Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.5 CrAccepted-Finance 81 ARYA NAGAR ASSANDH ROAD PANIPAT HARYANA 132103 | PANIPAT | HARYANA | 132103 | ₹17.5 Cr | L1 | Accepted-Finance LOWEST BIDDER |
| 2 | L2₹21.1 CrAccepted-Finance 52 SHANTI NAGAR MODEL TOWN PANIPAT OPPOSITE AMAR STEEL SHUTTERING WORKS | PANIPAT | HARYANA | 132103 | ₹21.1 Cr | L2 | Accepted-Finance HIGHER BIDDER |
Tender Value
₹15.2 Cr
EMD Value
₹30.4 L
Closing Date
29 Sept 2023, 11:00 amClosed
JITENDER SINGH
EE PHE Division No. 2 Sonipat
FOR PROVIDING SEWERGE FACILITY and SEWAGE TREATMENT PLANT
2023_HRY_307663_1
2023FC66CA60 684F 48D0 AFE2 453F4C69DE03587PUH
Open Tender
Civil Works
350 days
KHEWRA
2 documents required · 2 mandatory
₹20,000
Yes
₹30.4 L
Yes
25 Oct 2023
31 Aug 2023
29 Sept 2023
31 Aug 2023
29 Sept 2023
31 Aug 2023
NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentiond as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked. ` 1400 LPM x 40.00 M x 22.50 BHP
COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd 25mm2 3core
COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd 10mm2 3core
HT. ALLUMINIUM CABLE: Supply erection testing of standard make XLPE 3 core HT / 11 KV grade ISI marked Stranded compact circular aluminium conductor, conductor screen with extruded semi conducting compound, XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, cores laid up, innersheath of PVC, galvanised steel flat strip armoured, and overall PVC sheathed cable conforming to is 7098 (part-2) 2011 with up to date amendments for making following connection a) from G.O switch to metering equipment . b) from metering equipment to transformer complete in all respect. Make: Indian Cables Ltd./ Polycab / RR Cables / CAPP / Finolex / Havells / Gloster / Universal / Fort Gloster Industries Ltd./ Indian Cable Co. / Asian Cables Corporation Ltd 35 Sqmm size
LT CABLE ALLUMINIUM: Supply, erection, testing and commissioning of IS marked 3.5 core Cables, Solid Aluminum conductor up to 10sqmm and balance stranded conductor, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Aluminium wire for single core up to 70sqmm and balance Aluminium strip, Glavanised wire for cables up to2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip) extruded PVC type ST2 Outer sheathed, 650/1100V grade as per IS7098 (Part-1) 1988 with up to date amendments along with all accessories complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd. 25 Sqmm size
LT CABLE ALLUMINIUM: Supply, erection, testing and commissioning of IS marked 3.5 core Cables, Solid Aluminum conductor up to 10sqmm and balance stranded conductor, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Aluminium wire for single core up to 70sqmm and balance Aluminium strip, Glavanised wire for cables up to2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip) extruded PVC type ST2 Outer sheathed, 650/1100V grade as per IS7098 (Part-1) 1988 with up to date amendments along with all accessories complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd. 240 Sqmm size
Supply , erection, jointing and commissioning of 10 sqmm ISI marked alluminium cable in trenches under ground for campus lightening including all labour jointing material complete in all respect. (Length = 50 mtr.) Supply erection testing of reputed make LED light 100 wats with fittings and accessories complete in all repects. (LED = 5 no.)
STP 2.00 MLD: Design, construction, erection, testing and commissioning of 2.00 MLD Capacity Sewage Treatment Plant based on Sequential Batch Reactor (SBR) Technology complete in all respect including Landscaping, MCC Panel Room, all other contingent ie. Electrical, Mechanical, Piping and Instrumentation work with PLC and SCADA arrangement for STP integrated with IPS-1, MPS at STP including furniture and laboratory equipments as per detail given in the bid document and following components Supply and installation 2 Nos. fine Screens of suitable size for 2.00 MLD average flow with peak factor of 3. 2 No. High Mast of 9 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 6 No. LED suitable size, outdoor type energy efficient lamps on each pole, 20 no. LED outdoor light with 7 m. high GI pole along road / path including all accessories complete in all respect . Supply and installation of 1 No. 3.65 m wide Main Gate of MS and 1.25 m. wide wicket gate at STP to the entire satisfaction of Engineer-in-charge. (Total weight not less than 500 kg) . Providing and installing 2 No. centrifuges (1Working plus 1 Stand bye) including centrifuge feed pump, all fittings, instrumentations, electric panel board etc. as per design complete in all respect including packing dry sludge in 20 Kg. bag and supplying the same in market Kisan Sewa Kendra or as directed by Engineer-in-charge within the lead as pointed at clause 4.4.4 of the DNIT.
CC TV CAMERA: Providing and Installing 10 CCTV Cameras (4 Cameras for STP and 2 Cameras for each MPS) complete as per satisfaction of the Engineer– in- Charge, within 96 hours of signing the Agreement along with 90 days recording (DVR), 32 inch LED Screen, 16 Channel DVR at STP Site and 8 Channel DVR at MPS Site with connectors, cables, poles and power supply with online real-time output facility. The cameras at both the sites i.e. MPS and STP shall be synchronized at STP site i) At STP and MPS Site- 1 No. PTZ speed dome 360 degree 50X zoom camera, 3 No. 12 mm lens size, 1 Nos. 3.6mm lens size. Make: - CP Plus Internet Protocol minimum 5 MP WDR, Night vision color mode 2.4.2 12 mm very focal with extra IR. CCTV Cameras should be installed and commissioned before starting of the work.
ANNEXE BUILDING: Construction of HT / LT Panel room, PLC room, Centrifuge house, blower room and Lab cum office building including doors, windows and fittings with toilet block including all Sanitary fittings etc. as per drawings approved by SE at MPS and STP covered area built up with RCC framed structure and brick work finished with vitrified glazed tiles flooring, powder coated aluminum frame made with 10 guage sheet having size 100mm x 45mm for chowkhat, 75mm x 45mm for door frame and 45mm x 45mm for window frame with 5mm thick glass AIS/Saint Gobain/ Modi Float
EWQMS: Supply, Installation, Testing, Commissioning, Operation and Comprehensive Annual Maintenance of effluent quality monitoring system at 2.00 MLD capacity STP for online (continuous) measurement of PH, Total Suspended Solids (TSS), Chemical Oxygen Demand (COD), Biological Oxygen Demand (BOD) by single analyzer with various sensors (spectral measurement in the UV-VIS range 200-720mm) performing reagent and chemical free analysis with automatic cleaning of censor, signal cables and power cables, local data acquisition and display of data on continuous basis for up linking the data to CPCB, HSPCB and PHED, TUV approved complete in all respect as per Central Pollution Control Board (CPCB) guidelines for online continuous monitoring system for effluents and as contained in scope of work in the DNIT Multi-parameter measuring converter, for connecting up to 18 intelligent sensors Scope including 8 analog inputs / outputs (4 inputs and 4 outputs) (0/4-20Ma), wide- range power supply Optical COD/BOD and TSS probe with spectral processing of the UV-VIS range, for measurement in the outlet / effluent of 2.00 MLD capacity STP at village Madlouda with integrated with automatic cleaning . Robust digital pH/ORP sensor for pH/ORP electrodes, with built-in pre-amplifier and temperature sensor with Automatic Temperature Compensation (ATC) Cable length 100 Meter (minimum) Sensor adapter cable for all intelligent sensors, with IP68 water proof connection to the intelligent Sensor Net system. Cable length 100 meter (minimum) . Data transfer to CPCB, HSPCB and PHED servers Providing GSM 3G, 4G modem with mobile network connectivity including network
MPS FOR 2.00 MLD STP: Design, construction, erection, testing and commissioning of MPS and following components: RCC Inlet chamber, screening chamber, collecting tank, , wet well sump suitable for 2.00 MLD average flow with peak factor 3 including Providing and installing 5 no. non clog sewage submersible pump sets ie. 1 No.of 4200 LPM, 2 no. of 2800 and 2 no. of 1400 LPM having minimum head of 15 m, equipped with suitable LT panel boards, all safety devices, automatic capacitor bank and suitable size submersible cable from LT panel to pumps complete in all respect . K9 DI pipe of suitable dia at MPS including welding and screwing of flanges, ISI marked D.I. fittings, sluice valves, non returning valves as per requirements even for bye-pass arrangements complete in all respect. 3 Nos. CI Gear Operated Sluice Gate with SS Spindle (SS 410) and seats (SS 304) (2 nos. for screen and 1 no. for partition of collecting tank) as per design Supply and installation of 2 mechanical coarse screens suitable for for 2.00 MLD average flow with peak factor of 3.0 complete in all respect Entire infrastructure except construction of staff quarter, Boundary wall, path ways / roads and work covered under Schedule -1A (HSR - Items) required to be executed at site to make the MPS functional is included in the scope of work for lump-sum job. All the pumping machinery, panel board, Level sensor etc shall be controlled by PLC and SCADA and shall be synchronized with PLC panels at MPS and STP site through broadband internet facility. Raw sewage will be available near boundary wall within the premises of proposed STP but the conveyance of sewage through DI pipe of suitable diameter, from this terminal point to the receiving Chamber of the MPS is included in the Turnkey contract. The Level of the MPS / STP will be as per bed level of existing incoming sewer at MPS. The size and quantities of all the above components will be as per approved structural/ Hydraulic / Mechanical/ Electrical design to be approved by Departmental before actual execution of work
PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electrical LT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following items for 1 Non clog Submersible Pumping a) Main switch suitable ampere 1 No. (LandT Siemens, ABB) b) CT 100/3 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No (LandT Siemens, ABB) f) VSS 1 No. and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp = One Set i) Change over switch of suitable Amp = 1 No. (Each) Panel Board for motors having capacity of 22.50BHP
PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electrical LT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following items for 1 Non clog Submersible Pumping a) Main switch suitable ampere 1 No. (LandT Siemens, ABB) b) CT 100/3 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No (LandT Siemens, ABB) f) VSS 1 No. and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp = One Set i) Change over switch of suitable Amp = 1 No. (Each) Panel Board for motors having capacity of 10 BHP
PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electrical LT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following items for 1 Non clog Submersible Pumping a) Main switch suitable ampere 1 No. (LandT Siemens, ABB) b) CT 100/3 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No (LandT Siemens, ABB) f) VSS 1 No. and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp = One Set i) Change over switch of suitable Amp = 1 No. (Each) Panel Board for motors having capacity of 3 BHP
Operation and Maintenance for complete scope of work mentioned in the DNIT i.e. sewerage system, IPS and STP as per schedule-IV for a period of 5 year after 12 month during defect liability period and 03 Months trial run period and will be charged to the A/Mtc. estimate complete in all respect as per approved NIT (i) Operation and Maintenance during defect liability period (Operation only) after 3 month trial run period.
(ii) Operation and maintenance during 1st year
(iii) Operation and Maintenance during 2nd year.
(iv) Operation and Maintenance during 3rd year.
(v) Operation and Maintenance during 4th year.
(vi) Operation and Maintenance during 5th year.
Bidder Name
Amount
Jai Shree Balaji Constn Co.(GSTN-06AKLPK7500N1ZV)
Rajesh Kadiyan Contractor(GSTN-NA)
Jai Shree Balaji Constn Co.
Jai Shree Balaji Constn Co.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid