GE P KOCHI
GE P KOCHI NAVAL BASE KOCHI
PROVISION OF POWER SUPPLY FOR DC SERVICING BAY AT CENTRE FOR AVIONICS REPAIR AND SOFTWARE DEVELOPMENT AT NAY KOCHI
2026_MES_799803_1
8072
Open Tender
Civil Works
Item Rate
180 days
GE P Kochi
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE P Kochi
₹90,100
Yes
21 Nov 2026
21 Nov 2026
15 Dec 2026
21 Nov 2026
12 Dec 2026
5 Dec 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Supply, install, testing and commissioning of Transformer Rectifier Unit of 60 KW all as specified as under:- Type : DC POWER SUPPLY, Rating : 60 VDC / 1000A
A. AC INPUT
(i) Voltage : 440V AC ± 10%, (ii) Frequency : 50Hz ± 5%
(iii) Phase : Three phase 4-wire.
B. DC OUTPUT
(i) Boost Voltage : 60V DC, (ii) Output Current : 1000 A Max
(iii) Ripple : Not exceeding 5% rms at rated output voltage and current.
(iv) Steady state voltage : Not exceeding +/-2% for +/-10% supply regulation fluctuation and 10 to 100% load variation.
(v) Output voltage/current stability : Within +/-1% of set value.
(vi) Control power circuitry : Three phase full wave full control thyristorised
bridge fed thru’ 3 phase double wound transformer and
controlled by automatic voltage and current controller unit
with current limiting feature.
C. Measuring Meters : Following Analog Type Meters of 96mm x 96 mm with 90 deg deflection and 1.5% accuracy will be provided in the system for measuring the respective parameters.
a. AC Voltmeter with Selector Switch
b. DC voltmeter to measure voltages at Output
c. DC Ammeter to measure output current
D. INDICATIONS : Cluster LED Lamps provided for the following conditions
a. AC Main ON (R,Y,B), b. Output DC ON
Cluster LED type Annunciation with indication shall be provided for the following conditions a. AC Supply Unhealthy, b. DC Over Current
c. DC Under Voltage, d. DC Over Voltage | 1 | Each | - | - |
| 1.02 | E. PROTECTIONS : Following protections will be provided in the system.
a. AC Input Circuit Breaker, b. DC Output Circuit Breaker
c. Fast acting Semiconductor Fuses for the Rectifier Bridge, d. Phase fail protection, e. Over Current Protection, f. DCPS Current Limit F. SWITCHES & CONTROLS : Following switches and controls are
provided in the systems
a. AC Input Circuit Breaker, b. DC Output Circuit Breaker, c. Test, Accept/ Reset Push Buttons, d. Over current reset push buttons G. SPECIAL FEATURES:-
a. Soft start on DC side
b. Class-F insulation for all Magnetics, c. Automatic Voltage and current Regulation, d. Filter Circuit to limit Ripple, e. DCPS Current Limiting
H. GENERAL :-
a. Cabinet : Free Standing Steel Cabinet, Easy for Accessing,
Installation and Commissioning and Cable Entry at Bottom.
b. Colour : RAL 7032 , c. Painting Process : Powdered Coating
d. Protection : IP – 20, e. Temperature range : 0 to 50°C of operation
f. Relative humidity : 0% to 95% non-condensing
g. Cooling : Natural Cooling.
Make : Liveline/Aplab/Powerone | - | - | - | - |
| 2 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded copper conductor of size 25 Sq.mm 4 core complete all as specified and directed by Engr-in-Charge. | 15 | RM | - | - |
| 3 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded copper conductor of size 300 Sq.mm Single core complete all as specified and directed by Engr-in-Charge. | 50 | RM | - | - |
| 4 | Chemical Earthing with copper earth plate 90cmx60cmx5mm and 32x6mm complete with back filling earth enhancing compound as per IEC 62561-7:2018,connected accessories including copper coppe earth lead 32x6mm by means of bolts,nuts, check nuts and washers of copper and earth strip protected by by GI pipe 50mm dia light grade and connected from earth plate electrode to main switch borad/earthing test point or upto 7.5 mtr whichever is less including inspection /testing chamber and cover /PCC chamber pit in PCC 1:3:6 TYPE C-1,40MM thick pre-cast RCC cover re-inforced with 8mm dia TMT bars@ 10cm C/C on both sides and handle, excavation and earth work in any type of soil and removal upto 50 mtr for special equipments / DB complete all as specified and directed including testing on completion. | 1 | EACH JOB | - | - |
| 5 | Earth continuity conductor or main earthing lead on wall of height up to 40 meter / Ceiling floor by soldering and fixing on porcelain saddles with 20x3 Copper Strip complete all as specified and directed as required. | 3 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.43 MB
Tender.pdf
Tender Documents • 1.02 MB
BOQ_897374.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .