Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹28.0 L
EMD Value
₹28,000
Closing Date
3 Mar 2026, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUIVE ENGINEER, Capital Project Electrical Division, Gandhinagar
S.R to E.I , Switchgear & Landscape Light Fitting work At Swarnim park Phase-III( Gh-4 to Ch-4) Gandhinagar. For one year(As per site Requrirement)
278272
23/03 OF 2025/2026
Open
Electrical
Works
Gandhinagar
8 documents required · 8 mandatory
₹1,500
Yes
Executive Engineer, Capital Project Electrical Division, Gandhinagar.
₹28,000
Yes
19 Feb 2026
19 Feb 2026
19 Feb 2026
3 Mar 2026
19 Feb 2026
Name of work:- S.R to E.I , Switchgear & Landscape Light Fitting work At Swarnim park Phase-III( Gh-4 to Ch-4) Gandhinagar. For one year(As per site Requrirement)
Fund Head : 2059 P.W.M & R S.R
Sr. No. Item No. Particulars. Qty. Rate Amount
Signature of Contractor Deputy Executive Engineer Executive Engineer
C.P Electrical R & B Sub Dn 23 C.P Electrical R & B Dn
Gandhinagar. Gandhinagar.
Name of work:- S.R to E.I , Switchgear & Landscape Light Fitting work At Swarnim park Phase-III( Gh-4 to Ch-4) Gandhinagar For one year( As per Requrement).
Sr.No. Qty. Item Rate in Per Amount In Rs.
Replacing old & u/s by Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm
(Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up
to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push &
Rupees Four Hundred
1 127 Pt. accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single 410.06 Pt.
Ten And Paise Six Only
mounting base frame covered with textured/metallic/white front plate modules erected on / in
wall / ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as
directed.(j) in existing pipe erected concealed in wall/ceiling complete Cat. III
Replacing old & u/s by Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green)
both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires up to
mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME step
Rupees Five Hundred
type electronic fan regulator mounted and accessories with earth continuity of following type
2 9 Pt. 556.51 Fifty Six And Paise Pt.
erected on PVC / Metallic/Wooden box, single mounting base frame covered with
textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with
necessary ceiling rose / H.D.Connector as directed.(j) in existing pipe erected concealed in
wall/ceiling complete Cat. III
Replacing old & u/s by Point wiring for on board Looped Plug with 6A Modular type switch & 5 pin
Rupees Two Hundred
socket erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured
3 26 Pt. 257.55 Fifty Seven And Paise Pt.
/metallic/white front plate modules erected on / in wall / ceiling with following type accessories
Fifty Five Only
Replacing old & u/s by Providing following type of Modular Type Accessories mounted with PVC /
Rupees One Hundred
metallic/Wooden box, single mounting base frame covered with textured / metallic/white front
4 10 Nos 151.50 Fifty One And Paise Ea
plate , modules erected with necessary connections as per site situation directed by Engineer In
charge. (1)One No. SP 6 Amp. Cat.III
Rupees One Hundred
5 10 Nos (2) One No 5 pin plug Cat.III 151.50 Fifty One And Paise Ea
Rupees Twenty Five
6 25 Nos (7) Blank Plate Single Cat.III 25.25 And Paise Twenty Five Ea
Rupees One Hundred
7 14 Nos. (9) 16 Amp. SP one way switch Cat.III 180.79 Eighty And Paise Ea.
Seventy Nine Only
Rupees One Hundred
8 14 Nos. (10) 6/16Amp. Universal socket Cat.III 199.98 Ninety Nine And Paise Ea.
Ninety Eight Only
(21) Foot Light as per colour requirement with concealed box, modular accessories, acrylic glass
Rupees Six Hundred
cover with suitable LED watt with all accessories as per following module(C) Six modules
9 84 Nos. 604.99 Four And Paise Ninety Ea.
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to Rupees Twenty Four
10 200 Mtr be erected on/in wall or ceiling erected with necessary PVC fittings & Junction boxes fixed with 24.24 And Paise Twenty Mtr
adhesive solution & Clamps with following dia of pipes, in approved manner as directed.(a)20 mm Four Only
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to
Rupees Thirty Three
be erected on/in wall or ceiling erected with necessary PVC fittings & Junction boxes fixed with
11 150 Mtr 33.33 And Paise Thirty Three Mtr
adhesive solution & Clamps with following dia of pipes, in approved manner as directed.(b)
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to
be erected on/in wall or ceiling erected with necessary PVC fittings & Junction boxes fixed with Rupees Fifty Four And
12 150 Mtr 54.54 Mtr
adhesive solution & Clamps with following dia of pipes, in approved manner as directed.(c) 32 Paise Fifty Four Only
Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride
Rupees Four Hundred
rigid material with ignition free and flame proof confirming BS with necessary end caps Internal
Twenty Eight And
13 80 Mtr and external bend, flat bends, coupler, tee etc..All necessary accessories and measuring of 428.24 Mtr
Paise Twenty Four
following sizes
(2) 100 mm x 50 mm trunking
Replacing old & u/s by Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI
marked stranded Copper conductor wire in following type of pipe to be erected concealed in Rupees Eighty Two
14 130 Mtr /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of 82.82 And Paise Eighty Two Mtr
green colour for earth continuity of following size.(A) with medium class Rigid PVC pipe and Only
accessories.(b) 2 wire 2.5 sq. mm
(E) in existing pipe(e) 4 wire 1.5 sq. mm Rupees Eighty One
15 175 mtr 81.81 And Paise Eighty One Mtr
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded
Rupees One Hundred
Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm
16 150 Mtr 112.11 Twelve And Paise Mtr
copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of
following size(A) with medium class Rigid PVC pipe and accessories.(a) 2 wire 4 sq. mm
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded
Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm Rupees Four Hundred
17 30 Mtr copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of 425.21 Twenty Five And Paise Mtr
following size(A) with medium class Rigid PVC pipe and accessories.(i) 4 wire 10 sq. mm (use Twenty One Only
earth wire of 4 sq.mm )
Providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed
copper conductor with heat resistant PVC insulated conforms to IS 694, IEC - 227 erected in Rupees Ninety One
18 50 Mtr existing pipe of following size (Specifically for control panel, relays, power switchgears, motor 91.91 And Paise Ninety One Mtr
starters & control wiring) with required size of copper lugs, nuts and bolts if required. Only
(f) One wire 10.00 sq. mm
(h) One wire 25.00 sq. mm
Rupees Two Hundred
19 30 Mtr. 236.34 Thirty Six And Paise Mtr.
Thirty Four Only
(i) One wire 35.00 sq. mm Rupees Three
20 30 Mtr. 300.98 Hundred And Paise Mtr.
Ninety Eight Only
Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked
Rupees Forty Six And
21 630 Mtr. copper wires of following size to be erected as directed.(e) 1.50 Sq.mm 3 core round PVC 46.46 Mtr.
Paise Forty Six Only
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled
on single MCPCB, with housing used as a heat sink shall be made of thick sheet Steel
conforming to IS: 513/CRCA/aluminium pressure die cast powder coated and high U.V. &
corrosion resistance with diffuser housed in aluminium casted body with company mark/name Rupees Seven
160V to 270V,Power Factor more than 0.9, THD < 15 %, CCT 3000 K to 6500K, Luminaire Hundred Fifty Eight
efficacy> 85 lumens/watt , LED driver efficiency > 85 % ( fitting required LM-79 & LM-80 And Paise Fifty One
Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED Only
fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A)
Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded
mounting clips complete.IP20 (iv) 22-24 watts, Surge-2 KV Cat-III
Replacing old & u/s by Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt
to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall be made of
thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder coated and high U.V.
& corrosion resistance with diffuser with company mark/name 160V to 270V, Power Factor
more than 0.95, THD < 15%, Rupees Three
CCT 3000 K to 6500K, Hundred Seventy
23 35 Nos Luminaire efficacy> 85 lumens/watt ,LED 373.70 Ea.
Three And Paise
LED driver efficiency > 85 % Seventy Only
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of
Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity
between the ranges shown.)(A) Tube Light with integral driver(iv) 22-24 Watts, Surge - 2KV,IP-
20, conventional 4 feet Cat-III
Replacing old & u/s by Supplying and erecting LED street light / Flood light fittings with High
power White LEDs wattage of 3 Watt and above assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish
powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses,
with toughened glass with company mark/name engraved or embossed 160 to 270 V,Power Rupees Seven
Factor more than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire Thousand Two
24 40 Nos efficacy> 100 lumens/watt . LED driver efficiency > 85 %.( fittings required LM-79 & LM-80 7266.95 Ea.
Hundred Sixty Six And
certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED Paise Ninety Five Only
fittings.The Engineer incharge may select any wattage capacity between the ranges shown.)(B)
Flood Light (IP-65), Surge protection -4KV integral and ,Light must have 440VAC line supply
with over-voltage protection. (iv) above 90 to 120 watts Cat-III
(vi) above 160 to 200 watts Cat-III
Thousand Six Hundred
Forty Seven And Paise
(C) Post Top Lantern LED fitting comprises of finish cast aluminum spigot and spun aluminum
canopy fixed with opal polycarbonate, pipe arrangement for vertical mounting driver and
Thousand Ninety Two
26 22 Nos accessories wired upto terminal block.IP 65(i)20- 30W Cat-III 4092.52 Ea.
And Paise Fifty Two
Replacing old & u/s by Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. and above at 415 V . having normal current
27 2 Nos rating 250A. with variable thermal & magnetic release suitable to work on A.C.supply 50 c/s. with 20946.39 Ea.
Hundred Forty Six And
all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S.
Paise Thirty Nine Only
housing. ICS=100% of ICU only Cat III
Replacing old & u/s by Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. at 415 V. having normal current rating 125A.
Thousand Fifty Five
28 4 Nos with Fixed thermal & magnetic release suitable to work on A.C.supply 50 c/s. with all internal 8055.76 Ea.
And Paise Seventy Six
connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III
Providing and erecting Approved make Four pole moulded case circuit breaker having breaking
Rupees Six Thousand
capacity ICU of 25 KA. at 415 V,having normal current rating up to 25 A to 100A. with Fixed
One Hundred Seventy
29 9 Nos thermal & magnetic release suitable to work on A.C. supply 50 c/s. with all internal connections, 6173.12 Ea.
Three And Paise
spreader tinned copper & complete erected in existing 16 G.M.S. housing. ICS=100% of ICU
Replacing old & u/s by Providing and erecting Miniature circuit breaker single pole 6A to 25A Rupees One Hundred
30 522 Nos suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be erected in 112.11 Twelve And Paise Ea.
existing box. confirming to IS 8828/1996 with ISI Mark Cat.III Eleven Only
Replacing old & u/s by Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C Rupees Seven
31 45 Nos Curve) having 10KA breaking capacity & confirms to IS :8828 in existing box having following 737.30 Hundred Thirty Seven Ea.
capacity (c)63 Amp Cat.III And Paise Thirty Only
Replacing old & u/s by Providing and erecting Sheet Steel powder coated MCB distribution board
- flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS
8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should
32 8 Nos 3412.79 Hundred Twelve And Ea
be used of same company of MCB to be used) suitable for (B) three phase incoming and single
Paise Seventy Nine
phase horizontal type outgoing Per phase isolation type (PPI) (b) sheet steel double door (iii)8
providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of
Rupees One Thousand
30 mA and Short Circuit withstand capacity of 10 KA and suitable for operation on single phase
Nine Hundred Sixty
33 84 Nos 240 V,50Hz. having characteristic of quick action & tripping with all advance feature & do not 1969.50 Ea.
Nine And Paise Fifty
incorporate any electronic component. for following Max. rating erected as directed (i)
Amps.DP Cat. III
34 25 Kg. Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 SWG. 77.77 Seven And Paise Kg.
Seventy Seven Only
Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing
Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot
dipped G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe
dia of 25 mm having 200-250 Micron galvanising, connection terminal dia of 12mm with constant
ohmic value surrounded by highly conductive compound with high charge dissipation suitable for
following type of applications with chamber and heavy duty cover. (A)(approved make OEM has Rupees Four
to submit test certificate including value of earth resistance of installation duly stamped and Thousand Five
35 7 Nos signed by agency and officer Incharge has to ensure the value of earthing resistane mentioned in 4591.46 Hundred Ninety One Ea.
test Certificate) & having back filling compound of (B) Inner chemical (CCM Compound)- And Paise Forty Six
Resistivity:- 0.2 ohm / meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & Only
dry form, Sulphar content:- <2%(C) Back fill Compound :- Earthing compound should be capable
to retain moisture for long time Necessary test report must be submitted by Agency. (a) For
Electrical Installation up to 440V in normal soil
Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg.
Providing , erecting , fabricating the M.S. structure as per requirement on site incorporating
proper size of M.S. angles,square,round, flats, bars, channels, sections complete with cutting, Rupees Seventy
36 80 Kg. welding, grinding & finishing duly painted with one coat of red oxide with erection on site as per 77.77 Seven And Paise Kg.
direction of engineer in charge with necessary grouting, cementing, plastering & finishing Seventy Seven Only
Providing & erecting Approved make Power Saving 50 Watt Ceiling Fan with double ball bearing Rupees One Thousand
ISI mark with Condenser 230 volt A.C. 50 Hz 1200 mm sweep complete having 3blades with Nine Hundred Forty
aluminium blades with , canopy & 30 cm. down rod erected with earthing.(Make shall be Eight And Paise
approved by Engineer in charge)) Twenty Nine Only
Rupees One Hundred
Supplying and erecting 19 / 20 mm. nominal bore Medium Class M.S. Pipe down rod erected
38 9 Mtr. 108.07 Eight And Paise Seven Mtr.
duly painted for fan complete with proper insulation without leakage and earthing.
Supplying & erecting fan hook box of 10 mm M.S. round bar bounded to the RCC bars up to Rupees One Hundred
39 9 Nos 50mm length each side and pierced through a 16 Gauge M.S. box / Heavy Duty PVC box 108.07 Eight And Paise Seven Ea.
complete erected concealed in Ceiling with necessary finishing. Only
Rupees Eighteen And
40 9 Nos Providing 2.5mm.thick laminated acrylic sheet to cover the fan hook or Fan box. 18.18 Ea.
Paise Eighteen Only
Supplying and erecting triple pole & neutral 440V / 500V panel mounting Copper Busbars with
four equal Nos. of electrolyte bus having current density not more than 1.6 Amp. / sq.mm (Rated Rupees Three
current / cross section area) duly wrapped with colour insulating tape for phase sequence of Thousand Two
Rn.Mt following current carrying capacity, erected with necessary bus bar supports /insulators, main
41 10 3202.71 Hundred Two And Rn.Mtr
r cable socket to each bar, erected in existing cubical panel with necessary connections.(B) Paise Seventy One
Suitable for 200 Amp. capacity Only
(C) Suitable for 300 Amp. capacity Rupees Four
Rn.Mt Thousand Nine
r Hundred Nine And
Paise Sixty One Only
Replacing old &u/s by Providing & erecting weather proof, dust & vermin proof, floor mounted
front operated indoor type cubical panel board necessary IP-42 and above protection as per
approval from engineer incharge made from 14 SWG thick CRC M.S. sheet for outer body &
43 doors, 16 SWG thick CRC M.S.sheet for internal partitions with necessary accesories
supporting angles/ flats channel including cutting, bending, drilling, welding, riveting with internal
partitions & cable alley as per requirements & instruction of engineer-in-charge with erection of
supplied switch gears, BUSBARS, suitable size of inter connecting PVC copper wire / copper-
aluminium strips, rubber grommets, rib, bakelite control fuses/MCB for measuring instruments,
earth bus & earth bolts, foundation flange - bolts-base Plates, sufficient nos. of hinged doors,
handles with locking arrangement and rubber gasket,heavy duty end terminal connection,danger
notice board,necessary ventilation,earthing strip complete. The Panel shall be painted with
epoxy powder coating.
(The rates excludes the cost of switchgears, bus bars, inter connecting mains & Copper
Aluminium strips, meters, Fuses etc. The dimension shall be measured excluding base beams) Rupees Fourteen
Sq.Mt The panel shall be supplied with following approved manufacturers with following size.(B) The Thousand Nine
r standard companies switch gear shall be used and only manufacturers at CPRI approved factory Hundred Two And
(i) with 350 mm. Depth Paise Fifty Five Only
Supplying and erecting approved make panel mounting type Digital Voltmeter having 3 digits Rupees One Thousand
LED display, 0 to 750 AC Volts range erected on existing panel board with all connection, wiring Two Hundred Seventy
44 7 Nos etc .with manufacturers calibration certificate. 1275.63 Ea.
Five And Paise Sixty
Supplying and erecting approved make panel mounting type Digital Ammeter having 3 digits Rupees One Thousand
LED display, external CT operated, calibrated for 0 to 1000 Amps suitable to operate on 500 Volt Five Hundred Fifty
45 7 Nos AC , erected on existing panel board with all connection, wiring etc .with manufacturers 1558.43 Ea.
Eight And Paise Forty
calibration certificate. Three Only
Supplying and erecting Ammeter / Voltmeter selector switch for 3 phase AC Supply 500 V on Rupees Three
Hundred Seventeen
46 14 Nos existing panel board with necessary connections. 317.14 Ea.
And Paise Fourteen
Providing & erecting L.T. Current Transformer with bar primary 50/5 to 1000/5 ratio 15 VA Rupees Two Hundred
burden erected in existing CRCA box duly secured with insulating materials connected to the Seventy Four And
meter Paise Seventy Two
Supplying and erecting approved make suitable panel indicator LED type lamp, lens cover, Rupees Forty Three
48 21 Nos complete erected with necessary connections. 43.43 And Paise Forty Three Ea.
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor Rupees Five Hundred
49 270 Mtr. for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size 540.35 Forty And Paise Thirty Mtr.
of cables (F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core) Five Only
Replacing old & briken by Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable Rupees One Hundred
50 2325 Mtr. multistrand / Solid Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or 126.25 Twenty Six And Paise Mtr.
in existing trench / pipe of following size of cables(B) 4 core 6 Sq. mm Twenty Five Only
Making trench in soft soil of suitable width of 90 cm deep for laying cable or locating the fault all
Rupees Fifty Five And
51 1590 Mtr. over the run and back filling the same and making the surface as normal ground. 55.55 Mtr.
Paise Fifty Five Only
Making trench in Hard Murrum / Tar Road of suitable width of 90 cm or required depth for laying Rupees Seventy Four
52 150 Mtr. any size of cable or locating the fault all over the run and back filling the same and making the 74.74 And Paise Seventy Mtr.
surface as normal ground. Four Only
(B) If additional machinery like hammer driller or JCB use [Add] Rupees Three
Hundred Fifty Seven
45 Mtr. 357.54 Mtr.
And Paise Fifty Four
Providing & laying approved make Double walled corrugated pipes (DWC) of
polyethylene(conforming to IS 14930 II )with necessary connecting accessories of same material
Rupees Sixty Two And
53 1370 Mtr. at required depth in existing trench for laying of cable. below ground / road surface for 62.62 Mtr.
Paise Sixty Two Only
enclosing cable (A)50 mm outer dia
Locating Underground Cable Fault of Underground Cable including digging,pin pointing with
cable route tracker bu using cable fault location equipment like cable fault Van/Vehicle with
Rupees Six Thousand
supportive meters and accessories & doing high pressure testing of cable for checking
Eight Hundred Forty
54 4 Job healthiness of cable with suitable equipment after jointing of the faulty cable (excluding jointing 6847.80 Job.
Seven And Paise
kit) with report of showing distance from main source approx.(a) LT Cable 35 sq.mm and above
Providing and, fixing heavy duty flange type brass double compression type cable gland with
rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc Rupees One Hundred
55 6 Nos for following size of cables.(E) 3 X 1/2 core 120 Sq.mm 140.39 Forty And Paise Thirty Ea.
Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size
evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium Rupees Six And Paise
plated nut bolts in an approved manner. (A) 1.5/ 2.5/4/6 Sq.mm Six Only
Rupees Forty Five And
24 Nos (G) 120 Sq.mm. 45.45 Ea.
Paise Forty Five Only
Disconnecting the cable connection and Providing straight joint with PVC mould using heat shrink
/cast resin type epoxy compound Insulating material and making the joint complete using Rupees Two Thousand
necessary in line connectors, hardener, earth continuity connection, spacers etc. and Six Hundred Fifty Four
57 3 Nos reconnecting the same & ensure the joint resistance within the limits as per IS(C) 120 to 300 Sq. 2654.28 Ea.
And Paise Twenty
mm cable.. Eight Only
Supplying & erecting approved make Digital time switch having lithium cell 6 years operative and
operate battery backup 1 channel day clock with 14 memory programme, suitable to operate on Rupees Three
240V + 5%, 16A with, floating contacts Minimum switching setup time 1 minimum & LCD display. Thousand One
58 5 Nos Also comprised permanent ON/OFF switching. Programming switches & housed in fire proof 3168.37 Hundred Sixty Eight Ea
thermoplastic enclosure & transparent cover erected as required with necessary connection And Paise Thirty
erected as directed. Seven Only
Supplying & erecting power contactor ,AC3 duty for time switch complete erected as per direction Rupees Two Thousand
Cat III (D) 4 pole 440V 40 Amp. Seven Hundred Eighty
Two And Paise Fifty
Replacing old and damaged by SITC of LED fitting of Operating Temperature 10°C to 50°C,
Rated Input Voltage & requency 220-240 V AC, Rated Input Wattage 12W ± 10%, Rated Input
Current 0.060 Amp Nominall. Power Factor 0.90, ATHD <20%, Rated Luminous Flux 600 lm
(tolerance as per BIS), Rated Luminaire Efficacy 50 lm/W (tolerance as per BIS), Correlated
Color Temperature (CCT) 5000 K (tolerance as per ANSI), Color Rendering Index (CRI) >90 Ra, Rupees Seven
Beam Angle- Asymmetric, river Efficiency 380%, LED Life span >50000 Hrs (Ta=25°C @L70,) Thousand Three
60 75 Nos Housing- Die Cast Aluminium 6 with PU Coating Lens/Reflector Clear Polycarbonate Diffuser, 7321.49 Hundred Twenty One Ea
Mounting-Surface, Protections: Over Voltage Protection 300 V AC upto 20 min., Surge Protection And Paise Forty Nine
±2.0KV, Protection Class-Class & Ingress Protection (IP Rating) IP66, Impact Protection (IK Only
Rating) IK07, Short Circuit Protection Provided, Open Circuit Protection (No Load) Provided,
Reverse Polarity Protection Provided Product code LGTP03X012XW
Replaced old & u/s by Supplying and erecting led lamps with following wattage capacity of 220 to
240 voltage, minimum 15000 burning hours life, 500 V in built-surge protection,Polycarbonate
diffuser, mounting suitable for E14 / E27 / B22 lamp holders, pf >=
Rupees Four Hundred
61 96 Nos (A) LED Lamps integral type, with PC diffuser suitable LAMP holder (v) 30 watts Cast-III 404.00 Ea
Rupees Twenty Seven Lakh(s) Ninety Seven Thousand Two Hundred Eighty Seven And Paise Ninety Two Only
EXECUTIVE ENGINEER
CAPITAL PROJECT ELECTRICAL DIVISION
I/We am/are willing to carry out the work at(No above rates allowed) ____________% below ___________________________________
__________________percent (Should be written in figures and words) below the tendered rates mentioned above.
Amount of my/our tender works out as under :
Put to Tender Rs. Put to Tender Rs.
(Please strike out whichever is not applicable)
1 I/We hereby declare that I/We have visited the site, fully exquisite myself/ourselves with the local situation regarding materials and other factors pertaining to the work before
submitting this tender.
2 I/we hereby declare that I/We carefully studied the conditions of specifications and other tender documents of this work and agree to execute the same accordingly.
3 A tender with any overwriting in percentage (should both in word and figures) rejected out right.
4 Insertions and/or corrections in the percentage quoted ( both in word and figures) resulting into increase in the value of the work shall be rejected outright unless it is
authenticated by the office opening the tender at the time of opening of tender.
5 Dismentaling the existing material taken by contractor as mention rates.
Signature of Contractor Deputy Executive Engineer Executive Engineer
C.P Electrical R & B Sub Dn 23 C.P Electrical R & B Dn
Gandhinagar. Gandhinagar.
List of Dismental
Name of work :- S.R. To Landscape Light Fitting Work at Swarnim Park Phase-III (Gh-4 to Ch-4) , Gandhinagar.
Item Description Qty. Unit C.Cost D.M % DM Rate Amount
Cost of old u/s & broken Pt. wiring, Accessories &
1 1 lot Lump sum Lot. 2000.00
Cost of old u/s rusted Bollards with its foundation
2 bolt(Non SOR)
3 Cost of old u/s Downlight (SOR-2-15-3.) 6 Nos 717 4% 28.68
4 Cost of old & u/s conventional type Fitting(SOR-2-7-1.) 35 Nos 450 4% 18
5 Cost of faulty Cable 1 lot Lump sum lot. 5000
6 Cost of old u/s 250 MCCB( SOR-3-4-4.) 2 nos 20611 5% 1030.55
7 Cost of old u/s 125 MCCB( SOR-3-4-2.) 4 nos 7848 5% 392.4
8 Cost of old u/s 100 MCCB( SOR-3-4-1.) 9 Nos 5984 5% 299.2
9 Cost of old u/s SPMCB (SOR-3-10-1-B) 522 Nos 98 5% 4.9
10 Cost of old u/s DPMCB (SOR-3-10-2.) 24 Nos 284 5% 14.2
11 Cost of old u/s FPMCB (SOR-3-10-5) 45 Nos 704 5% 35.2
12 Cost of old & u/s Flood light(SOR-2-7-1.) 8 Nos 9382 4% 375.28
13 Cost of Old Manual Timer (SOR-6-7-2.) 5 Nos 3094 5% 154.7
14 Cost of Old Contactors (SOR-6-7-3.) 5 Nos 2729 5% 136.45
15 Cost of Old & u/s Panel Cup board.(SOR-6-7-3.) 1 lot. Lump sum Lot. 3000.00
Dy. Ex. Engg. Ex. Engg.
Signature of Contractors C.P. Elect. Sub Div. no. 23 C.P. Elect. Division
Gandhinagar. Gandhinagar.
Name of work:- S.R to E.I , Switchgear & Landscape Light Fitting work At Swarnim park Phase-III( Gh-4 to Ch-4) Gandhinagar.
For one year(As per site Requrirement)
SR.NO. ITEM MAKE LIST
1 Wiring Accessories Anchor, Schneider, Legrand, LK(L&T)
2 Wires & Cable KEI,Polycab,Finolex, RR Kabel
LED Tube Fittings,lamps, Post top
3 Philips, LT, Jaguar
4 Switchgear LK(L&T), ABB, Schneider, C & S, Indoasian.
5 Fan Crompton Greaves, Orient, Usha.
Dy.Ex.Engg Executive Engineer
C.P.Elect sub Div.23 C.P.Elect.Division
Gandhinagar Gandhinagar.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
23 - 2025-26.pdf
ANNEXURE A.pdf
G S T LTR.pdf
GR.pdf
pq.pdf
SBD Document.pdf
SCHEDULE A B C DM AND MAKELIST.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .