Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC | ₹1.3 Cr | L1 | Accepted-AOC Lowest Bid Accepted |
| 2 | L2₹1.3 CrRejected-Finance | ₹1.3 Cr | L2 | Rejected-Finance Not Being Lowest Bidder |
| 3 | L3₹1.4 CrRejected-Finance FLAT NO B 205 S NO 296 2 DIVINE HOMES PORWAL ROAD LOHEGAON PUNE 411047 | PUNE | MAHARASHTRA | 411047 | ₹1.4 Cr | L3 | Rejected-Finance Not Being Lowest Bidder |
| 4 | L4₹1.8 CrRejected-Finance 8 51 PLOT NO 6 LIC COLONY SUJATA NAGAR PENDURTHY MANDAL VISAKHAPATNAM 530042 AP | 530042 | ₹1.8 Cr | L4 | Rejected-Finance Not Being Lowest Bidder |
| Sl No | Description | Qty | Unit | Sai Sri Constructions L2 | GAGANSRI INFRA L1 | LEOENTERPRISES L4 | BSK Construction L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 400 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 1 | EACH JOB | 2,00,000 ₹2 L | 1,75,000 ₹1.8 L | 1,95,000 ₹1.9 L | 1,55,000 ₹1.6 L |
| 1.10[a] Onload Changeover switch I-O-II open execution, 4 Pole, 200 Amps – 01 No. [To be fixed after incomer] [b] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 02 Nos as incomers [Mains+DG] [d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 04 Nos [Outgoing] [e] Three line multifunction meter having LCD display - 01 No [f] Current Transformer and Potential Transformer - 01 Set [g] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | |||||||
| 2.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1500 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 2 | EACH JOB | 3,15,000 ₹6.3 L | 3,10,000 ₹6.2 L | 3,14,000 ₹6.3 L | 2,35,000 ₹4.7 L |
| 2.10[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release - 01 No [Outgoing] [c] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [d] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing] [e] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [f] Three line multifunction meter having LCD display - 01 No [g] Current Transformer and Potential Transformer - 01 Set [h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | |||||||
| 3.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 3 | EACH JOB | 1,95,000 ₹5.8 L | 2,00,000 ₹6 L | 2,45,700 ₹7.4 L | 1,75,000 ₹5.3 L |
| 3.10[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing] [c] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing] [d] Three line multifunction meter having LCD display - 01 No [e] Current Transformer and Potential Transformer - 01 Set [f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | |||||||
| 4.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1250 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 1 | EACH JOB | 2,95,000 ₹3.0 L | 2,70,000 ₹2.7 L | 2,90,000 ₹2.9 L | 2,30,000 ₹2.3 L |
| 4.10[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [c] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing] [f] Three line multifunction meter having LCD display - 01 No [g] Current Transformer and Potential Transformer - 01 Set [h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | |||||||
| 5.00 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | 1 | EACH JOB | 1,95,000 ₹1.9 L | 1,95,000 ₹1.9 L | 2,25,000 ₹2.3 L | 1,95,000 ₹1.9 L |
| 5.10[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer] [b] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 03 Nos [Outgoing] [c] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing] [d] Three line multifunction meter having LCD display - 01 No [e] Current Transformer and Potential Transformer - 01 Set [f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | |||||||
Updated dates
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
25 Apr 2026, 6:00 pmClosed
Col Shinde SS
Commander Works Engineers, Station Road, Visakhapatnam - 530 004
SPECIAL REPAIRS FOR CONVERSION OF OVERHEAD LINES TO UNDERGROUND CABLES OF NAD COLONY UNDER GE U I VISAKHAPATNAM
2025_MES_744085_2
82631/E8
Open Tender
Civil Works
180 days
Visakhapatnam
As per NIT
9 documents required · 9 mandatory
₹1,000
GE UTILITY I
₹2.2 L
Yes
15 Jun 2026
4 Apr 2026
27 Apr 2026
4 Apr 2026
25 Apr 2026
11 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 400 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | - | EACH JOB | - | - | |
[a] Onload Changeover switch I-O-II open execution, 4 Pole, 200 Amps – 01 No. [To be fixed after incomer]
[b] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 02 Nos as incomers [Mains+DG]
[d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release- 04 Nos [Outgoing]
[e] Three line multifunction meter having LCD display - 01 No
[f] Current Transformer and Potential Transformer - 01 Set
[g] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | - | - | - | - | |
Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1500 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | - | EACH JOB | - | - | |
[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer]
[b] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release - 01 No [Outgoing]
[c] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing]
[d] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing]
[e] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing]
[f] Three line multifunction meter having LCD display - 01 No
[g] Current Transformer and Potential Transformer - 01 Set
[h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | - | - | - | - | |
Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | - | EACH JOB | - | - | |
[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer]
[b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 01 No [Outgoing]
[c] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing]
[d] Three line multifunction meter having LCD display - 01 No
[e] Current Transformer and Potential Transformer - 01 Set
[f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | - | - | - | - | |
Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 1250 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | - | EACH JOB | - | - | |
[a] MCCB, 630 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer]
[b] MCCB, 250 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing]
[c] MCCB, 200 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing]
[d] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 02 Nos [Outgoing]
[f] Three line multifunction meter having LCD display - 01 No
[g] Current Transformer and Potential Transformer - 01 Set
[h] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | - | - | - | - | |
Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, as per IEC-61349, Platform Mounted, Dust and Vermin proof LT Feeder Panel Board, cubical type, Compartmentalised, fabricated with 3.15mm thick CRCA Sheet duly powder coated, out door canopy type with lifting hooks, consisting of Aluminium bus bar 850 Amps rating (04 Nos) for R-Y-B Phase and Neutral of high conductivity Aluminium and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain/ SMC insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size etc with double stud hinged door, front and back opening, handles on each door with locking arrangement and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 shade, The panel shall be mounted on and including 150mm thick PCC 1:3:6, type C-2 and panel fixed with legs minimum 450mm long made of angle iron frame of size 50x50x5mm including connecting up with existing incoming and outgoing cables, disconnecting and dismantling old panel board complete including and comprising of the following:- | - | EACH JOB | - | - | |
[a] MCCB, 400 Amps, TMA type 4 Pole, 415 V, 36 KA, adjustable thermal release- 01 No [Incomer]
[b] MCCB, 100 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 03 Nos [Outgoing]
[c] MCCB, 63 Amps, TMD type 4 Pole, 415 V, 25 KA, adjustable thermal release - 04 Nos [Outgoing]
[d] Three line multifunction meter having LCD display - 01 No
[e] Current Transformer and Potential Transformer - 01 Set
[f] Colour Coded LED Phase Indicating Lamps for each Phase – 03 Nos (R, Y, B) | - | - | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.58 MB
82631Retenderdoc.pdf
Tender Documents • 0.91 MB
BOQ_850295.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid