Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 LAccepted-Finance | ₹1.9 L | L1 | Accepted-Finance Found in order |
| 2 | L2₹1.9 LAccepted-Finance | ₹1.9 L | L2 | Accepted-Finance Found in order |
| 3 | L3₹2.0 LAccepted-Finance | ₹2.0 L | L3 | Accepted-Finance Found in order |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Others-Labour Department Registration Certificate Not Attached & Available in Bid. |
Tender Value
₹1.9 L
EMD Value
₹3,000
Closing Date
31 Jan 2024, 12:00 pmClosed
Executive Engineer
Electy. 400KV S/S Division UPPTCL, Bareilly
MAJOR OVERHAULING OF ELGI MAKE RECIPROCATING AIR COMPRESSORS OF 220KV CIRCUIT BREAKER ALONGWITH OTHER ASSOCIATED WORKS AT 400KV SUBSTATION, BAREILLY
2024_UPTCL_880300_1
E-Tender No. 09/400KV(B)/2023-24
Open Tender
Air Compressor
60 days
Electy. 400KV Substation
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Executive Engineer 400KV S/S Div.
₹3,000
5 Feb 2024
12 Jan 2024
31 Jan 2024
12 Jan 2024
31 Jan 2024
12 Jan 2024
Amount
Major Overhauling of Reciprocating Air Compressor (THPC 200 ELGI make) of 220KV SF6 Circuit Breaker Installed at 400KV Substation, Bareilly 220 KV Bays with all cost of men, materials, T&P etc. required for satisfactory completion of the Job, as per Technical Specification & direction of the Supervising Engineer as per details below.
Dismantling of Compressor Pipelines, HP & LP Headers, and Piston Rings etc. with the temporary arrangement of pipes etc. to maintain the pressure of concern CBs up to 31.5Kg/cm2 / 20Kg/cm2 during repair /overhauling period (01 Job for each Compressor).
Removing of piston Rings by dismantling of H.P&L.P cylinders then cleaning the carbonizing piston & ring grooves thoroughly. Replacement of Ring grooves along with related works. (01Job for each Compressor) as per details below.
H.P. side
L.P. side
Cleaning of HP & LP Headers after opening the headers, then tapping of valve plates and foot valves, complete replacement of Piston assembly 70mm & 50mm size Elgi make. As per details below. (01Job for each Compressor) as per details below.
H.P. side 50mm Part No-000415050
L.P. side 70 mm Part No-000210030
Repairing of worn out Crank & Replacing the damaged Bar Pin, Bushes, both side Bearing, Oil Seal etc. with new ones Elgi make. (01 Job for each Compressor).
Replacement of Air Filter Element by new one. Elgi make Part No-A320122 (01Job for each Compressor) as per sample.
Overhauling of Non Return Valve & Safety Valve of the Compressor by replacement of Teflon seal, Nylon washers, Tension Spring, Lock washer etc. by new ones. Elgi make (01Job for each Compressor).
Replacement of all the Gaskets, Packing’s then Reassembly of the same and finally checking of all pipe lines for No Air leakage and ensuring of inter locking of pressure 31.5Kg/cm2 / 20Kg/cm2 each part should be Elgi make. The above materials provided by the contractor won cast (01Job for each Compressor)
Reassembling of Header and filling of Lubricating Oil (Servo Plus 150) up to required level & Checking, Cleaning & repairing of Electrical Wirings, if required functioning of the Compressors (01Job for each Compressor).
M/s S.S. Refregeration
JBS ELECTRICALS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf