pipe in ground/wall/ceiling complete with fittings.<br>80mm dia<br>
od268149/2022_2023 : Supply and laying of the following size medium class GI pipe in ground/wall/ceiling complete with fittings.<br>100mm dia<br>
od268150/2022_2023 : PIPES FOR CABLE PROTECTION<br>Supply and laying of the following size medium class GI pipe in ground/wall/ceiling complete with fittings.<br>150mm dia<br>
14.15.1 : Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.63 mm· dia (OD-63 mm & ID-51 mm nominal)
14.15.2 : Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.90 mm dia (OD-90 mm & ID-76 mm nominal)
14.15.3 : Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.120 mm dia (OD-120 mm & ID-103 mm nominal)
14.15.4 : Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.160 mm dia (OD-160 mm & ID-135 mm nominal)
14.15.5 : Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.200 mm dia (OD-200 mm & ID-175 mm nominal
od265889/2022_2023 : DG EXHAUST PIPING<br>Supply and laying of 200mm dia exhaust line with flexible including bends, flanges, nut, bolt, packing, necessary supports etc. and painting the same using Heat resistant Aluminum paints.<br>
od265890/2022_2023 : Supply and laying of 150mm dia exhaust line with flexible including bends, flanges, nut, bolt, packing, necessary supports etc. and painting the same using Heat resistant Aluminum paints.<br>
od265891/2022_2023 : Providing thermal insulation of exhaust line glass wool with Al. Sheet, chicken mesh, necessary supports and screws.<br>
1.10.2 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B
1.11 : Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
1.55.2 : Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B
1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
1.56 : Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
od265993/2022_2023 : Supply and fixing suitable size GI box / PVC surface box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.<br>
od265994/2022_2023 : Supply and fixing suitable size GI box / PVC surface box with modular plate and cover in front on surface or in recess, including providing and fixing 2 Nos of 6 pin 5/6 & 15/16 A modular socket outlet and 2 Nos of 15/16 A modular switch, connections etc. as required<br>
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.27.6 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.12 Module (200mmX150mm)
1.24.6 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet
1.24.7 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet
od268145/2022_2023 : Data socket outlet.
1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
1.26 : Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.14.8 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 4 sq. mm + 2 X 4 sq. mm earth wire
1.14.9 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 6 sq. mm + 2 X 6 sq. mm earth wire
1.14.10 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 10 sq. mm + 2 X 6 sq. mm earth wire
1.18.2 : Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair
1.18.3 : Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.4 Pair
1.53.1 : Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
1.19 : Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
od266771/2022_2023 : SUPPLY OF LIGHT & OTHER FITTINGS<br>Supply and providing the following fittings and items at site<br>Battern/Angle Holder
od266772/2022_2023 : SUPPLY OF LIGHT & OTHER FITTINGS<br>Supply and providing the following fittings and items at site<br>LED Bulb (up to 12W)
od266773/2022_2023 : SUPPLY OF LIGHT & OTHER FITTINGS<br>Supply and providing the following fittings and items at site<br>20W LED Tube Set.<br>
od266774/2022_2023 : 24W LED Tube Set.
od266775/2022_2023 : 100W LED Flood Light.
od266776/2022_2023 : 50W LED Flood Light.
od266777/2022_2023 : 26W BLDC Ceiling Fan of Sweep 1200mm.
od266778/2022_2023 : High Speed Metal Type Exhaust Fan of Sweep 225mm.
od266779/2022_2023 : High Speed Shutter Type Exhaust Fan of Sweep 200mm.
od266780/2022_2023 : High Speed Shutter Type Exhaust Fan of Sweep 150mm.
od268142/2022_2023 : Installation, testing and commissioning of PVC battern /angle holder fitting complete with all accessories directly on ceiling/wall, including giving connections etc. as required.<br>
od268143/2022_2023 : Installation, testing and commissioning of 100W LED Flood light fittings complete with all accessories directly on wall/piller/ceiling, including giving connections etc. as required.<br>
od268144/2022_2023 : Installation, testing and commissioning of 50W LED Flood light fittings complete with all accessories directly on wall/piller/ceiling, including giving connections etc. as required.<br>
1.41 : Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
1.44 : Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
1.50.1 : Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
od267560/2022_2023 : HIGH MAST LIGHT<br>Supply Part<br>Supply of 12 Meter High Mast shaft in one section suitable for 55 m/sec wind speed along with head frame, luminaires carriage suitable for 6 luminaires in symmetrical arrangement and other complete accessories manufactured in factory.<br>
od267561/2022_2023 : Supply of raising lowering system comprising double drum winch, 5mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightning finial rod.<br><br>
od267562/2022_2023 : Supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template etc. complete as required.<br>
od267563/2022_2023 : Supply of 150W LED Flood Light
od267564/2022_2023 : Supply of LED type single dome aviation obstruction light.
od267565/2022_2023 : Installation Part <br>Construction of shallow foundation with M20 grade concrete for the highmast considering the safe soil bearing capacity at site as 10 T/sqmtr at 2 metre depth with all materials and labour.<br>
od267566/2022_2023 : Erection of the high mast with the help of suitable tools and plants, wiring of luminaires with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 sq. mm, lugs, MCB and all labour.<br>
od267567/2022_2023 : CCTV CAMERA<br>Supply Part<br>Supply of the following IP Camera System with all necessary accessories etc. complete as required and providing 2 Years Complete Warranty and Service Support.<br>IR Night Vision Bullet Camera (8.0 Mega Pixel & 30 Meter)<br>
od267568/2022_2023 : Switch (8 Channel)
od267569/2022_2023 : NVR (8 Channel )
od267570/2022_2023 : Surveillance Hard Disk (4 TB )
od267571/2022_2023 : LED Monitor (17.3)
od267572/2022_2023 : SMPS 10A
od267573/2022_2023 : White Surface Box (4'' x 4'')
od267574/2022_2023 : NVR Wall Mount Rack (6U)
od267620/2022_2023 : Installation Part<br>Installation of Camera System with all required accessoriesand labour.<br>
od267621/2022_2023 : ENERGY METER & CT<br>Supply and installation of the following Energy Meters and CTs after getting it tested from Electrical Inspectorate / KSEB / TMR. (All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission <br>of supporting documents.).<br>Three Phase 4 Wire CL : 1 (Direct Operated)<br>
od267622/2022_2023 : Three Phase 4 Wire CL : 0.5S (CT Operated)
od267623/2022_2023 : Single Phase 2 Wire CL : 1 energy meter
od267624/2022_2023 : 100/5A CL : 0.5S, 5VA Resin Cast CT
od267625/2022_2023 : 150/5A CL : 0.5S, 5VA Resin Cast CT
od267626/2022_2023 : 200/5A CL : 0.5S, 5VA Resin Cast CT
2.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
od268133/2022_2023 : Supply and fixing 2Kg Dry Chemical Powder (DCP) type fire extinguisher complete with Gun Metal cap, hose with squeeze grip nozzle, wall fixing brackets conforming to BIS: 2171 and with ISI mark<br>
od268134/2022_2023 : Supply and fixing safety instruction chart in word duly framed in good frame work as required.<br>
od268135/2022_2023 : Supply and providing a set of 2 Nos. 9.5 Litre capacity GI bucket painted in post office red colour with prior coat of red oxide paint and written with white paint "FIRE" and mounted on MS angle iron frame with bracket ofappropriate size and capacity including filling sand etc.<br>
od268136/2022_2023 : Supply and providing First Aid Box as approved by St.John Ambulance Brigade / Indian Red Cross conforming to IS 2217 : 1963.<br>
od268137/2022_2023 : Supply and fixing laminated shock treatment chart duly mounted on a good frame work<br>
od268138/2022_2023 : Supply and providing electrical grade rubber mat of size 2m x 1m having 12mm thickness in front of panels and DBs conforming to IS 15652 : 2006 standard.<br>
od267832/2022_2023 : Supply and providing electrical grade rubber mat of size 2m x 1m having 6mm thickness in front of panels and DBs conforming to IS 15652 : 2006 standard.<br>
od267833/2022_2023 : Supply and providing tested industrial safety helmet conforming to IS 2925 : 1984<br>
od262574/2022_2023 : NAMING FOR IDENTIFICATION<br>Painting letters or figures of 2.5cm/4.5cm sizes with enamel paint as identification mark to Panel boards, DBs etc as required.<br>
od262575/2022_2023 : EARTH EXCAVATION AND BACK FILLING<br>Excavation of all types of soils for the laying of XLPE insulated power cable, GI / HDPE / RCC Pipes, Earthing Copper conductors to the required width and depth up to1.2m and back filling after providing sand cushioning and<br>protective covering by laying bricks breadth wise above the cable. The supply of sand and bricks will come within this scope. The trench dimensions and specifications shall be as per the Electrical Inspectorate, KSEB & CPWD standards.<br>A. Excavation and Back Filling<br>
od262576/2022_2023 : EARTH EXCAVATION AND BACK FILLING<br>Excavation of all types of soils for the laying of XLPE insulated power cable, GI / HDPE / RCC Pipes, Earthing Copper conductors to the required width and <br> depth up to 1.2m and back filling after providing sand cushioning and protective covering by laying bricks breadth wise above the cable. The supply of sand and bricks will come within this scope. The trench dimensions and specifications shall be as per the Electrical Inspectorate, KSEB & CPWD standards.<br>B. Supply and laying of Bricks.
od262577/2022_2023 : EARTH EXCAVATION AND BACK FILLING<br>Excavation of all types of soils for the laying of XLPE insulated power cable, GI / HDPE / RCC Pipes, Earthing Copper conductors to the required width and depth up to 1.2m and back filling after providing sand cushioning and<br>protective covering by laying bricks breadth wise above the cable. The supply of sand and bricks will come within this scope. The trench dimensions and specifications shall be as per the Electrical Inspectorate, KSEB & CPWD standards.<br>C. Supply and filling of sand.<br>
od262578/2022_2023 : DOCUMENTATION<br>Preparation of drawings and getting approval from ElectricalInspectorate. (*All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting documents).<br>
od262579/2022_2023 : Submission of completion report, arranging Inpsection and obtaining Sanction Order from Electrical Inspectorate .(All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting <br>documents.).<br>
od262580/2022_2023 : Co-ordination with KSEB for getting additional power allocation by the submission of 7 sets of HT agreement and executing the agreement etc.(All Statutory fees shall be remitted by the Client / Consumer or it shall be reimbursed on the submission of supporting documents.).<br>
Supply of 200KVA, 3 Phase 415V, 0.8 power factor Diesel Generator
13 passenger lift 1 no
EXCLUSIVE OF GST
1.PLUMBING & SANITARY FITTINGS: Note: Make of Water supply and sanitary items: Best branded ISI make Jaquar, Cera, Hindware, Parryware or eq. in the order of pref. Water pipe: Supreme, Finolex or eq. with IS and all fittings with IS.
2.ELECTRICAL: Note: Rate should be inclusive of preparation of schematic diagram and getting approval from KSEB/Electrical Inspectorate. Statutory fees paid to KSEB/EI shall be paid by us separately.
Make of Electrical equipments/materials
All electrical materials/equipments shall be of best branded items with ISI, strictly as per schedule specification
Panel Boards: CPRI certified reputed manufacturers make
MCB/ELCB/DB - L&T/LEGRAND/SCHNEIRDER or equivalent
Cables & wires - Finolex/KEI/POLYCAB/RPG/V-GUARD
Switches/Sockets/Regulators - SCHEIDER/ABB/HAVELS/LEGRAND or equivalent
Rigid PVCPipes/Casing & Capping - A-ONE/REPUTED MAKE with ISI , Precession, Balco, GEO
Cable Glands & Sockets - REPUTED MAKE , Cosmos
Indicating Lamps - TEKINIC/RISHUB/STC, L&T, Schneider or equivalent
Ceiling/Exhaust fan: Havells, Orient, Usha, Crompton Greaves, Bajaj
3. STEEL WORK G.I.PIPE: Make: JINDAL, Tata or eq. primary make in the order of preference.
4.DELUXE MULTI SURFACE PAINT SYSTEM: Make: JOTUN, Asian, Berger, Nerolas or eq. in the order of pref.
ELECTROWIND ENGINEERING CO
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .