| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.5 CrAccepted-AOC 20 SC BOSE COLONY GALL NO 2 DEFENCE LAB ROAD RATNADA JODHPUR 342001 | JODHPUR | JODHPUR | RAJASTHAN | 342001 | ₹5.5 Cr | L1 | Accepted-AOC Being Lowest |
| 2 | L2₹5.6 Cr+₹17.1 L (3.14%)Rejected-Finance | ₹5.6 Cr+₹17.1 L (3.14%) | L2 | Rejected-Finance Not Lowest |
| 3 | L3₹6.0 Cr+₹53.9 L (9.89%)Rejected-Finance | ₹6.0 Cr+₹53.9 L (9.89%) | L3 | Rejected-Finance Not Lowest |
| 4 | L4₹6.1 Cr+₹66.7 L (12.2%)Rejected-Finance 1630 SECTOR 7C CHANDIGARH 160019 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160019 | ₹6.1 Cr+₹66.7 L (12.2%) | L4 | Rejected-Finance Not Lowest |
| 5 | L5₹6.3 Cr+₹83.7 L (15.4%)Rejected-Finance | ₹6.3 Cr+₹83.7 L (15.4%) | L5 | Rejected-Finance Not Lowest |
Tender Value
₹6.4 Cr
EMD Value
₹6.5 L
Closing Date
15 Nov 2021, 6:00 pmClosed
CE (AF) GANDHINAGAR
LEKAWADA PATIA CHILODA GANDHINAGAR 382042
PROVISION OF 33 KVA ELECTRIC SUPPLY AT AF STN JODHPUR
2021_MES_473830_1
80308
Open Tender
Civil Works
Lump-sum
360 days
GE (AF) JODHPUR
AS PER NIT AND TENDER DOCUMENTS
10 documents required · 10 mandatory
₹3,000
GE (AF) JODHPUR
₹6.5 L
16 Dec 2021
8 Sept 2021
16 Nov 2021
8 Sept 2021
15 Nov 2021
25 Oct 2021
14 Sept 2021 - 20 Sept 2021
Amount
NOTE: Schedule ‘A’ Part I to XII are under Ser No. 1.00 to 12.00. are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lump sum price worked out for BUILDINGS / STRUCTURES as listed in Sch 'A’ Part I.
Lump sum price worked out for EXCAVATION & EARTH WORK as listed in Sch 'A’ Part II
Lump sum price worked out for INTERNAL ELECTRIFICATION as listed in Sch 'A’ Part III
Lump sum price worked out for INTERNAL WATER SUPPLY as listed in Sch 'A’ Part IV
Lump sum price worked out for EXTERNAL ELECTRIFICATION as listed in Sch 'A’ Part V
Lump sum price worked out for EXTERNAL WATER SUPPLY as listed in Sch 'A’ Part VI
Lump sum price worked out for LIGHTENING PROTECTION as listed in Sch 'A’ Part VII
Lump sum price worked out for ROAD/ CULVERT as listed in Sch 'A’ Part VIII
Lump sum price worked out for AREA DRAINAGE as listed in Sch 'A’ Part IX
Lump sum price worked out for SEWAGE DISPOSAL as listed in Sch 'A’ Part X
Lump sum price worked out for BOUNDARY WORK, FENCING AND GATE as listed in Sch 'A’ Part XI
Lump sum price worked out for TRANSFORMER PLATFORM AND AREA CABLE DUCT as listed in Sch 'A’ Part XII
SCHEDULE `A' PART-XIII MISCELLANEOUS ITEMS OF WORK (Note for items 14 to 38. The contractor shall quote his rate for each of these items separately. The estimated rate is left blank since the same is not prepriced by MES)
Supply and fixing 80 mm bore gun metal, globe or gate valve, with iron wheel head, screwed both ends for iron pipe or for unions and fixing complete all as specified and directed .
S&F of OPR-60 Early streamer Emission (ESE) lightening protection air terminal with NFC-17-102 standards complete all as specified and as directed.
S&F AI/SS /GI Pipe fabrication support structure providing with guy wire and MAST 5M mounting mast and suitable base plate should have been provision system termination arrangement for the down- conductor complete all as specified and as directed.
S&F of ABB lightning flash counter working electro mechanically without any power supply equipment should count lightening strokes of 0.4 KA to 150 KA complete all as specified and as directed.
Supply and installation of 70 sqmm copper cable down conductor with suitable mounting accessories & GI protection pipe of size 25mm dia. The mounting clamp should be conductive material complete all as specified and as directed.
Supply and fix mild steel galvanised steel punched type concertina coil 1050 mm dia (dia of coil when unstretched ) and fixed to angle iron with 3.15 mm dia GI wire complete all as specified and as directed.
Supply, installing, testing and commissioning out door type step down transformer, HT 33/11 KV, 03 phase with OFF load tap changer switch , secondary 11KV, 03 phase with off load tap changing on HT side to vary secondary voltage within limit, AC, 3 phase, 50 HZ, as per IS:2026 of capacity 3.15MVA, core type copper wound, oil immersed, naturally cooled, Oil natural, air natural (ONAN), with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol, DYN-11 (Vector Group) with neutral brought out on secondary side (LV side) and having tapping at +- 7.5% in step of 2.5% each HV side to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree Celsius in oil and 55 degree Celsius in HV / LV winding when measured by resistance method after continuous full load run on an ambient temp of 55 degree Celsius. Hot spot temperature rise over a maximum yearly weighted temperature of 32 degree C and should be 98 degree C IS-2006 marked with all accessories and fittings as per IS-2026 or as per latest IS. The core of transformer shall be bottles to reduce hot spots and first grade CRGO sheet shall be used. The insulation level (impulse with stand in KV peak) shall be 170 on HV and 75 on LV side impulse level (power frequency) with stand in KV rms shall be 70 on HV and 28 on LVside. The percentage impedance of transformer at 75 degree C rated current frequency should be 6.25% (IS tolerance) IS 2026 marked and shall comprise of following
(a) Three nos porcelain bushing suitable for 33 KV on HV side complete with copper rods, nuts and washers and arching horns. (b) One cable box HT side (Secondary side) consisting of three Nos porcelain with copper bushing rods complete with nuts and washers with two Nos cable gland suitable for reception / taking out of PVC /XLPE insulated heavy duty HT armoured cables including gland, joint and jointing materials complete. (c) Oil conservator with filter type drain valve and oil level gauge. (d) Dehydrating breather with first fill of dehydrating agent. (Silica gel) (e) Explosion vents. (f) Thermometer pocket on tank cover.
(g) One No. 100 mm dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having maximum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals on tank cover to facilitate fixing of 32 X 6 mm galvanized iron earth strip for earthing of neutral & body. (j) Rating plate and terminal marking plate. (k) Oil level gauge. (l) Oil drain filler valve. (m) Lifting lugs. (n) Oil filling hole with cap / plug with connecting plate complete. (o) Air release valve plug. (p) Four plain solid cast steel detachable rollers. (q) Extra bushing for neutral, outside the LT Cable box for providing independent earthing for neutral.
(r) First filling of new and unused transformer oil IS-335/93 (fourth revision) marked filtered and tested upto50 KV dielectric strength at 2.5 mm air gap between testing electrodes. (s) One danger notice board having conventional danger sign of skull with bones in painted in red colour. (t) Buchholz relay (having contacts for alarm & trip). Note I :-Certification of electric strength shall be submitted by the contractor, after filling the oil. Note II :- Including all control wiring with copper conductor multi core of suitable size (Transformer to control panel in P/H)
Supply, transporting,erection,testing& commissioning of 36kV,1800MVA,1250A,50Hz,voltage class outdoor type Vacuum Circuit Breaker,for use on system voltage 33kV along with indoor CRP panel as per description below. The Circuit Breaker and accessories shall confirm to IEC 62271-100 or IS 13118 and other relevant IEC/IS standard. The Circuit breaker shall be complete with terminal connection, operating mechanism,controlcabinets,cableaccessories,withgland,terminalblock,lugs,necessary steel support structure for CB and control cabinet. The Circuit Breaker shall be required to perform as per technical parameters given below:
a) Installation - Outdoor, 3-Pole,vacuum Live Tank, porcelain Clad,Switchyard Breaker. b) Rated Voltage -36kV c) Rated Current -1250A or higher upto2000A . d) power frequency withstand voltage (kV rms) - 95 kV e) 12/50 µsec. Lightning impulse withstand voltage (kV peak) -195kVp. f) Rated Short Circuit Current Breaking capacity (3 sec.) at rated voltage specified : 31.5kA . g) Control Voltage including Trip /closing coil - 110VDC h) Spring charge voltage - 230VAC i) Symmetrical Interrupting Capacity (kA rms) as per IEC : 31.5kA j) Rated Short Circuit Making Current (kAp) - 80 kAp
k) Out of Phase Breaking Capacity - As per IEC. l) Rated Operating Duty : As per IEC. m) Temperature Rise over the design ambient temperature - As per IEC 62271-100. n) Operating Mechanism - Spring type. o) Creepage Distance - 900mm. p) No.of Trip/close coils - 2 nos. each. q) Spring charging handle - Integral part of Operating mechanism. (Separate Spring charge handle not acceptable).
Note : i) Cost of supply and fix of Outdoor type Terminal Kiosk having terminals /disconnecting links for termination of CT/PT wiring including PT secondary fuses complete all as required at site are deemed to be included in the quoted rate. Ii) Cost of construction of foundation including construction material and necessary earth work as per manufacturer design for breaker & TK complete all as required at site are deemed to be included in the quoted rate.
Feeder Protection and Control Relay, Protections 50,51,50N,51N,46,49,67,67N,27,59,59N,95, Measurement for 3I,I0,3U,U0,Kw,KVA,PF,Hz,Kwh, 16 DI + 10 DO, One front RJ45 Port, Two Rear FO(LC) Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature., Static type Trip Circuit Supervision Relay Type TCS, Space heater with ON/OFF toggle switch. 5 Amp. 3 pin socket with ON/OFF switch. 40 Watt incandescent lamp with holder suitable for 240 V AC with door switch. Terminal Block. MCB for AC & DC Supply, Control fuses with links. Earth bus 25 x 6 mm copper, Control Wiring 1.5sq.mm PVC insulated single core tinned copper type, Test Terminal Block It also includes: control wiring with multi core PVC insulted copper cable from yard to P/H, Make of CRP Panel and VCB should be single. RMUs, VCB Panels,Outdoor PCVCBs ,Substation SCADA shall be from one same Manufacturer to ensure ease of maintanance after expiry of warranty period. (Make : ABB, L&T, Siemens)
Supply, Installation, testing , Commissioning of 11kV Air Insulated HT Indoor type Switchgear Panels with maximum system voltage rating of 12kV consisting of following (a) Incomers of 800A VCB 2 Nos (b) 3 Nos Buscoupler 11 KV of 800A VCB (riser,if applicable) (c) 09 Nos Outgoing Feeders with 800A VCB (d) Copper Busbar Rating of 1250 Amps,Short Circuit Capacity of 26.3kA .Bus-bars shall have full Voltage Sleeving on it and shall be self-supported type ,i.e. without any support insulators .
Note : (i) The Incomer Panels shall contain Line PT arragement . The Panel, Vacuum Circuit Breaker , Vacuum Bottle, Numerical relays shall be of same make as the Panel Manufacturer . Bus bar should be of electrolyte Copper.The panel shall be tested for IAC AFLR for 26.3kA/1s. The IED (Numerical relay) shall be Complied to 61850 protocol without any external protocol converter.GOOSE signals shall be freely configurable.WEB HMI feature should be present.Inter-opera+B4bility test shall preferably shall be done.Proof w.r.t Interoperability shall be submitted by the Manufacturer.The relay shall have integral arc-protection based on simultaneous detection of current and light to ensure reduced cubicle damage and increase personal safety. (<15 ms) The relay must support IEC 61850 Edition 1 and Edition 2(with test reports) and shall supports HSR and PRP redundancy protocols. It shall comply with international standard of NERC CIP or BREW for cyber security . The Circuit Breaker shall be of floor rolling design with encapsulated Vacuum bottles, and shall have all fool-proof interlocks as : Interlocks shall be provided to prevent a ‘Closed’ breaker to rack out from ‘Service’ to ‘Test’ /'Isolated’, position or insert a ‘closed’ breaker from ‘Test’ to ‘Service’ position. In either case the breaker contacts must remain in open position. Before racking out the breaker must be fully discharged from any static charge. Switchgear should be SCADA Compatible. Panel should be Aluzinc coated All Panels shall have integral earth Switch with making capacity . RMUs, VCB Panels,Outdoor PCVCBs shall be from one same Manufacturer to ensure ease of maintanance after expiry of warranty period. Panels shall be tested for Seismic Zone -IV Test reports shall be submitted for the same.
(ii) Each Incomer shall be configured as follows : (a) CTs : 400-200/1-1, 5VA, Cl-5P10, Cl-0.5 (b) PT drawout type : 11000/V3/110/V3/110/3,50VA,Cl-1.0,3P (c) Feeder Protection and Control Relay, REF615 of ABB or Equivalent of L&T/ Siemens, Protections 50,51,50N,51N,46,49,95, Measurement for 3I, I0, 3U,UO,Kw, KVA, PF, Hz, Kwh, 16DI + 10 DO, One front RJ45 Port, Two Rear FO(LC) Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature. Seperate TCS and Mastertrip relay to be provided -01 Nos (d) Auxiallry relay fro transformer OTI. (e) WTI and Bucholz. Annuncitor window. (f) Accessories including Breaker Control Switch (T-N-C), space heater (g) Trivecto meter. with thermostat, DC , AC control circuit through MCB, Indicating Lamps for RYB, spring charge, DC healthy, Breaker ON/ OFF/ TRIP and TEST/ SERVICE position, Multifunction Meter with RS485 port for MODBUS communication (Acc.Cl.0.5), Digital Ammeter (Acc.Cl.0.5), Digital Voltmeter(Acc.Cl.0.5).
(iii) Each out going shall be configured as follows : (a) CTs : 100-50/1-1, 5VA, Cl-5P10, Cl-1.0 (b) Feeder Protection and Control Relay REF615 of ABB or Equivalent of L&T/ Siemens, Protections 50,51, 50N, 51N,46,49,67,67N,27,59,59N,95, Measurement for 31,10,3U,UO,Kw, KVA,PF,Hz, Kwh,16DI+10DO, One front RJ45 Port. Two Rear FO (LC) Port for IEC-61850 Protocol. Drawout Type with CT Shorting feature Seperate TCS and Mastertrip relay to be provided. (c) Accessories including Breaker Control Switch (T-N-C), space heater with thermostat, DC , AC control circuit through MCB, Indicating Lamps for RYB, spring charge, DC healthy, Breaker ON/OFF/TRIP and TEST/ SERVICE position, Multifunction Meter with RS485 port for MODBUS communication (Acc.Cl.0.5), Digital Ammeter (Acc.Cl.0.5), Digital Voltmeter(Acc.Cl.0.5).
(iv) Bus Coupler shall be configured as follows : (a) Accessories including Breaker Control Switch (T-N-C), space heater with thermostat, DC , AC control circuit through MCB, Indicating Lamps for RYB, spring charge, DC healthy, Breaker ON/OFF/TRIP and TEST/ SERVICE position. .
Supply, installation, testing & commissioning of 11 KV Outdoor type extensible RMU floor mounted with internal eletrolytic grade copper bus bars, consisting of combinations of 630 Amp 2 Nos. fixed manual Load Break Switch as incomer & 1 Nos. fixed type manual Vacuum Circuit Breaker. All live parts, bus bars, LBSs connections of RMU shall be enclosed in on+B3e tank to avoid multiple interconnections & sealed for life robotically welded non magnetic and non ferrite grade stainless steel tank Grade 304 of minimum 2.5 mm thick having IP67 degree of protection filled with SF6 gas as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. The unit shall have front cable entry for ease of installation and shall have site replaceable bushings for ease of troubleshooting during breakdown. RMU should be complete with all accessories such as Terminal boots, VPIS, cable supports, all front cable terminations, mechanical indications for Load break switch ON/OFF, Manometer as per with IEC standards 62271-200, 60056, 60129, 60265, 60298, 60420, 60529 and 60694. Altitude of installation up to 1000m as per IEC 60120. Extensible Bushings, if applicable shall be bolted type top mounted outside the tank for connection of external bus bar .Also, the outer enclosure shall cover the full length of the switchgear, to ensure IP3X+IP54 protection for cable boxes . RMU should be SCADA Compitable. The unit shall be internal arc proof 21kA for 1 sec. for tank +Cable Box , and tested and totally safe for human beings. The gas release & personnel safety with internal arc proof shall not depend on plinth design.
The release of gas to be from the top of the unit, so that, even if the person is operating the unit, opening the cover, & there are personnels near the sides of the RMU/plinth, top release will ensure their safety. The release in no case should be from any side or bottom of the unit, as the same is unsafe for the operating personnel/pedestrian or general public. Bidder shall provide type test report to prove compliance to the ‘Internal fault IAC-AFLR as per IEC 62271-200.Internal arc proof & testing shall be done with enclosure door in open condition, with switching devices in operation mode. The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. The Manufacturer shall furnish performance Certificate for similar kind of RMUs in their own legal Name . Any Joint venture certificates / partnership with other firms shall not be considered. RMUs, VCB Panels, Outdoor PCVCBs, CRP shall be from one same Manufacturer to ensure ease of maintenance after expiry of warranty period. The unit shall include the following with all necessary standard fitting required at site.
630A Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 95kV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation and pad-lockable Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
630A VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity Manual operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker with pad-locking feature. Three position single spring mechanism for disconnector/earthing switch with pad-locking feature. “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV
Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Resin cast ring core protection CT plate mounted type : 100/1 A, 5P10, 2.5 VA - 3 Nos Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B). Make : ABB, Siemens, Schneider.
Supply and install 33 KV single phase outdoor oil cooled CT of ratio 100-50/5-5 Amp class 1.0-5P10 burden 15 VA insulation level 70/170 KV. Note I :- Including all control wiring with copper conductor multi core of suitable size shall be catered with 33 KV HT switch gear complete all as specified and directed.
Supply and install 33 KV single phase out door oil cooled PT of ratio 33 KV/rt3/110 V /rt3/110V /rt3 class 0.5 -3 , Burden 50 VA-50 VA, insulation level 70/170 KV, voltage factor 1.2 cont and 1.9 for 30 sec , confirming to IS-3156. Note II :- Including all control wiring with copper conductor multi core of suitable sizeshall be catered with 33 KV HT switch Gear complete all as specified and directed.
Supply and install HT 33 KV outdoor type gang operated air-break switch suitable for horizontal mounting fixed type complete with 9 insulator and with earth switch of 400Amps with its mounting arrangment complete all as specified and directed.
M&L for 40 to 50 mm thick rough dressed jodhpur stone cover 25 to 30 cm wide and not less than 50 cm in length laid dry and abuting each other with gap between adjecent slab not exceeding 10mm over UG cable for protection complete all as specified and directed.
(iii) Each capacitor step shall be protected with 3 Nos of 11KV HRC fuses. Further it shall also be provided with0.2% series reactors for limiting in-rush current. The series reactors shall be 11 Kv aluminium wound air cored, class F insulated, epoxy resin impregnated and dry type suitable for panel installation. Each capacitor step is energized through APFC relay (auto operation) or through ON / OFF push buttons provide on the cubicle (Manual operation) suitable thermostat, cubical illumination lamps, etc shall be provided for each continious current (Amps) :- 130% of rated current rated short time current:- 16.66 times rated current / 2 sec IS-5553, Part 4-1989. Make- PQ/Srihans/Infrad (iv) Capacitor duly vacum contactors appropriate rating for capacitor switching for each step confirming to IS-9046. Each capacitor step is provided with following:- 400A, 12KV, Vacum contactor coil voltage 110V with electrical latching IEC62271-106- 3 Nos12kV HRC Fuses- 2.0% series reactor (aluminium wound). Make- ABB (V-Contract VSC), Scheneider Electric (Rollersc/CBX), General Electric (v) Automatic power factor controller relay microprocessor IEC 61010-1, 61326-1 based for switching ON & OFF of capacitor bank with voltage visual alarm if unit fails to achieve required power factor automatic lock out of faulty, steps and display of power factor achiedved (leading or lagging). Make- ABB (RVT), Scheneider Electric (VarPlus Logic), General Electric
(vi) 0.2% series reactor inductor coils of appropriate rating along with each capacitor bank to minimize inrush current aluminium wound, class - F, epoxy resing impregnated, dry panel mounted type, line side Air core series reactors, maximum continious current (Amps) :130 % of rated current, rated short current : 16.66 times rated current /2sec IS-5553, Part-4-1989, IEC 60076-6. Make- Scheneider Electric (BCV), General Electric Meter (vii) 11KV Cast resin type RVT for unbalance protection. (viii) 9KV, 10KA, Panel Mounted LA, (ix) Neutral displacement relay and recolose delay timer relay for each capacitor bank, complying to IEC 60255-5. Make- ABB(SPAJ 160C), Schneider Electric (Sepam C86) Trench (CPR 04), General Electric or equivalent make approved. (x) Each step should having overvoltage relay B 21 (Schneider or equivalent) with SCADA compatible intelligent panel meter PM5000 (Schbeider or equivalent) of fange as required and recommended by manufacture with build sector switch and CTs of appropriate ration. Make- L&T/AE/Schneider/ABB (xi) Ventilating fans of required size it dissipates the liberated by capacitor unit complete with automatic switching ON and OFF of fans depending upon the temperature of the panel.
(xii) Bus bar or appropriate rating for incoming and outgoing connections suitable to withstand short curcuit current 35KS for 1 second made of tinned aluminium bus bar, support insulators, cables, ferrules, terminal borrs mounted on SMC silicon free chlorine free post insulators and arranged such a way that the joints are minimum. (xiii) Emergency push button to disconnect the unit incase of emergency. (xiv) Indicator LED (RED & GREEN) type for phase indication and capacitor banks ON & OFF indication, (xv) Current Transformer 01 Nos of appropriate rating 11KV/230 volts, 1 phase, 10VA to be fixed in incoming existing panel for operation of APFC relay compare with control wiring (xvi) All accessories prewired with suitable size conductor cable insulated with fibre glass insulation to withstandhigh temperature, housed in cubical panel mode out of 2mm thick MS sheet factory made duly powder coated front and rear open able with locking arrangement complete.. Enclosure system complying to IEC 62262 (IK 10 certification for external mechanical impacts) with foundation as required or recommended by manufacturer. Make of Panel- schneider CAT No. H300BRA016 or equivalent of make L &T/Siemens.
Note : APFC panel shall be manufactured by original manufacturer i.e. Schneider/L&T/Siemens only. The approved vendor for capacitor banks should have their own manufacturing facility or major components such as capacitors, reactors, conductors, control and protection relays and enclosure sustem. The firms specified specified cannot authorise any other vendors to manufacture APFC panel on their behalf and the panel so manufactured will not be accepted. The panel manufactured by original manufacturer only with external bus.
Supply and fix LED security light 60 Watt IP65 with required sizeof GI pipe and necessar accessories required for connection as directed by Engineer-in-Charge
M & L for pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 33000 volts grade.
M&L disc Type, porcelain, vitreous insulator with four discs for 33KV system including one galvanised iron washers and one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut single in assembly with suitable size of clamps/metal parts for insulation pressure 11KV each disc complete all as specified and directed.
Supply and fix visibilis distance to go marker each face (Perforated) of size 1.20 x 1.50 m of tringular (hollow) shape made of Frangible high grade reinforced plastic board, internal structure fabricated using 04 Nos fibre channel 65x30x3 cm thick monolithic structure to withstnad high velocity winds resist temperature varying from extreme cold enviornment to sweltering hot conditions, the entire trangular structure fixed on 03 Nos 40mm dia 2.10mtrs long fibre pipe with suitable size of screws @ 15 cm c/c and the distance go marker monolithic structure embeded in plain cement concrete 1:3:6 type C-2 using 40 mm graded crushed stone aggregate in pit to size 15cmx15cmx15cm including painting the entire structure internally and externally with two coat of first quality synthetic enamel paint and finally stacking the numerals on (two) view face of board with write om MES SUB STATION XXX high intensivity prismatic reflector sheet 15cm wide and height of numerals as per requirement of Aviation guidelines complete including excavation/earthwork in hard/dense soil returning filling and removal of surplus soil etc complete all as specified and directed by EIC..
S & F Energy saving LED flood light of 100 W capacity with built in control box (IP65) suitable for out door application with all necessary acessories required for mounting of light all as specified and directed by Engr-in charge.
S&F PVC junction box of size 450cm x450cm x300 mm inluding connector strips 12 way 3 Nos of suitable connector strips of suitable rating arrangement with MCB for ON/OFF complete all as directed.
M&L for precast cable route Indicator made out of cement concrete 1:2:4, type B1, using (20mm graded stone aggregate) having 15cm square shape at top and 30cm square shape at bottom and total height of 100cm fabricated as per direction of Engineer-in-Charge and grouted into PCC 1:2:4, type B-1, as per site requirement including embossed with "HT 11KV Cable and LT cable 1100V" at 50 meters in synthetic enamel Paint red coloured and necessary excavation and earth work in any type of soil complete all as specified and directed.
Boring of holes under road pavement,hardstansding by trenchess technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm suitable for 0.4 mpa working pressure complete all as specified and directed.
Supply, Installation, testing and commissioning single phase input supply, single phase output, PWM technology IGBT based, ON line battery charger for standard maintenance free (SMF) battery bank with features of protection in case of High and Low voltage etc. of capacity not less than 5KVA complete all as specified and directed.
Supply and fixing PG clamps aluminium for making connections on 33KV OH line and bus bar gantry complete all as directed.
Manning and Operation of 33/11KV substation under defect liability period of following installations including maintain proper day to day repord / log sheet complete with following qualified technical staff along with proper tools/saftey measures, own conveyance, transport and T&P including communication system for personal communication with GE office:- 1. Power Transformer 33/11KV 3.15MVA- 02 Nos 2. 33KV SF6 Breakers, 33KV Yard, DGOD, CT, PT 3. 11KV VCB Panels 4. 11Kv APFC Panel 5. Load Break Switch and connected accessories. 6. HT cables and Joints. (i) The contractor will ensure proper functioning all electrical installation like HT VCB, transformer, HT/LT cables with joints, GO/DO, all external electric supply works as per site requirement and as directed by Engineer-in-Chagre.
(ii) Cost of fixing/refixing/removing, transport, communication system, uniform all type of tools as required deemed to be included in the unit cost. New 33/11KV Substation (a) First shift - 2 Electrician (b) Second shift - 2 Electrician (c) Third shift - 2 Electrician (iii) The rate of recovery in case of absence of manpower shall be as under:- (a) Electrician Rs 500/- per day per shift per electrician (iv) Electrician should be well experienced (minimum 6-8 years) in the field/ITI qualified with (2-3 Yr) experience and well experience of Electrical services sectors all as directed by Engineer-in-Charge. (v) All petty consumable items required for repair like nuts, bolts, washers, screws, tapes, grease oil/lubricants, copper lugs for connections etc deemed to be included in the cost. (Note : Daily cleaning of all rooms viz floor, walls and ceiling fan including internal electrical fixtures, HT VCBs, APFC panel and 33KV yard shall be deemed included in quoted rate by contractor. (vi) Manpower/ electrician employed in the work shall not continue working beyond 11 months.
Jeet Construction
Jagdish Prashad and Company
SAGGI ELECTRIC COMPANY
M/S JIWAN KUMAR MITTAL
RISING ELECTRICALS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .