Executive Engineer (Elec./Mech.), Water Works Dep, Vadodara Municipal Corporation
Supply, Installation, Testing and Commissioning of Electrical Infrastructure from 11kV (HT) to 415 V (LT) under Phase-02 at the Charging Station at Gotri under PM eBus Sewa Scheme with Two (02) Years of O&M
345346
PRO No. 394/2026-27
Open
Electrical Works
Works
Vadodara
3 documents required · 3 mandatory
₹10,000
Municipal Commissioner Vadodara Municipal Corporation
₹5.1 L
17 Sept 2026
17 Sept 2026
17 Sept 2026
3 Oct 2026
17 Sept 2026
NAME OF WORK: “SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF ELECTRICAL INFRASTRUCTURE FROM
11KV(HT) TO 415V(LT) UNDER PHASE-2 AT THE CHARGING STATION AT TP-60, FP 205, GOTRI VADODARA UNDER PM E-
BUS SEWA SCHEME INCLUDING COMPREHENSIVE OPERATION AND MAINTENANCE FOR PERIOD OF 2 YEARS
Item Quantit Total Amount as per
Item Quantit Total Amount as per
Description Unit Estimated Rate Rate In Words
No. y estimated rates
1 2.00 Providing, and erecting 11 KV D.P. 9 mtr. high Structure Ea. 98433.59 Rupees Ninety Eight
made of 6" x 3" ‘I’-Section Girder, 4" x 2"channels, clamps, Thousand Four Hundred
nuts, bolts etc. Suitable for erection of the followings duly Thirty Three And Paise
connected with necessary ACSR conductors. as per drawing Fifty Nine Only
approved by the Engineer- in charge complete with
following. Height as per IS 7 Mtr above ground ) (A) 11 KV
200 Amps Drop out fuses with S.R.B.P. tubes carries.-Three
nos (B) 11 KV G.O.D. switch complete with insulators,
operating handle with galvanised pipe, Sq.bar etc. 400 Amp.-
One Set (C) 11 KV lightening arrestor with clamp-Three
Nos. (D) 11 KV shackle insulators- Six Nos. (E) The above
D.P. structure should be earthed with 25 mm.X 3 mm thick
double copper earth strips run separately and connected with
separate copper plate earth electrode.
2 2.00 SITC of the Heat shrinkable type Outdoor H.T.cable end Ea. 11601.87 Rupees Eleven Thousand
terminations suitable for 11 kV, 3C x 240 sq.mm. XLPE (E) Six Hundred One And
armoured cable. Paise Eighty Seven Only
3 4.00 SITC of the Heat shrinkable type Indoor H.T.cable end Ea. 7054.85 Rupees Seven Thousand
terminations suitable for 11 kV, 3C x 185 sq.mm. XLPE (E) Fifty Four And Paise
armoured cable. Eighty Five Only
4 400.00 Providing and erecting ISI Marked 3core 240 Sq.mm XLPE Mtr. 2217.96 Rupees Two Thousand
insulated 11 KV armoured cable Aluminium conductor IS- Two Hundred Seventeen
7098 to be laid on wall with clamps or in provided cable And Paise Ninety Six
trench / pipe approved manner as directed. Only
5 1.00 Supply, installation, testing & commissioning Outdoor type Nos. 728053.45 Rupees Seven Lakh(s)
11 KV 630 Amps. 21 kA for 3 second SF6 type extensible Twenty Eight Thousand
and motorized 4 way smart Ring Main Unit (RMU) complete Fifty Three And Paise
with (2 VCB + 2 LBS) with FRTU and FPI as per IS Forty Five Only
6 2.00 Supply, installation, testing and commissioning of 1600 Ea. 7627015.00 Rupees Seventy Six
kVA, 11 kV / 433 V Compact Substation (CSS) 11 kV, Lakh(s) Twenty Seven
630A, 21kA/3 sec, 1 Way, indoor, Non-Extensible SF-6 Thousand Fifteen Only
insulated RMU, comprising 1 No. Riser Module for direct
cable connection & 1 No. fixed Manual Vacuum Circuit
Breaker in stainless steel tank- with Operating handle,
Voltage presence indicator (VPIS) & manometer integrated
earthing switch Self powered IDMT Relay. Interconnection
between HT switchgear and transformer shall be using
1Cx3x95 sq.mm Al. unarmoured XLPE Cable Protection
CT– 50-100/1A, 2.5VA, 5P10. Mechanical position
indicator. Switch ON/OFF/EARTHED. Voltage presence
Indication Manometer Operating Handle RMU shall be
capable for cable termination of 1C x 1R x 300 sq.mm
unarmoured Al XLPE Cable. Single Phase, Resin Cast CTs
with ratio 50-100/1 ring type 2.5VA burden, accuracy class
1.0 Resin Cast Fixed type PTs with ratio
11KV/R3/110V/R3,50VA burden,
accuracy class 1.0 Digital Multifunction meter CL-1 Hooter
& Annunciator Aux Relay
VADODARA MUNICIPAL CORPORATION
NAME OF WORK: “SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF ELECTRICAL INFRASTRUCTURE FROM
11KV(HT) TO 415V(LT) UNDER PHASE-2 AT THE CHARGING STATION AT TP-60, FP 205, GOTRI VADODARA UNDER PM E-
BUS SEWA SCHEME INCLUDING COMPREHENSIVE OPERATION AND MAINTENANCE FOR PERIOD OF 2 YEARS
Item Quantit Total Amount as per
Item Quantit Total Amount as per
Description Unit Estimated Rate Rate In Words
No. y estimated rates
1600 KVA, 11KV/433V, 3 Phase, 50 Hz, Dyn11 Dry cast
resin type copper wound transformer without enclosure type
design (IP-00) having Insulation Class F, Temp Rise in
winding will be 90o C [Max.] with Off Circuit Tap Links of
tapping range +5% to -10% in step of 2.5%(6 step,
position) Losses shall be as per ECBC Standard Total losses
at 50% Load : 6320 Watts (max.) Total losses at 100% Load
: 16800 Watts (max.) Impedance: %Z –6.25% (IS Tol.)
Winding temperature indicator with alarm & trip contacts
433V LT Indoor panel with 2500 Amps Aluminium Bus bars
(100% for Phase and 50% for Neutral), Fabrication using
1.5/2mm CRCA sheet steel, Ingress protection IP2X/4X,
complete with internal wiring consisting of following.
2500A,4P,433V,50 kA MDO type Microprocessor based
release ACB with (O/L,S/C+ E/F protection) Resin Cast CT-
2000/5A, 15VA, Accuracy CL-1.0 RYB, ON-OFF-TRIP
Indication Digital Multifunction Meter CL-1 Outgoing
630A, 4P,433V,36 kA Manually fixed type Microprocessor
based release MCCB with (O/L,S/C+ E/F protection) 7 Nos.
400A,4P,433V,36 kA Manually fixed type Microprocessor
based release MCCB with (O/L,S/C+ E/F protection) 2 Nos.
Digital Multifunction Meter CL-1 with CT's APFC Panel
480 kVAR MPP Type Standard Duty Capacitor Bank
1000A,3P,50 kA Manually Fixed type Microprocessor base
release ACB with (O/L,S/C+E/F protection) for APFC.
Outdoor type enclosure having construction of Galvanised
Sheet Steel. The Enclosure shall have IP54 degree of
protection for HT & LT switchgear compartment & IP34
degree of protection for Transformer compartment. The
enclosure exterior shall be Powder coated (Color -RAL-1001-
Cream). Each compartment will be provided with the door
and pad locking arrangement. The Compartment illumination
lamp with door operated switch shall be provided for MV &
LV compartment. Interconnection Between HT switchgear &
Transformer using 1Cx3Rx95Sq.mm XLPE Al Single core
cable & Interconnection between Transformers to LT
switchgear using Aluminium bus bars. Internal earthing
connections including Transformer Neutral by using 50x6
7 2.00 Civil Works for CSS Foundation and Fenching of swithyard Ea. 1515000.00 Rupees Fifteen Lakh(s)
Fifteen Thousand Only
VADODARA MUNICIPAL CORPORATION
NAME OF WORK: “SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF ELECTRICAL INFRASTRUCTURE FROM
11KV(HT) TO 415V(LT) UNDER PHASE-2 AT THE CHARGING STATION AT TP-60, FP 205, GOTRI VADODARA UNDER PM E-
BUS SEWA SCHEME INCLUDING COMPREHENSIVE OPERATION AND MAINTENANCE FOR PERIOD OF 2 YEARS
Item Quantit Total Amount as per
Item Quantit Total Amount as per
Description Unit Estimated Rate Rate In Words
No. y estimated rates
8 10.00 Supplying & erecting earth pit of minimum bore dia.150mm Ea. 5760.03 Rupees Five Thousand
size approved make Earthing Electrode consisting Pipe-in- Seven Hundred Sixty
Pipe Technology as per IS 3043-1987 made of corrosion free And Paise Three Only
hot dipped G.I.Pipes having Outer pipe dia of 50mm having
80-200 Micron galvanising, Inner pipe dia of 25 mm having
200- 250 Micron galvanising, connection terminal dia of
12mm with constant ohmic value surrounded by highly
conductive compound with high charge dissipation suitable
for following type of applications with chamber and heavy
duty cover.(approved make OEM has to submit test
certificate) & having back filling compound of (B) Inner
chemical (CCM Compound)- Resistivity:- 0.2 • / meter
testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no
load & dry form, Sulphar content:- <2%(C) Back fill
Compound :- Earthing compound should be capable to
retainmoisture for long time Necessary test report must be
submitted.(c) For Electrical Installation covering Transformer
Neutrals, Lightning arrester Earthing, A.C.Plant & Sensitive
Computer System(like Automation, SCADA) i.e independent
(b)For Electrical installation up to 11 KV in normal soil.
Length of Pipe : 2.00 mtrs Back filling Compound :1 no. Bag
9 10.00 Supplying & erecting earth pit of minimum bore dia.150mm Ea. 8636.51 Rupees Eight Thousand
size approved make Earthing Electrode consisting Pipe-in- Six Hundred Thirty Six
Pipe Technology as per IS 3043-1987 made of corrosion free And Paise Fifty One Only
hot dipped G.I.Pipes having Outer pipe dia of 50mm having
80-200 Micron galvanising, Inner pipe dia of 25 mm having
200- 250 Micron galvanising, connection terminal dia of
12mm with constant ohmic value surrounded by highly
conductive compound with high charge dissipation suitable
for following type of applications with chamber and heavy
duty cover.(approved make OEM has to submit test
certificate) & having back filling compound of (B) Inner
chemical (CCM Compound)- Resistivity:- 0.2 • / meter
testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no
load & dry form, Sulphar content:- <2%(C) Back fill
Compound :- Earthing compound should be capable to
retainmoisture for long time Necessary test report must be
submitted.(c) For Electrical Installation covering Transformer
Neutrals, Lightning arrester Earthing, A.C.Plant & Sensitive
Computer System(like Automation, SCADA) i.e independent
(c) For Electrical Installation covering Transformer Neutrals,
Lightning arrester Earthing, A.C.Plant & Sensitive Computer
System(like Automation, SCADA) i.e independent Earthing
in normal soil.
Length of Pipe : 3.00 mtrs
Back filling Compound :2 nos Bags of 25 Kg.
10 150.00 Providing and erecting required size HOT deep Galvanised Kg. 77.77 Rupees Seventy Seven
iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT And Paise Seventy Seven
panel board, Motors etc. using proper clamp. Only
VADODARA MUNICIPAL CORPORATION
NAME OF WORK: “SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF ELECTRICAL INFRASTRUCTURE FROM
11KV(HT) TO 415V(LT) UNDER PHASE-2 AT THE CHARGING STATION AT TP-60, FP 205, GOTRI VADODARA UNDER PM E-
BUS SEWA SCHEME INCLUDING COMPREHENSIVE OPERATION AND MAINTENANCE FOR PERIOD OF 2 YEARS
Item Quantit Total Amount as per
Item Quantit Total Amount as per
Description Unit Estimated Rate Rate In Words
No. y estimated rates
11 80.00 Providing and erecting required size Copper strip for earthing Kg. 794.87 Rupees Seven Hundred
of H.T. OCB / ACB/ Transformer, LT panel board, Motors Ninety Four And Paise
etc. using copper clamp. Eighty Seven Only
12 2.00 Supplying & erecting carbon dioxide (CO2) fire extinguisher Ea. 6591.26 Rupees Six Thousand
user of following capacity with necessary clamps made from Five Hundred Ninety One
50 x 6 mm M.S. Flat with nut & bolts grouted in wall And Paise Twenty Six
complete.[A] For 4.5 Kg Capacity Only
13 2.00 Supplying & erecting ABC powder type 'Ceasefire' type Fire Ea. 848.40 Rupees Eight Hundred
extinguisher as per IS 13849 or 1 Kg capacity with necessary Forty Eight And Paise
clamp for erection on wall Forty Only
14 2.00 Providing and fixing printed instruction chart both in English Ea. 130.29 Rupees One Hundred
and Gujarati and duly framed with front glasses, for Thirty And Paise Twenty
treatment of person suffering from Electric shock with Nine Only
minimum 50" diagonally size.
15 2.00 Providing pair of rubber hand gloves suitable for working on Ea. 214.12 Rupees Two Hundred
11 KV/22 KV supply. Fourteen And Paise
16 10.00 Supplying rubber matting of following thickness as per Sq.Mtr 1027.17 Rupees One Thousand
IS:15652/IEC 61111 (b)4mm Twenty Seven And Paise
17 2.00 Supplying stand first AID box with antiseptic cream, Ea. 299.97 Rupees Two Hundred
medicine for use on wounds due burn, crepe bandage, gauge Ninety Nine And Paise
bandage, medicated ready to use bandage (Band-aid) Ninety Seven Only
adhesive tape for medicinal user, Scissors, anti-septic
solution (Savlon or similar) etc. (All above contents shall be
of standard makes)
18 2.00 Supplying and erecting floor mounting stand for keeping four Ea. 942.33 Rupees Nine Hundred
nos. of FIRE buckets comprising 1500 mm in length, 900 Forty Two And Paise
mm height frame made out of 30mm X30 mm X 4 mm angle Thirty Three Only
iron with cross supports for legs, welded with 4 hooks and
duly painted with one coat of red lead and two coats of
approved enamelled silver paint.
19 300.00 Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured Mtr. 1747.30 Rupees One Thousand
cable multistrand Aluminium conductor for 1.1 KV. to be Seven Hundred Forty
laid on wall with necessary clamps or in existing trench / Seven And Paise Thirty
pipe of following size of cables (K) 3 1/2 core 400 Sq.mm ( Only
185 Sq. mm 1/2 core)
20 12.00 Providing and, fixing heavy duty flange type brass double Ea. 369.66 Rupees Three Hundred
compression type cable gland with rubber ring for PVC Sixty Nine And Paise
insulated armoured cable complete with out going tails, Sixty Six Only
insulating tape etc for following size of cables. (J) 3 & 1/2
core 400 Sq. mm
21 48.00 Solder less crimping type Aluminium lugs conforming to IS Ea. 110.09 Rupees One Hundred Ten
suitable for cable of following size evenly crimped with high And Paise Nine Only
pressure tool & connected to switchgear terminals with
brass/cadmium plated nut bolts in an approved manner. (L)
22 400.00 Making trench in soft soil of suitable width of 90 cm deep for Mtr 55.55 Rupees Fifty Five And
laying cable or locating the fault all over the run and back Paise Fifty Five Only
filling the same and making the surface as normal ground.
VADODARA MUNICIPAL CORPORATION
NAME OF WORK: “SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF ELECTRICAL INFRASTRUCTURE FROM
11KV(HT) TO 415V(LT) UNDER PHASE-2 AT THE CHARGING STATION AT TP-60, FP 205, GOTRI VADODARA UNDER PM E-
BUS SEWA SCHEME INCLUDING COMPREHENSIVE OPERATION AND MAINTENANCE FOR PERIOD OF 2 YEARS
Item Quantit Total Amount as per
Item Quantit Total Amount as per
Description Unit Estimated Rate Rate In Words
No. y estimated rates
23 300.00 Providing & laying approved make Double walled Mtr, 137.36 Rupees One Hundred
corrugated pipes (DWC) of polyethylene(conforming to IS Thirty Seven And Paise
14930 II )with necessary connecting accessories of same Thirty Six Only
material at required depth in existing trench for laying of
cable. below ground / road surface for enclosing cable
(D)120 mm outer dia.
24 400.00 Providing & laying. R.C.C. Hume pipe for cable to be laid 90 Mtr 263.61 Rupees Two Hundred
cm. below ground across the road crossing or on floor with Sixty Three And Paise
necessary material in an approved manner and making the Sixty One Only
ground as per original. (E)150 mm dia
25 8.00 Supplying and erecting high tension cable end box outdoor Ea. 4195.54 Rupees Four Thousand
type suitable. for 11 KV 240Sq.mm 3core H.T. cable One Hundred Ninety Five
complete with gland bushing and jointing material. And Paise Fifty Four Only
1.00 COMPREHENSIVE OPERATION AND MAINTENANCE 1910802.45 Rupees Nineteen Lakh(s)
FOR 1st YEAR Ten Thousand Eight
Hundred Two And Paise
Forty Five Only
1.00 COMPREHENSIVE OPERATION AND MAINTENANCE 2439088.68 Rupees Twenty Four
FOR 2nd YEAR Lakh(s) Thirty Nine
Thousand Eighty Eight
And Paise Sixty Eight
Amount in Word|:
Two Crore Fifty-Four Lakh Eighty-One Thousand Three Hundred Forty-One Rupees Only
I/We am/are willing to carry out the work at… ...................... % above/below percent(Should be written in figures and words) of the
estimated rate mentioned above. Amount of my /our tender works out as under.
IF TENDER IS BELOW IF TENDER IS ABOVE
1) Put on Tender 2,54,81,341.00 1) Put on Tender
2] Deduct Rs. 2] Add________% above Rs.
3] Net Amount ofRs.
tender 3] Net Amount of tender Rs.
4] Amount in 4] Amount in Words
Note-1 All works shall be carried out as per Public Works Department Handbook and other specifications of Division or as directed.
Note-2 All the columns is Schedule should be filled in ink and the total of the entries in the last column should be struck by the contractor under his signature.
Note-3 Rates quoted include clearance of site (prior commencement of work and at its close)in all respects and hold good for work under all conditions, site,
Note-4 To be continued on additional sheets, if found necessary.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2.0 Volume - 2 O and M E-BUS GOTRI.pdf
3.0 TECHNICAL SPECIFICATIONS OF CSS.pdf
4.0 1600KVA CSS SLD-Layout drawing.pdf
5.0 SCH_B_PM E-BUS CHARGING STATION GOTRI PHASE-II.pdf
1_VOL-1_Prequalification_Bid_FINAL_17-09-2026.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .