Loading…
Loading…
Tender Value
₹5 Cr
EMD Value
₹5 L
Closing Date
3 Oct 2026, 12:00 pm6d left
Deputy Municipal commissioner Gandhinagar Municipal Corporation, Gandhinagar
TENDER FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OFSOLAR POWER SYSTEM AT VARIOUS PLACES UNDER GMC
344609
Tender No. 96 of 2026-27
Open
Miscellaneous Services
Works
Gandhinagar
3 documents required · 3 mandatory
₹6,000
Deputy Municipal Commissioner, Gandhinagar Municipal Corporation
₹5 L
12 Sept 2026
12 Sept 2026
12 Sept 2026
3 Oct 2026
12 Sept 2026
NAME OF WORK:PROVIDING SOLAR POWER SYSTEM AT VARIOUS PLACES UNDER GMC
SOR No. Qty. Unit Description SOR Rate Per Amount
1 14.1.1 Supply, Installation, Testing & Commissioning of following size of Grid Tied Solar Power Plant with
Solar Panels (ALMM approved): Frame Material : Anodized Aluminum alloy Frame With Twin Wall Profile, Front
Cover : High Transmission Low-Iron Tempered Glass (AR Coated), High efficency and positive power tolerance
Pmax: 0/+5, Module Efficiency should be approx. 19.5%-22%, Normal operating temperature 45'C, Junction
Box with Waterproof IP67 & MC4 Compatible and Enclosed with Bypass diodes, 100% Electroluminescence
test to ensure error free Modules, Thep. temp. co-efficient of the PV module shall equal or better than -
0.45%/degree C. Solar PV modules of minimum fill factor 75% to be used. Unit Production:- More than 4.5 Unit
/kw /day (Actual)(1Year Avg) With 10 year Product warranty and 25 year Linear Power Warranty includes all
mechanical and electrical parameters of the Solar panel. Modules must be complied to the DCR(Domestic
content requirements). The Ration of AC to DC is 5:6 for the Installation capacity which are given in AC KW.
Solar Inverter: MPPT Range: MPPT Range: 80-1000 V , Max efficiency: 97.5% - 98.9%, O/p Frequency:
50/60Hz, Operating Altitude (m) ≤4000, O/p Power Factor: ~1, O/P THDi: <3%, Operating Tempreture Range: -
25~60°C, Integrated protection of Inverter are Anti-islanding Protection, Input Reverse Polarity Protection,
Insulation Resistor Detection, Ground fault protection, Residual Current Monitoring Unit, Output Over Current
Protection, Output Short Circuit Protection, Output Over Voltage Protection, PV array string fault Protection.
Protection Degree: IP65, User Interface LCD & APP, Datalogger & Communication: GPRS / Wi-Fi.
Integrated, Input Reverse Polarity Protection Integrated, Insulation Resistor Detection Integrated, Residual
Current Monitoring Unit Integrated, Output Over Current Protection Integrated, Output Short Circuit Protection
Integrated, Output Over Voltage Protection Integrated, Protection Degree: IP65, User Interface LCD &
APP,Datalogger & Communication: GPRS / Wi-Fi, Module Mounting Structure: The mounting (Rectangular pipe
/ square pipe / circular pipe) with requisite cross bars, nuts and bolts, etc. shall be Hot deep galvanized with
minimum 80micron coating. The Rectangular / square /circular hollow pipe section used for the structure should
have a minimum thickness of 2.0 mm. other than above, the material thickness should be minimum 2.5 mm. A
certificate of a structural engineer certifying the strength and stability of the mounting structure to withstand the
weight and wind speed of 150 km/hour throughout the life span of 25 years of the system, shall be submitted by
the vendors. Hot Dipped Galvanized steel coils. suitable arrangement for base plate for foundation , solar panel
mounting, the structure should be suitable for carry the load of solar panel,wiring, sprinkler system etc. with
necessary foundation work/wall mount, j bolt, anchor fastner etc. the nut bolt used for installtion of stucture
should be (SS 304) quality.The ground clearance of the bottom most edge of solar panel shall not be less than
300 mm to 1200 mm or as per site’s technical/feasibility requirement.
a. Column –The minimum section (thickness) should be 60MM*40MM
b. Rafter - The minimum section (thickness) should be 60MM*40MM
c. Purlin - The minimum section (thickness) should be 40MM * 40MM Balane of System with necessary
Swichgears (Suitabel size and protection of ACDB & DCDB), inter connecting wiring, earthing system as per the
CEIG drawing approval, lightining arrester system as per the CEIG drawing approval, all liasoning work with
various gov. dipartment like state nodal agency,DISCOM & CEIG is included in agency scope
(Excluding All charges namely GEDA Application fees, Solar connectivity Charges, Meter connectivity Charges,
Meter testing Charges and system stability/strenthning charges.)
1 PER KW (A) Grid Tied Solar Power System: 1 - 6 kW (Single phase) 54500.00 PER KW
1 PER KW (B) Grid Tied Solar Power System: 7 - 10 kW (3 - phase) 51500.00 PER KW
1 PER KW (C ) Grid Tied Solar Power System: 11 - 25 kW (3 - phase) 49600.00 PER KW
1 PER KW (D) Grid Tied Solar Power System: 26 - 50 kW (3 - phase) 49250.00 PER KW
1 PER KW (E) Grid Tied Solar Power System: 51 - 100 kW (3 - phase) 47500.00 PER KW
1 PER KW (F) Grid Tied Solar Power System: 101 - 250 kW (3 - phase) 46500.00 PER KW
1 PER KW (G) Grid Tied Solar Power System: 251 - 500 kW (3 - phase) 45750.00 PER KW
2 14.2.1 S.I.T.C of Poly Crystline/Mono Crystline PV Module (ALMM approved) with 72 Cells - 150 Cells or More , Frame
Material : Anodized Aluminum alloy Frame With Twin Wall Profile, Front Cover : High Transmission Low-Iron
Tempered Glass (AR Coated), High efficency and positive power tolerance Pmax: 0/+5, Module Efficiency
should be approx. 18%-21%, Normal operating temperature 45'C, Junction Box with Waterproof IP67 & MC4
Compatible and Enclosed with Bypass diodes 100% Electroluminescence test to ensure error free Modules,
Thw temp. co-efficient of the PV module shall equal or better than -0.45%/degree C. Solar PV modules of
minimum fill factor 75% to be used. Unit Production:- 4 to 5 Unit /kw /day (Actual)(1Year Avg) With 10 year
Product warranty and 25 year Linear Power Warranty.
1 PER WATT (A) Moudule o/p Range: 250 - 335 watt, Maximum Power Voltage Vmpp: 26 -38 V, Maximum Power Current
Impp: 8 - 8.9 A
1 PER WATT (B) Moudule o/p Range: 365 - 390 watt, Maximum Power Voltage Vmpp: 39 - 40 V, Maximum Power Current
1 PER WATT (C) Moudule o/p Range: 435 - 455 watt, Maximum Power Voltage Vmpp: 40 - 42 V, Maximum Power Current
1 PER WATT (D) Moudule o/p Range: 480 - 505 watt, Maximum Power Voltage Vmpp: 41 - 42 V, Maximum Power Current
Impp: 12 - 13 A
1 PER WATT (E) Moudule o/p Range: 520 - 545 watt, Maximum Power Voltage Vmpp: 41 - 42 V, Maximum Power Current
3 14.3.1 S.I.T.C of Solar Inverter Gried Tied: MPPT Range: 80-1000 V, Max efficiency: 97.5% - 98.9%, O/p Frequency:
50/60Hz, Operating Altitude (m) ≤4000, O/p Power Factor: ~1, O/P THDi: <3%, Operating Tempreture Range: -
25~60°C, Anti-islanding Protection: Integrated, Input Reverse Polarity Protection Integrated, Insulation Resistor
Detection Integrated, Residual Current Monitoring Unit Integrated, Output Over Current Protection Integrated,
Output Short Circuit Protection Integrated, Output Over Voltage Protection Integrated, Protection Degree: IP65,
User Interface LCD & APP,Datalogger & Communication: GPRS / Wi-Fi (Optional)
1 Per Watt (A) Solar Inverter: 1 kW to 3 kW: Max. input Current: 10A, Max DC i/p Power: 1300-3900W & Nominal o/p
Power: 1000-3000W Nomimal O/p Voltage: 220/230 V 1-Phase, Nominal O/p Current: 5-13.5A.
1 Per Watt (B) Solar Inverter: 3 kW to 6 kW: Max. input Current: 11A, Max DC i/p Power: 3900-7200W & Nominal o/p
Power: 3000-6000W, Nomimal O/p Voltage: 220/230 V 1-Phase, Nominal O/p Current: 13.6-27.3A.
1 Per Watt (C) Solar Inverter: 6 kW to 15 kW: Max. input Current: 22 A, Max DC i/p Power: 7800-19500 W & Nominal o/p
Power: 6000-16500 W, Nomimal O/p Voltage: 400 V 3-Phase, Nominal O/p Current: 10-24A,
1 Per Watt (D) Solar Inverter: 15 kW to 25 kW: Max. input Current: 27 A, Max DC i/p Power: 22100-32500W & Nominal o/p
Power: 15000-25000W, Nomimal O/p Voltage: 400 V 3-Phase,Nominal O/p Current: 25-37A.
1 Per Watt (E) Solar Inverter: 25 kW to 50 kW: Max. input Current: 30 A, Max DC i/p Power: 22100-51500 W & Nominal
o/p Power: 25000-50000W, Nomimal O/p Voltage: 400 V 3-Phase,Nominal O/p Current: 37-80A.
1 Per Watt (F) Solar Inverter: 50 kW to 100 kW: Max. input Current: 40 A, Max DC i/p Power: 66500-130500 W & Nominal
o/p Power: 50000-100000 W, Nomimal O/p Voltage: 400 V 3-Phase,Nominal O/p Current: 80-144 A.
1 Per Watt (G) Solar Inverter: 100 kW to 136 kW: Max. input Current: 40 A, Max DC i/p Power: 130.5 -176.5 KW & Nominal
o/p Power: 100-136 KW, Nomimal O/p Voltage: 540 V 3-Phase, Nominal O/p Current: 144-145 A,
1 Per Watt (H) Solar Inverter: 136 kW to 200 kW: Max. input Current: 40 A, Max DC i/p Power: 176.5-260KW & Nominal
o/p Power: 136-200KW, Nomimal O/p Voltage: 540 V 3-Phase, Nominal O/p Current: 144-145A,
4 14.4.1 1 PER KG Supplying and Erecting Seamless Box Pipe of suitable size for rooftop solar installations with good stability
agaist wind, Thickness 2 mm and 80 micron, Hot Dipped Galvanized steel coils. suitable arrangement for base
plate for foundation , solar panel mounting, the structure should be suitable for carry the load of solar
panel,wiring, sprinkler system etc. with necessary foundation work/wall mount, j bolt, anchor fastner etc. the nut
bolt used for installtion of stucture should be (SS 304) quality.
box. pipe ref. size (A) 40 x 40 x 2mm, (B) 50 × 50 × 2mm, (C.) 60 x 40 x 2mm,(D) 72 x 72 x 2.5mm
5 14.4.2 1 PER KG Supplying and Erecting 'C' Channel of suitable size for rooftop solar installations with good stability agaist
wind, Hot Dipped Galvanized steel coils. It have suitable arrangement for base plate for foundation Screw
Arrangement , solar panel mounting, the structure should be suitable for carry the load of solar panel,wiring, 177.00 PER KG
sprinkler system etc. with necessary foundation work/wall mount, j bolt, anchor fastner etc. the nut bolt used for
installtion of stucture should be (SS 304) quality.
6 14.4.3 1 Ea. Supplying and Erecting Stainless Steel Nut Bolt (SS 304) for Installation of Solar PV Module, Structures, and
other related items with required size as engineer in charge demands for project Size, length upto 10 x 150 mm
7 14.5.1 DC Cable: Electron beam cross linked compound,UV, Ozone, Temperature & Hydrolysis resistant Flame
Retardant, Low Smoke Excellent Encapsulation
Very long / Service life >
Standards / Material Properties:
Fire performance : IEC 60332-1-2
Smoke emission : IEC 61034/ EN 50268-2
Halogen Free: EN 50267-2-1/-2, IEC 60754-2
Toxicity: EN 50305, ITC – Index <3
Ozone Resistant : EN50396
Weathering UV: HD 605/A1 or DIN
Approvals : EN 50618; H1Z2Z2-k
with suitable sized of PVC pipe(ISI Mark) and Clamps,Shadels,Lugs.
1 PER MTR (A) 1 core 4 sqmm copper DC cable Colour Red 88.00 PER MTR
1 PER MTR (B) 1 core 4 sqmm copper DC cable Colour Black 88.00 PER MTR
8 14.6.1 1 Ea. S,I,T.C of Distribution board from AC Side, ACDB 1-Phase - 1 kW - 6 kW: AC MCB: 16-25A, 2POLE, C-
CURVE, 10KA, AC SPD: 40KA, 1P+N, TERMINAL/END PLATE/END CLAMP: 6SQMM (KUT6) FOR OUTPUT,
AC Interconnection with suitable size wire/cable, All switchgears and connection are enclosed with IP66
Enclosure which have transperant cover in frontside to view and operate the MCB position.
9 14.6.2 1 Ea. S,I,T.C of Distribution board from AC Side ,ACDB 3-Phase - 6 kW - 10 kW: AC MCB 20-32A, 4POLE, C
10KA, AC SPD 40KA, 3P+N, TERMINAL/END
PLATE/END CLAMP: 6SQMM (KUT10) FOR OUTPUT,AC Interconnection with suitable size wire/cable. All
switchgears and connection are enclosed with IP66 Enclosure which have transperant cover in frontside to view
and operate the MCB position.
10 14.6.3 1 Ea. S.I.T.C of Distribution board from AC Side, ACDB 3-Phase - 11 kW - 20 kW: AC1 DUTY CONTRACTOR‐40A
100A MCCB 4P(Cat III), 3 PHASE SPD, VOLTAGE MONITORING RELAY,
ELR WITH CBCT, PHASE INDICATING LAMP, POWER CABLE &
OTHER ACCESSORIES, All switchgears and connection are enclosed with IP66 Enclosure and operate the
11 14.6.4 1 Ea. S.I.T.C of Distribution board from AC Side ,ACDB 3-Phase - 21 kW - 50 kW: AC1 DUTY CONTRACTOR‐80A
100A MCCB 4P(Cat III), 3 PHASE SPD, VOLTAGE MONITORING RELAY,
ELR WITH CBCT, PHASE INDICATING LAMP, POWER CABLE &
OTHER ACCESSORIES, All switchgears and connection are enclosed with IP66 Enclosure and operate the
12 14.6.5 1 Ea. S.I.T.C of Distribution board from AC Side , ACDB 3-Phase - 51 kW - 100 kW: which includes AC1 DUTY
CONTRACTOR‐200A
4P, 200A MCCB 4P(Cat III) WITH SPREADER & SHUNT, 3 PHASE SPD,
VOLTAGE MONITORING RELAY, ELR WITH CBCT, PHASE 49500.00 Ea.
INDICATING LAMP, POWER CABLE & OTHER ACCESSORIES. All switchgears and connection are enclosed
with IP66 Enclosure and operate the position.
13 14.6.6 1 Ea. S.I.T.C of Distribution board from AC Side , ACDB 3-Phase - 101 kW - 200 kW: AC1 DUTY
CONTRACTOR‐300A
4P, 200A MCCB 4P (Cat III)WITH SPREADER & SHUNT, 3 PHASE SPD,
VOLTAGE MONITORING RELAY, ELR WITH CBCT, PHASE
INDICATING LAMP, POWER CABLE & OTHER ACCESSORIES. All switchgears and connection are enclosed
with IP66 Enclosure and operate the position.
14 14.7.1 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB 1-Phase - 1 kW - 3.5 kW(1in:1out) : DC MCB 500V, 16A, DC
SPD 600V, TYPE 2, TERMINAL/END,PLATE/END CLAMP: 4SQMM
(KUT6) FOR OUTPUT, DC CABLE With suitable size of interconnection.
15 14.7.2 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 3.6 kW - 6 kW (2in:2out) : DC MCB 500V, 16A, DC SPD 600V,
TYPE 2, TERMINAL/END PLATE/END CLAMP 7000.00 Ea.
4SQMM (KUT6), GREEN (KUT6), DC CABLE With suitable size of interconnection.
16 14.7.3 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 6 kW - 10 kW (3in:3out) : DC MCB 500V, 16A, DC SPD
1000V, TYPE 2, TERMINAL/END PLATE/END CLAMP 9000.00 Ea.
4SQMM (KUT6), GREEN (KUT6), DC CABLE With suitable size of interconnection.
17 14.7.4 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 10 kW - 20 kW (4in:4out) : Input Mcb - 1000 V, 16 Amp,
1000 V DC SPD TYPE 2, TERMINAL/END,PLATE/END CLAMP: 12200.00 Ea.
4SQMM (KUT6) FOR OUTPUT, DC CABLE With suitable size of interconnection.
18 14.7.5 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 20 kW - 25 kW (5in:5out) : Input Mcb - 1000 V, 16 Amp,
1000 V DC SPD TYPE 2, TERMINAL/END,PLATE/END CLAMP: 17200.00 Ea.
4SQMM (KUT6) FOR OUTPUT, DC CABLE With suitable size of interconnection.
19 14.7.6 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 35 kW - 40 kW (8in:8out) : Input Mcb - 1000 V, 16 Amp,
1000 V DC SPD TYPE 2, TERMINAL/END,PLATE/END CLAMP: 24200.00 Ea.
4SQMM (KUT6) FOR OUTPUT, DC CABLE With suitable size of interconnection.
20 14.7.7 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 50 kW - 65 kW (12in:12out) : Input Mcb - 1000 V, 16 Amp,
1000 V DC SPD TYPE 2, TERMINAL/END,PLATE/END CLAMP: 29200.00 Ea.
4SQMM (KUT6) FOR OUTPUT, DC CABLE With suitable size of interconnection.
21 14.7.8 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 60 kW - 80 kW (16in:16out) : Input Mcb - 1000 V, 16 Amp,
1000 V DC SPD TYPE 2, TERMINAL/END,PLATE/END CLAMP: 31500.00 Ea.
4SQMM (KUT6) FOR OUTPUT, DC CABLE With suitable size of interconnection.
22 14.7.9 1 Ea. S.I.T.C of Distributiob System DC Side, DCDB - 80 kW - 300 kW (18in:18out) : Input Mcb - 1000 V, 16 Amp,
1000 V DC SPD TYPE 2, TERMINAL/END,PLATE/END CLAMP: 38500.00 Ea.
4SQMM (KUT6) FOR OUTPUT, DC CABLE With suitable size of interconnection.
23 14.8.1 1 Ea. Supplying & Errecting MC4 Connector Male - Female Set for Solar DC Cable which is installed in Solar PV-
module/Inverter/DCDB etc.
24 14.9.1 Providing & erecting Automatic solar panel cleaning system for solar power projects which includes necessary
plumbing work (UPVC pipes and accessories) from source of water to project site (upto 30 meters),Suitable size
of sub mercible/ open well motor, necessary wiring for motor and sprinkler system with safety, timer circuit for
automatically on/off the sprinkler system, necessary size oand number of nozzles/JET (minimum 1 Nozzle/Jet
1 PER KW (A) 1KW-5KW Cleaning System 4500.00 PER KW
1 PER KW (B) 5KW-10KW Cleaning System 4500.00 PER KW
1 PER KW (C ) 11KW-20KW Cleaning System 4300.00 PER KW
1 PER KW (D) 21KW-50KW Cleaning System 4300.00 PER KW
1 PER KW (E) 51KW-100KW Cleaning System 4150.00 PER KW
1 PER KW (F) 101KW-200KW Cleaning System 4150.00 PER KW
25 14.10.1 The all inclusive comprehencive annual maintance contract cost covers yearly maintanance of solar Pv
Modules, Inverter, wiring,earthing,switchgears, etc with material and labour cost including preventive
maintanance.The cost covers entire installation. AMC also includes monthly site visit and inspection of project
with submission of inspection and solar generation report. All parts should be replaced/repaired if found faulty
within specified time. Agency has to provide necessory licening work for warranty,power,Bidirectional meter etc
1 PER KW (A) 1KW-10KW System 6500.00 PER KW
1 PER KW (B) 11KW-20KW System 6000.00 PER KW
1 PER KW (C ) 21KW-50KW System 5000.00 PER KW
1 PER KW (D) 51KW-100KW System 4500.00 PER KW
1 PER KW (E) 101KW-200KW System 4000.00 PER KW
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
E tendering notice.pdf
MAKE LIST.pdf
SBD FOR solar updated.pdf
special condition.pdf
schedule B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .