| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.9 LAccepted-Finance | ₹3.9 L | L1 | Accepted-Finance L1 |
| 2 | L2₹4.1 LRejected-Finance | ₹4.1 L | L2 | Rejected-Finance L2 |
| 3 | L3₹4.2 LRejected-Finance VILL CHHOTO CHAND GHAR PO BARA CHAND GHAR DIST NADIA PIN 741196 | 741196 | ₹4.2 L | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | A.D.B.S L1 | ASIM KRISHNA MODAK L3 | KARMAKAR ELECTRICAL L2 |
|---|---|---|---|---|---|---|
| 1.00 | FIRE DETECTION
Supply, Installation,Testing & Commisioning of Microprocessor Controlled Addressable Intelligent multisensor detector ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ NOTIFIER / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST ) | 40 | Nos | 3,040 ₹1.2 L | 3,055 ₹1.2 L | 3,050 ₹1.2 L |
| 2.00 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ NOTIFIER/ Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST ) | 6 | Nos | 4,700 ₹28,200 | 4,715 ₹28,290 | 4,710 ₹28,260 |
| 3.00 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base complete ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ NOTIFIER / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Note : Hooter must be Addressable by itself or by using control module. If Loop Power Hooter is not used, separate wiring from control Panel upto the the hooter will be in contractor scope without any extra cost. | 3 | Nos | 4,950 ₹14,850 | 4,985 ₹14,955 | 4,970 ₹14,910 |
| 4.00Supply, Installation, Testing & Commissioning of Power supply 230 V AC to 24V DC with all other accessories. (Make: Reputed) | ||||||
| 5.00 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with 20 mm NB PVC rigid conduit pipe(Make: Precision /Polycab) on the surface of the wall. | 1,000 | Mtr | 99 ₹99,000 | 125 ₹1.3 L | 110 ₹1.1 L |
| 6.00Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. | ||||||
| 7.00The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required. | ||||||
| 8.00 | The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST ) | 1 | unit | 1,30,000 ₹1.3 L | 1,30,660 ₹1.3 L | 1,30,500 ₹1.3 L |
Tender Value
Refer Docs
EMD Value
₹7,882
Closing Date
24 Jan 2026, 12:00 pmClosed
Executive Engineer,PWD
O/o The Executive Engineer Murshidabad Electrical Division P.W.Dte. 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Electrical Installation work of proposed extended OT Complex of Murshidabad Medical College and Hospital, Murshidabad - SITC OF FIRE DETECTION SYSTEM.
2026_WBPWD_989226_1
WBPWD/EE/MsdED/47/e-Q of 25-26
Open Tender
FIRE FIGHTING ORG
20 days
Murshidabad
Please refer Tender documents.
5 documents required · 5 mandatory
₹7,882
13 Mar 2026
15 Jan 2026
26 Jan 2026
15 Jan 2026
24 Jan 2026
17 Jan 2026
FIRE DETECTION Supply, Installation,Testing & Commisioning of Microprocessor Controlled Addressable Intelligent multisensor detector ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ NOTIFIER / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ NOTIFIER/ Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base complete ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ NOTIFIER / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST ) Note : Hooter must be Addressable by itself or by using control module. If Loop Power Hooter is not used, separate wiring from control Panel upto the the hooter will be in contractor scope without any extra cost.
Supply, Installation, Testing & Commissioning of Power supply 230 V AC to 24V DC with all other accessories. (Make: Reputed)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with 20 mm NB PVC rigid conduit pipe(Make: Precision /Polycab) on the surface of the wall.
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/GST )
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx