Senior S.E,CEC, PWD.
Office of the Senior SUPERINTENDING ENGINEER, Central Electrical Circle 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Construction of proposed G3 storied Research and Innovation Complex within the campus of the Kalyani University in the district of Nadia SITC of Fire Alarm System
2026_WBPWD_5017575_1
WBPWD/CEC/NIT/03/T/2nd/26-27
Open Tender
FIRE FIGHTING ORG
Percentage
21 days
Kalyani
Please refer Tender documents.
5 documents required · 5 mandatory
₹17,320
Office of the Senior S.E,CEC, PWD.
3 Sept 2026
29 Jul 2026
17 Aug 2026
1 Aug 2026
15 Aug 2026
5 Aug 2026
4 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing & Commissioning of Microprocessor based addressable OPC compliant fully networkable fire alarm Two Loop Control Panel (VDS/UL/LPCB/FM approved) with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS2189:2008 or its latest amendments, and with minimum 320 character alpha-numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pinpoint location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches with help of monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 1 | No | 0.29 | ₹0.29 |
| 2 | Supply, Installation, Testing & Commissioning of Microprocessor based Intelligent addressable and network connected Repeater OPC compliant panel (VDS/UL/ERTL/LPCB/FM approved), having all the controls and monitoring as on the main fire alarm panel, functioning as a controller, allowing remote command in system reset, trouble and alarm silence, and manual alarm. It shall be programmable to display information for the entire system (all panels in the network), having minimum 320 characters LCD display for system status text display (including Alarm, missing point trouble, system test, service, local system test, custom test by polling circuit and address). The repeater panel should annunciate alarm and trouble conditions on signal actuation. Degree of protection as per OEM Standard (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 1 | No | - | - |
| 3 | Supply, Installation, Testing & Commissioning of Microprocessor controlled addressable Multi-sensor detector (VDS/UL/LPCB/FM approved) with inbuilt optical smoke sensors and heat detector sensor, with inbuilt short circuit fault isolator as per NFPA (Note: Detectors without built-in fault isolator are also acceptable with one independent short circuit fault isolator after every four detectors provided without extra cost). Detectors should have built-in response indicator with LED indicator, 360-degree optical view with single or multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage detectors. Degree of protection as per OEM Standard. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 140 | No | - | - |
| 4 | Supply, Installation, Testing & Commissioning of Microprocessor-controlled Addressable Heat detector (VDS/UL/LPCB/FM approved) with a combination of fixed type & Rate of Rise of Temperature feature. Detector shall have a minimum triggering temperature programmable from 58 deg. C to 68 deg. C, having a high level of immunity to electromagnetic influences and showing alarm signal once limit temperature is reached. Detector shall have built-in short circuit fault isolator as per NFPA (Note: Detectors without built-in fault isolator are acceptable with one independent fault isolator after every four detectors in the loop without extra cost).The detector should have a built-in response indicator with LED. Degree of protection as per OEM Standard. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 4 | No | - | - |
| 5 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box with metallic cover having two LEDs and Degree of protection as per OEM Standard etc. complete with all connections as required. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 60 | No | - | - |
| 6 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered/panel powered Hooter (sound output of minimum 90 dB) cum strobe (strength of light 10cd) complete with built-in short circuit fault isolator as per NFPA (Note: Hooters without built-in fault isolators are acceptable with one independent short circuit fault isolator provided without extra cost). VDS/UL/LPCB/FM approved. Degree of protection as per OEM Standard Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 8 | No | - | - |
| 7 | Supply, Installation, Testing & Commissioning of Addressable Manual Call Point (VDS/UL/LPCB/FM approved) with built-in short circuit fault isolator as per NFPA (Note: MCP without built-in fault isolator is acceptable with one independent short circuit fault isolator provided without extra cost). Degree of protection as per OEM Standard. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 8 | No | - | - |
| 8 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 8 | No | - | - |
| 9 | Supply, Installation, Testing & Commissioning of Addressable Control Modules/Relay Module (VDS/UL/LPCB/FM approved) for controlling Fire exit doors/AHU/Lift etc. with inbuilt short circuit fault isolator/External fault isolator with adjustable setting parameter likes (Resistive, Inductive or capacitive) of Input or output, complete in single or multiple housing with degree of protection IP42 with flash LED indicator that confirms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 8 | No | - | - |
| 10 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. (Esser/Bosch/Johnson Controls/GST/Ravel/ NOTOFlRE/ Edward /System Sensor) | 12 | No | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.26 MB
BOQ_5087864.xls
BOQ • 0.26 MB
2911.pdf
Tender Documents • 0.54 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .