Executive Engineer (WW Ele/Mech), Water Works Dep, Vadodara Municipal Corporation
PROVIDING, SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING OF DIRECT WATER DISTRIBUTION SYSTEM BY BYPASSING THE EXISTING ELEVATED SERVICE RESERVOIR (ESR) AT SAYAJIBAUG WATER TANK, INCLUDING CONSTRUCTION OF ALL ALLIED CIVIL WORKS, SUPPLY AND INSTALLATION OF PUMPS, MOTORS, PIPING, VALVES, ELECTRICAL PANELS, INSTRUMENTATION, CABLING, TESTING, COMMISSIONING AND COMPREHENSIVE OPERATION & MAINTENANCE 24 MONTHS. (PHASE-I).
363877
575/2026-27
Open
Civil Works - Water Works
Works
Vadodara
3 documents required · 3 mandatory
₹20,000
Municipal Commissioner, Vadodara Municipal Corporation
₹10.5 L
7 Dec 2026
7 Nov 2026
9 Dec 2026
7 Nov 2026
27 Nov 2026
7 Nov 2026
120 days
BILL OF QUANTITIES
1. The bill of Quantities shall be read in conjunction with the Instructions to Bidder,
Conditions of Contract, Technical Specifications and Drawings.
2. The quantities given in the Bill of Quantities are estimated and provisional, and are
given to provide a common basis for bidding. The basis of payment will be the actual
quantities of work ordered and carried out, as measured by the Contractor and
verified by the Engineer and valued at the rates and prices tendered in the priced
Bill of Quantities, where applicable, and otherwise at such rates and prices as the
Engineer may fix within the terms of the Contract.
3. The rates and prices tendered in the priced Bill of Quantities shall, except in so far
as it is otherwise provided under the Contract, include all constructional plant,
layout, supervision, materials, erection, maintenance, insurance, profit, taxes and
duties, together with all general risks, liabilities and obligations set out or implied in
4. The rates and prices shall be quoted entirely in Indian Currency.
5. A rate or prices shall be entered against each item in the Bill Quantities, whether
quantities are stated or not. The cost of Items against which Contractor has failed to
enter a rate or price shall be deemed to be covered by other rates and prices
entered in the Bill of Quantities (in case of Item rate contract).
6. The whole cost of complying with the provisions of the Contract shall be included in
the items provided in the priced Bill of Quantities, and where no Items are provided
the cost shall be deemed to be distributed among the rates and prices entered for
the related items of Work.
7. General direction and descriptions of work and materials are not necessarily
repeated or summarized in the Bill of Quantities. References to the relevant sections
of the contract documentation shall be made before entering rates or prices
against each item in the Bill of Quantities.
8. The method of completed work of payment shall be in accordance with the
specification for Road and Bridge works. For building works specifications for
building are to be followed.
9. Errors will be corrected by the Employer for any arithmetic errors pursuant to Clause
29 of the Instructions to Bidder.
10. Rock is defined as all materials which, in the opinion of the Engineer, required
blasting, or the use of metal wedges and sledgehammers, or the use of compressed
air drilling for its removal, and which cannot be extracted by ripping with a tractor of
at least 150 kw with a single rear mounted heavy duty ripper.
ROVIDING, SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING OF DIRECT WATER DISTRIBUTION SYSTEM BY BYPASSING THE EXISTING ELEVATED SERVICE RESERVOIR (ESR) AT SAYAJIBAUG WATER TANK, INCLUDING CONSTRUCTION OF ALL
ALLIED CIVIL WORKS, SUPPLY AND INSTALLATION OF PUMPS, MOTORS, PIPING, VALVES, ELECTRICAL PANELS, INSTRUMENTATION, CABLING, TESTING, COMMISSIONING AND COMPREHENSIVE OPERATION & MAINTENANCE 24 MONTHS. (PHASE-I).
1 The Contractor shall exhibit a board with detailed specification and details
of work as directed by the Engineer-In-Charge for which no extra payment
2 The labour cess will be deducted from the bill amount excluding GST as per
prevailing rules i.e. 1% of the work done.
3 GST and Income tax TDS will be deducted at a source while making payments of
PROVIDING, SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING OF DIRECT WATER DISTRIBUTION SYSTEM BY BYPASSING THE EXISTING ELEVATED SERVICE RESERVOIR
(ESR) AT SAYAJIBAUG WATER TANK, INCLUDING CONSTRUCTION OF ALL ALLIED CIVIL WORKS, SUPPLY AND INSTALLATION OF PUMPS, MOTORS, PIPING, VALVES, ELECTRICAL
PANELS, INSTRUMENTATION, CABLING, TESTING, COMMISSIONING AND COMPREHENSIVE OPERATION & MAINTENANCE 24 MONTHS. (PHASE-I).
BILL OF QUANTITY
Sr. Item Description Quantity Rate Unit Amount
1 Excavation for pipe line trenches for water supply ,sewerage line ,manhole etc 740.00 102.35 Cum
all with shorting and struting if requried as per requried gradient adn line
includin all safety provisions using site rails and staking excavated stuff
including upto requried lead cleaning the site etc complete fro all lift and
starta as specified a) 0.0 mt to 1.50 mt. depth.
2 Manufacture, Supply, Lowering, Laying, Jointing & Delivery of Electric 120.00 13200.00 Rmt
Resistance Welded (Up to 500mm)/Submerged Arc Welded M.S.Pipe having
beveled ends plate or coil conforming to IS-3589-2001 or its latest revision/
ammendment for following thickness outside diameter at GWSSB store or site
anywhere in Gujarat State including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading, unloading conveyance to
Departmental stores, stacking etc. all complete.
711 mm dia MS Pipe with 8.0 mm thick with 406 micron epoxy coating inside &
457 mm dia MS Pipe with 6.3 mm thick with inside epoxy Painting (406 25.00 7700.00 Rmt
Micron) & O/S Gunniting (25 mm Thick)
3 Lowering, Laying & Jointing and welding in position, to correct line and level 120.00 665.85 Rmt.
M.S pipe with outer gunnintig and inside lining/Epoxy painting on padestal or
chairs up on prepared formation or prepared bedding in trenches the rates incl
bedding in trenches the rates incl conveyance from store to site of work
loading,unloading,joint platering hystrotesting etc.
711 mm dia MS Pipe with 8.0 mm thick with 406 micron epoxy coating inside &
457 mm dia MS Pipe with 6.3 mm thick with inside epoxy Painting (406 25.00 449.65 Rmt.
Micron) & O/S Gunniting (25 mm Thick)
4 Refilling the pipeline trenches incl. remming, watering, consolidating desposal 1620.00 25.30 Cum
of surplus stuff as directed within a radius of 3 Km
5 Providing and supplying lSI mark CI D/F Sluice Valves as per IS: 14846 (Latest 2.00 281009.00 Nos
Edition) of following class and diameter including all taxes, insurance,
transportation, freight charges, octroi, inspection charges, loading, unloading,
conveyance to departmental stores. stacking etc. complete. 700 mm Dia
6 Lowering,laying and joining in position following DI reflux valves, Butterfly 2.00 5784.50 Nos
valves, Sluice valves and Air valves including cost all labour, jointing material,
including nut bolts and giving satisfactory hydraulic testing, etc. complete
Sluice valve /BF valve for 700 Mm dia
Sr. Item Description Quantity Rate Unit Amount
7 Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4) 14.00 5641.90 Cum
(proportions as per mix design or as per Table 9 of IS456 2000 in masses by
weigh batching ) using granite, quartzite trap metal of size 6 mm to 20 mm for
RCC work, including scaffolding centering, form work, needle vibrated
consolidation, curing comp. up to 6 meter depth or height (excluding cost of
reinforcement and neat finishing) with centering and shuttering/deshuttering
etc. comp. for structure for other than water retaining.
Footing for column or foundation (with form work)
8 Providing and cast in situ C.C. in grade M-25 (approx. corresp. to prop. 1:1.5:3) 12.00 9288.55 Cum
(proportions as per mix design or as per table9 of 15456 2000 in masses by
weigh batching ) using quartzite trap metal of size 12 mm to 20 mm and or
mm to 12 mm including scaffolding centering form work, needle vibrated
consolidation, curing and hydraulic testing etc. complete (excluding cost of
reinforcement) with centering and shuttering/deshuttering etc. complete up to
6 meter height/depth from Av. G.L. for all structures with water proofing
8.1 Beams/ring beams/ girders 7.00 9599.05 Cum
9 Steel /Reinforcement bars: Supplying cutting, bending, binding and placing in 1.30 89129.60 MT
position steel as per plan and design and as per ISS 2502 including cost of
steel and binding wire for reservoirs/structures only including lift up to
meter height or depth below G.L. for all diameters Do-deformed (TMT) bars
confirming to relevant IS Fe -500 grade for all diameters. Do-deformed (TMT)
bars confirming to relevant IS Fe -500 grade for all diameters.
10 Brickwork using common burnt clay building brick having crushing strength 124.88 4080.74 Cum
not less than 35 kg/sq.cm in foundation and plinth in cement mortar 1:6
11 Provinding 20 mm thick inside cement plaster in Cement mortar (1:3) to stone 180.00 292.70 Smt
or brick masonary including racking out the joints and niru or cement finishing
12 Supplying and fixing the MS cover for valve chamber with required channel, 8800.00 85.99 Kg
girder, plate, angles with hole above to operate valve including required chain
to open and paint two coats of redoxide and two coats of anti corrosion paint.
etc complete as per the instruction of Engineer in charge.
13 Demolition including stacking of serviceble materials and disposal of 15.00 1073.56 Cum
unserviceble materials with all lead & lift [i] R.C.C. work
14 Demolition including stacking of serviceble materials and disposal of 20.00 558.57 Cum
unserviceble materials with all lead & lift [i] Brick work.
15 Dewatering by pumping set of required capacity including temporary platform 1600.00 21.07 Hp/Hr.
carting pumping at site and fixing the same in position including all
accessories, and fuel and labour etc. complete.
16 Excavation in bituminous road as per required gradient and line including 20.00 291.16 Cum
safety provisions using site rails and stacking excavated stuff including up to
all required lead cleaning the site etc. complete for all lifts as specified.
17 Box cutting the Road surface to proper slope and camber for making a base 50.00 105.75 Cum
for road work incl. removing the excavated stuff and depositing on the road
side slope us directed upto 50 Mt.lead.
Sr. Item Description Quantity Rate Unit Amount
18 GSB :Providing and laying of good quality material of GSB in proper line,level 30.00 1045.00 Cum
and camber (compacted thickness 300 MM with roller 8-10MT capacity on
GSB as per specification and instruction by engineer incharge.
19 Providing & laying compacted machine crushed black stone aggregate 250 20.00 1748.00 Cum
mm thick wet mix macadam in two layers in the material with water to OMC in
mecanically mix (pug mill) carriage of mix material by tipper to site
laying,spreading and compacting in sub base of compacting power vibrater
roller to achive the desired density (mechanically laid) etc.complete.as per
technical specification MORTH clause-406
20 Providing and laying Mixture of macadam carpet of thickness as prescribed / 12.09 3822.74 MT
average required compacted thickness using coarse aggreagete/fine
aggregate/filler as per required gradiation, applying tack coat at the rate of
Kg/10 Sm. And using asphalt (VG-30) 4% by wt. of mix and mixing by drum mix
process spreading by paver finisher and flushing Quarry dust on B.T. surface
at the rate of 0.75 CM/100 SM including consolidtion etc. complete by using
Sevaliya , Timba Quarry Material.
21 Job Connection For Proposed Line to Existing Line Connecation with 9.00 34200.00 Nos
Necessary all Tools Tackels labours and requriements and instruction of EIC.
@ Sayajibaug ESR to Fahtegunj
@ Sayajibaug ESR to Kalaghoda
@ Sayajibaug ESR to Karelibaug
22 Removing tiled or stone/paver block floor laid in mortar including stacking of 60.00 50.00 Cum.
serviceble material and disposal of unserviceble material with all lead and lift.
23 Laying and fixing of 50mm thick interlocking paver block as per design given 60.00 140.55 Cum.
by Engineer Incharge with 50mm thick sand bed layer, watering, compacting
paving with compacter by mechanical compacter etc. complete as per
specification .( Approved Rate)
24 Designing (aesthetically) and constructing R.C.C frame structure of pump 102.00 17596.15 SQM
room with positive suction I Negative suction
With Gantry structure (Min. Height 4.5 M) Upto 6.00 M (Plinth Level to Top
slab Beam For HT Panel & Trasformer Room
1. Minimum 15 % opening for ventilation should be provided.
2. Pump room rolling shutter, door and windows of aluminium section and
window grill of iron should be provided (Included in Cost).
3. Plinth level of Pump house should be min.1 meter above GL.
4.Cost does not include foundation for pumping machinery.
25 Welding in all positions with required number runs, for M.S. Pipes internally 15.00 838.35 Rmt
and/or externally including gauging wherever necessary, fixing
appurtenances and other accessories in connection with pipe laying work as
per specification.
26 Cutting of CI/DI pipes : Labour charges for cutting pipes with the help of 15.00 126.50 Rmt
requisite tools and as directed. 1) Pipe thickness upto 11 mm
2) Pipe thickness upto 11 mm to 20 mm 15.00 161.00 Rmt
Sr. Item Description Quantity Rate Unit Amount
27 Manufacture, supply and delivery of cast iron Detachable joints (Short & long) 5.00 4835.00 Nos
complete with joint flanges duly drilled, synthetic rubber sealing rings
manufactured from styrene butadine rubber (SBR) and other required
accessories such as nut, bolts etc. conforming to IS specification 8794-1988
or its latest revision if any suitable for use with A.C. Pressure pipes. Delivery of
joints including its accessories including loading, unloading, carting, stacking,
insurance, all taxes, octroi etc. complete.
Short Collar with lSI Mark (Class- 5,10)
28 Manufacture, Supply & Delivery of Ductile Iron Flange socket spigot bends, 500.00 148.00 Kg
tees, reducers or any other specials as per BS-EN-545/1995 Class-A series
K12 suitable for use with D.I.Pipes manufactured as per IS:8329/1994 delivery
of specials is to be made to GWSSB store or site of works any where in Gujarat
including all taxes, leading, unloading, carting, stacking, insurance, inspection
charges, octroi etc. complete.
A. Socket & Spigot Type
1. 80 to 300mm dia
B. Flanged ended 500.00 155.00 Kg
1. 80 to 300mm dia
29 MS Specials plain ended/flange ended Manufacture, supply and delivery of 5000.00 96.00 Kg
80 mm to 300 mm dia Mild steel plain ended/flange ended specials complete
like tee, bend, skew tee etc. as per IS. The delivery of specials is to be made to
VMC store or sites including all taxes, loading, carting, unloading, stacking,
insurance, octroi, inspection charges etc. complete as per instruction of
engineer in charge.
M.S Specials plain & socket ends
Above 300 mm dia.
M.S Specials flanged ends 5000.00 98.00 Kg
Above 300 mm dia.
30 Designing (aesthetically) and constructing R.C.C frame structure of pump 55.00 11920.53 SQM
room with positive suction I Negative suction without gantry structure up to
3.60M Height(From Plinth Lvl to Top slb of Beam)
31 Construction of temparary Platform of size 10m x 5 m for temparory shifting of 1.00 652880.00 Job
panels and other materials with otta of 1.0 M above from neaest road and
PPGI roofing sheet for side and shed as per EIC for Temparary Arragement for
Bossting Station
Rate Analysis For Platform
Sr. Description Qty Unit Rate Total
Excavation for foundation upto 1.5 m depth including sorting out and 30.00 Cum. 118.82
1 stacking of useful materials and disposing off the excavated stuff
upto 50 Meter lead. (A) Loose or soft soil
Brick work using common burnt clay building bricks having crushing 31.00 Cum. 4080.74
2 strength not less than 35 kg./Sq.Cm. in foundation and plinth in
Cement Mortar 1:6 (1- Cement : 6 -fine sand)(B) Conventional
Filling in foundation and plinth with murrum or selected soil in layers 61.00 Cum. 293.36
3 of 20cm. thickness including watering, ramming and consolidating etc.
Providing and Laying Cement Concrete 1:3:6 (1-Cement, 3-Coarse 6.00 Cum. 3050.40
4 Sand, 6-hand Broken stone aggregates 40 mm nominal size) and
curing complete excluding cost of formwork.
Providing and laying cement concrete work 1:2:4 (1- Cement : 8.00 Cum 3892.57
2- Coarse sand : 4- graded stone aggregates 20 mm nominal
size) and curing complete excluding cost of formwork and
reinforcement for reinforced concrete work
Providing ISI Mark T.M.T. Bar 500Fe reinforcement for R.C.C. work, 318.00 Kg 76.52
6 including bending and placing in position complete upto floor two
Supplying cutting, bending, binding and placing in position steel as per 3.00 MT 89129.60
plan and design and as per ISS 2502 including cost of steel and
7 binding wire for reservoirs/structures only including lift up to 6 meter
height or depth below G.L. for all diameters Do-deformed (TMT) bars
confirming to relevant IS Fe -500 grade for all diameters.
Providing and fixing of Corner Angle for Various Flashing in 100mm x 210.00 Sqm 779.75
100mm size in Equal Shape with 5mm edge lipping on both side . The
Angle Flashing shall be made out of 0.5 mm thick pre coated GI sheet
with edge bending of approximate 5mm. The Precoated sheet shall be
of minimum 240 mpa steel grade confirming to IS 14246:1995 and
8 shall have zinc coating of minimum 120 gsm as per IS:277:1992 , 5-7
microns poxy primer on both side of the sheet and polyester top coat
15-18 micron. The PPGI Sheet shall have plastic protective guard film
of minimum 25 microns to avoid scratches during transportation. The U
track shall be fixed with suitable POP rivet with wall and roof panels
with minimum spacing of 450 mm c/c.
ELECTRICAL - MECHANICAL WORKS
Sr.No Item Description Qty. Unit Amount in Rs.
A MECHANICAL WORKS
1.0 Submerged Centrifugal Pump: 3.00 Nos 2376000.00
Providing submerged centrifugal pump set (water immersed ,dry air filled ,class F insulated
TEWC motor integrally mounted on volute casing pump set for water duty ,3 Phase 50 ±3%
Hz , 415 +- 10% Volts along with suitable foundation /installation devise with cable lenght
from pumps to panel & of following material of construction.
Impeller -CF8M ,Casing -CI FG 260 ,Wearing ring -SS,TC mechanical seal ,CS/SS Bearing
,SS Shaft with Seelevs , SS Stainer & MS Motor body
Motor rating 180.00 KW, Capacity: 1080.00 m3/hr, Head:40 mtrs (2W+1S)
1.1 Submerged Centrifugal Pump:Installation testing and commisioning pump set 180.00KW 3.00 NOS 84000.00
GWSSB SOR -2022-23 ELECTRO-MECHANICAL, SECTION E, ITEM NO. 44A AND 44B,
1.2 Uninstallation of existing pumping machinery from existing pump house including all 1.00 LS 500000.00
pumps,panel,cables,valves, NRV,specials etc. with all lead and lift to specified department
store or as specified by EIC.
As per market rate
1.3 Uninstallation of temporary installed pumping machinery including all pumps ,panel ,cables 1.00 LS 100000.00
,valves , NRV ,specials etc. with all lead and lift or as specified by EIC
As per market rate
1.5 Neccesary arrangement for installation of 3 nos of pumps like Core cutting in existing slab 1.00 Job 75000.00
of sump & grating for boosting purposes with including all labour charges with neccessay
all tool,machinery and equipments
As per market rate
2.0 Supply, installation, testing and commissioning of Manually Gear operated Horizontal shaft 3.00 NOS 34070.65
DI DF Butterfly Valve, conforming to IS 13095 / BS 5155, PN 1.6 with SS 304 renewable seat
rings, indicator, gear box with bolts, nuts & washers, gaskets, etc. as per specifications and
complete in all respect.
Size: 400 mm NB (at pump delivery)
GWSSB SOR -2022-23 CIVIL, SECTION 1 &2A, ITEM NO. 14.1A , PG NO 24 + itno. 15 A pg
3.0 DI D/F PIPES 25.00 Mtr 12244.85
Supply, installation, testing, commissioning of double flanged DI Pipes confirming to IS
8329-2000, class K9 with connections complete for delivery and header lines and as per
specifications & drg. The scope also includes connection with main header/rising main.
Size: 400 NB Delivery Line at Pump
3.0.1 700NB Header Line 120.00 Mtr 30376.20
GWSSB SOR -2022-23 CIVIL, SECTION 1A, ITEM NO. 8, PG NO 6+ It no. 5 pg
4.0 DI FITTINGS 6000.00 KG 158.00
Supply, installation, connection with delivery / header, testing and commissioning of
Flanged DI Fittings and Specials like 90 deg. Bend, Drilled / Blind Flanges, Reducer /
Enlarger, TEE etc. as required to complete the piping and connection of pumps with main
header/rising main conforming to IS
Size: 700 mm NB and 400 NB
GWSSB SOR -2022-23 CIVIL, SECTION 1A, ITEM NO. 8, PG NO
4.1 MS Specials
Supply, installation, connection with delivery / header, testing and commissioning of 10000.00 KG 98.00
Flanged M. S. Specials flanged ends Above 300 mm. dia.
GWSSB SOR -2022-23 CIVIL, SECTION 1A, ITEM NO. 7.1B, PG NO
5.0 Supply, installation, testing and commissioning of DI DF Dual Plate Check Valve conforming 3.00 NOS 85775.65
to API 594, Class 125 with CS dual door, hinge pin & stop pin of SS 410, springs of AISI
and seat of SS 304, along with all required accessories, gaskets and hardwares,etc.
complete as per IS and Specification.
Size :400 mm NB
GWSSB SOR -2022-23 CIVIL, SECTION 1&2A, ITEM NO. 15.1.B, PG NO 25 + It no. 15a pg
Sr.No Item Description Qty. Unit Amount in Rs.
6.0 EXPANSION BELLOWS: 3.00 NOS 17640.00
Supply, installation, testing and commissioning of flanged metallic S.S. expansion bellows
confirming to EJMA standard with PN 1.6 rating & all necessary carbon steel hardware’s as
per data sheet.
Size: 400mm NB- on delivery side
6.1 Size:700 mm NB- on header 2.00 NOS 39720.00
GWSSB SOR -2022-23 ELECTRO-MECHANICAL, SECTION E, ITEM NO. 14B.10 AND
7.0 AIR VALVE: 1.00 NO 30301.75
SITC of CI Tempor proof Flanged Air Valve with Isolation Sluice Valve as per IS 14845 PN-
1.6 &IS-14846 PN-1.6 respectively with SS304 float, gun metal nozzle, complete hardware's,
bolts, nuts & washers, gaskets etc. including all taxes, Insurance, Transportation, freight
charges, Inspection charges, loading, unloading, conveyance to departmental stores,
stacking, security etc. as per IS and Specification.
Size: 150 mm NB - PN 1.6 (On Header line outside the Pump house)
GWSSB SOR -2022-23 CIVIL, SECTION 1&2A, ITEM NO. 16.2D, PG NO 26 + + It no. 15c pg
7.1 Providing, supplying and delivery of Water Hammer Control Devices for use on various
pumping main of following class and diameter including all taxes, insurance, transportation.
freight charges, octroi, inspection charges, loading, unloading, conveyance to departmental
stores, stacking etc. complete
Zero velocity valves above 300mm dia with M.S. body (class-15)
Size: 700mm 1.00 NOS 256833.50
GWSSB SOR -2022-23 CIVIL, SECTION 1&2A, ITEM NO. 17.1.D, PG NO 27 + + It no. 15a
8.0 Electric Operated Hoist : 1.00 NOS 554250.00
Supply, erection, testing and commissioning of Single girder type Providing EOT Crane with
electric operated hoist Class II Duty gear travelling trolley with necessary lift complete
with long travel rail track moving or cross girder all three motions electrically operated by
suitable rating motor IP54 control panel and down pendent control block break safety
device cable from motor to starter panel &other required accessories &tested as per IS
Specifications.
Capacity: 3 Ton, Span: as per site condition, Lift: as per site condition
GWSSB SOR -2022-23 ELECTRO-MECHANICAL, SECTION E, ITEM NO. 37.2(2.1), PG NO
9.0 Monoblock pump for fire usage:SITC of Monoblock pump 3 phase 400/440 volt, 50 c/s. A.C. 1.00 Nos 58808.00
suppl;y & 2800 RPM as per IS 9079 MOC : Casing : CI-FG260, Impeller : SS-CF8M & Shaft :
SS:410 with DOL / Star Delta starter suitable for local & remote pump control application
consisting of MPCB, overload relay and contactors as per Type II coordination including
digital voltmeter, analogue ammeter with selector switch, run hour meter, required
protective relays & control accessories with 20 Rmt Cables& necessary pipes,Specials
valves and connecation with Existing Pipeline as per instruction of EIC
For Fire & Swimming Pool, Garden & Crematorium Dept.12.50 HP & 980 LPM & 30 M Head
GWSSB SOR -2022-23 ELECTRO-MECHANICAL, SECTION E, ITEM NO. 4B, PG NO 35 +It
NO :2.1€+Instalation Charges
10.0 PRESSURE GAUGE: 3.00 NOS 3012.00
Design, Supply, Installation, Testing, Commissioning of Bourdon Type Pressure Gauge, ±1%
accuracy, Direct bottom 1/2" NPT (M) process connection, IP 67, Glycerine filled, SS304
Case with Bayonet Type Bezel, SS316 L Bourdon Tube, SS316 Movement material,
Aluminium dial with black graduation on white background, Micro Zero adjustable pointer,
gasket, Blow out disc, shatter proof glass, SS tag plate etc as per IS 3624.(Non-clog
submercible Pump delivery & header).
Range : 0 - 10 kg / sq.cm.and 150 mm dia
GWSSB SOR -2022-23 ELECTRO-MECHANICAL, SECTION F, ITEM NO. 10.2B, PG NO
Sr.No Item Description Qty. Unit Amount in Rs.
11.0 HDPE Storage Tanks: 1.00 No. 17908.00
Supplying Rotationally moulded HDPE storage tank with ISi Mark of approved make incl. all
taxes ransportation octroi etc. complete.
GWSSB SOR 22-23 /section A- Item no.20 , pg.29
12.0 Providing laying and jointing in true line and level 15mm dia. U.P.V.C. Pipe ( SCH- 40) for cold
water including fittings as approved by Engineer In Charge. Pipe shall be fixed on the wall
with the help of clamp at every two metre C/C or shall be concealed as directed including
necessary fittings etc. including testing of pipe and joints and fixing the same with adhesive
solvent, including cost of all materials.
U PVC SCH40 for cold water 50 mm dia. 1.00 100.00 193.73
U PVC SCH40 for cold water 25 mm dia. 1.00 100.00 90.93
U PVC SCH40 for cold water 32 mm dia. 1.00 100.00 117.97
R & B SOR 23-24, Basic Material, Item code.23061, Pg No.182
13.0 Purchasing & supplying of structure steel at site of works, with Railway freight, loading, 5000.00 Kg 64.84
unloading, carting, etc. complete such as joints, channels, angles, iron rails, etc. required for
su[pport of all elec- mechanical equipment as per Tender & IS
GWSSB SOR -2022-23 Civil, SECTION A, ITEM NO. 22.1A(1), PG NO
13.1 Labour charges for lowering laying, erecting, fixing, various size of M. S. section such as 5000.00 Kg 13.07
joints channel, angles plates etc. complete
GWSSB SOR -2022-23 Civil, SECTION B, ITEM NO.16b1), PG NO
B ELECTRICAL WORKS
1 11 kV SWITCHYARD / TWO POLE (DP) STRUCTURE: 1.00 No. 120663.00
Supply, Installation, Testing and Commissioning of 11 kV, 3 Phase, 50 Hz, Two Pole
Structure made of 6" X 3" 'I' section girder having min. 9mtr. length, 4" X 2" M.S. channels,
angles, clamps, nuts, bolts, stay wires including earthing system etc. suitable for erection of
following / indicated accessories duly connected with ACSR conductor as per approved
drawings & in compliance with requirements of IS/IEC
(a) 11kV 200A DO (drop out) fuses with S.R.B.P. tubes carries (03 nos.)
(b) 11kV 400A G.O.D. switch complete with insulators, operating handle with
galvanized pipe, square bar etc. (01 set)
(c) 11kV lightning arrestors with clamps (03 nos.)
(d) 11kV shackle (Disc/Pin/Post) as required insulators (06 nos.)
(e) ACSR Dog Conductor (mini. 30Mt.)
(f) 11 kV fiber operating rod
(g) 20 mm dia. GI stay sets (2 sets), required foundation etc.and to be painted with two coat
of red oxide and final two coat of Aluminium paint at site as per IS, Specification and Drg.
(GWSSB E&M SOR 2022-23, Page No. 44, SEC-E, Item no. 19.1)
1.1 Shifting of Existing Two pole structure to new location within Pump House Boundary as per 1.00 Job 75000.00
site condition and EIC instruction with existing accessories like. Pole, Isolator, GOD switch,
HT fuse, Lighting Arrestor, etc.and making new 4 Nos.earthing with required length of 50 x
6mm GI Strip as per standard engineering to complete the job as per EIC instruction.
Necessary foundation of pole and earthing civil work shall be considered. Necessary
accessories to change / Modificatinon as per site condition shall be part of work. Liasoning
charges for the work shall be bourne by contractor.
(As per Market Rate and RA)
Supply, Installation, Testing & Commissioning of Approved make Outdoor type One way, 1.00 No. 403077.17
Non Extensible, Manual 11kV, 21kA, 630A Ring Main Unit with 01 Cable Housing + 01 Manual
Vacuum Circuit Breaker (with 01 Set of CTs + 01 No. Self Powered Numerical Relay) as per
(As per Market Rate and RA)
Sr.No Item Description Qty. Unit Amount in Rs.
RMU FOUNDATION : Constructing RMU foundation complete including excavation and 3.00 Cu.Mtr 6197.35
preparation of base, providing Plain Cement Concrete (PCC) 1:3:6 as levelling course,
providing and casting Reinforced Cement Concrete (RCC) M-20 grade for foundation as per
approved drawings, including centering, shuttering, reinforcement, compaction, curing and
constructing brick masonry steps in Cement Mortar 1:6 finished with 10 mm thick cement
plaster in Cement Mortar 1:4, including all materials, labour, tools, scaffolding, curing, leads,
lifts and all incidental works complete as per specifications and directions of Engineer-in-
3 SITC OF HV CABLES
Supply, laying, testing & commissioning of 6.35 / 11 kV (E) grade, XLPE insulated, stranded
Aluminium conductor, galvanised steel flat strip / round wire armoured, extruded PVC type
ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in
existing cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per
site requirement) conforming to IS:7098 (Part-2) & IEC:60502 (Part-2) of following sizes (
DP Structure to HT Panel, HT Panel to Transformer)
3.1 3 Core x 240 Sqmm 200.00 Mtrs. 1045.00
(GWSSB E&M SOR 2022-23, Page No. 52, SEC-E Item no. 24.1 h)
Providing & fitting Heat Shrink Cable Termination/ Jointing kits for 6.6 kV(UE) / 11 kV(E)
grade XLPE insulated cable including necessary earth connectivity connection, material &
consummables making the termination/ joint complete ensuring the joint resistance is within
the permissble limit as per IS, of following types & sizes:
3.2 Indoor Termination Kit Suitable for 3 Core x 240 Sqmm 4.00 Nos. 4798.00
(GWSSB E&M SOR 2022-23, Page No. 58, SEC-E Item no. 31.1 d)
3.3 Outdoor Termination Kit Suitable for 3 Core x 240 Sqmm 2.00 Nos. 6763.00
(GWSSB E&M SOR 2022-23, Page No. 58, SEC-E Item no. 31.2 d)
DISTRIBUTION TRANSFORMER
SITC of outdoor type, three phase, oil immerged, distribution transformer of required KVA &
voltage ratio, copper double wound, vector group - Dyn11, HV delta connected & LV star
connected with neutral brought out connected to provide separate earthing terminals,
bushing / cable box on HV side and cable box on LV side suitable for cables or bus duct as
per requirement with standard fittings, conforming to IS: 1180 (Part-1) / 2014 with its latest
amendment including first fill of transformer oil & following accessories.
(a) Oil conservator with filling holes with cap and prismatic oil level gauge.
(b) Silica Gel dehydrating breather charged with silica gel
(c) Oil drain cum sampling valve with plug
(d) Oil filter valve
(e) Lifting Eyes / Hooks / Lugs
(f) Two earthing terminal
(g) Diagram and rating plate
(h) Air release plug
(i) PRV with Trip Contact
(j) Thermometer pocket
Sr.No Item Description Qty. Unit Amount in Rs.
(k) Four bi-directional plain roller with base channel with hauling holes
(l) Fixed / Separate type radiator banks
(m) Off circuit externally operated tapping switch (For rating < 1000 kVA)
(n) 100 mm stem type oil temperature indicator (For rating < 500 kVA)
(o) Bucholtz relay with shut off valve (For rating ≥ 500 KVA)
(p) 150 mm dial type oil temperature indicator with Alarm / Trip contact (For rating ≥
(q) 150 mm dial type winding temperature indicator with Alarm / Tip contact (For rating ≥
(r) Marshalling box
(s) Neutral Terminal for seperate Earthing
(t) 150 mm dia. magnetic type oil gauge (For rating ≥ 1600 kVA)
(u) Inspection cover & Jacking lugs (For rating ≥ 1600 kVA)
(w) Prismatic Oil Level Gauge - For main Tank
(x) Surge Relay for OLTC
For transformer having oil storage capacity for 2000 liters and higher, nitrogen injection fire
KVA with (NIFPS)Level
Efficiency is to be
2 provided. 1.00 No. 5862000.00
With On Load Tap Changer +10% to -10% steps of 1.25% with RTCC & AVR.
(As per Market Rate)
RCC plinth / foundation for distribution transformer of capacity > 1000 & ≤ 1600 KVA 1.00 No. 50000.00
(GWSSB E&M SOR 2022-23, Page No. 48, SEC-E Item no. 20.3.4 b)
4.3 Supply and levelling of Switchyard & transformer yard using gravel, fine sand and other 20.00 Sq.Mtr. 400.00
required filing material, enmarked for the Switchyard & Transformer yard including
removing of trees or boulders etc. if any. The general level of the yard shall be at a
convenient level for movement of man and material and it should match with FGL and as per
Specification and Drg.
(As per Market Rate and RA)
4.4 Supply and Installation of GI Chain link fencing frames with L angle/Channel post around 20.00 Rmt. 1250.00
Switchyard & Transformer yard etc. as per Specification and Drg.
(As per Market Rate and RA)
4.5 SITC of 3.0 mtr wide gate with GI chain link as per Specification and Drg. 1.00 No. 12500.00
(As per Market Rate and RA)
5.1 LT PANEL (PMCC) :
SITC of PMCC Panel (50kA), compartmentalized, Floor mounted / Stand Mounted,
operating height maximum 1800/1900 mm, Extensible on both ends, suitable for Indoor /
Outdoor installation as per site suitability, local/remote operation as per site conditions
complete in all respects as per Tender SLD / Specification / IS and including following as
(1) Incomer 1 : FP, 1000A, 50 KA Microprocessor MDO ACB LSIG with RS 485 MODBUS
communication with Digital Voltmeter with VSS, Digital PF Meter, Digital Ammeter with
ASS, Resin Cast CT- Cl : 0.5,10VA, MFM Cl : 0.5, Indicating lamps, Push buttons etc.
(1.1) Surge protection device, 3P + N, Type 2 for lightning/surge protection.
Load sensing Resin cast Cl-0.5 CTs in Incomer for APFC panel.
(2) 1000A TPN, EC grade Al. Main busbars. (Busbars size as per 50KA fault level and
Temperature rise with current density of 0.8A/Sq.mm)
(3) Transformer Fixed Compensation Feeder (50 KVAr): Each comprising of 125A FP Thermal
magnetic MCCB, Indication Lamp, Capacitor duty contactor, 25 KVAr-2 Nos. MPP Heavy
Duty Capacitors, A/M switch, ON Delay timers, Push buttons, Individual MCCB/MCB for each
capacitor step as per Tender SLD.
(4) VFD / Soft Starter Panel Feeders - 4 Nos.
Each feeder comprising of 400A TPN TM MCCB, 50kA with Indicating lamps, MFM with RS-
485 etc.complete in all respects.
(5) 125 KVAR APFC Panel Feeder : 1 No.
Each feeder comprising of 250A TPN TM MCCB, 50kA with with Digital Ammeter, ASS, CT,
1.18(i) + 1.18(j) + Market Rate
Sr.No Item Description Qty. Unit Amount in Rs.
5.2 SITC of 125 KVAR APFC PANEL, Totally enclosed, Compartmentalized, Floor / Stand 1.00 No. 304744.80
mounted, Dust & Vermin proof, Indoor type, fabricated from CRCA sheet steel with minimum
thickness of 3 mm for base frame/ channel/ gland plates, 2.0 mm for load bearing
members/ doors & 1.6 mm for internal partitions, suitable for Outdoor installation, 3-Phase,
4 Wire, 415V, 50Hz, Neutral effectively grounded, with instrumentation compartments
accomodating meters, aux / protective relays, LED type indicating lamps & control MCBs as
per IS:13947, air insulated electrolitic grade Aluminium busbar for three phase & neutral
system, GI earth bus for entire length, power/ control wiring using 1100V grade, FRLS
insulated copper conductor wires conforming to IS: 694 & 8130, incoming & outgoing cable
connections for 1100V grade, Aluminium/ Copper conductor XLPE/ PVC insulated & PVC
sheathed armoured cable complete in all respects as per Tender SLD / Specification / IS and
including following as minimum:
1.1 250A, TPN, 50 KA TM MCCB with Digital Voltmeter with VSS, Digital Ammeter with ASS,
Resin Cast CT- Cl: 0.5,10VA, A/M switch, Indicating lamps, Push buttons etc.
1.2 Microprocessor based APFC Relay, 96 / 144sq.mm, 8 Stage with RS 485, minimum
operating current 10mA.
2. OUTGOING CAPACITOR FEEDER:
Capacitor feeder of following rating comprising of TP MCCB/ 'D' Curve MCB, Capacitor duty
contactor, 415V Heavy duty MPP type capacitor, A/M Switch, ON Delay timer,ON / OFF Push
button, ON Indication lamp etc. as per Tender SLD & Specification.
2.1 25 KVAR FEEDER: 3 Nos
(GWSSB E&M SOR 2022-23, Page No.72, SEC-E Item No. 40.3 + Market Rate
5.3 Outdoor Cable Junction Box
SITC of Outdoor Cable Junction Box, stand mounted, dust & vermin proof, minimum degree
of protection - IP 55, Operation on 3-Phase, 4 Wire, 415V, 50Hz, effectively grounded, with
400A TPN Al. busbar considering current density 0.8A/sq.mm, busbar support, insulator,
Terminal arrangement for control cable, Internal Control wiring, LED Light etc. JB shall be
fabricated from cold rolled, cooled annealed (CRCA) sheet steel & minimum thickness of
various members shall be as follows:
Base Frame / Channel / Gland Plate: 3 mm, Load Bearing Members / Doors: 2 mm and
Internal Partitions: 1.6 mm. Minimum JB Dimension (600W x 600H x 450 D mm) + Stand
Height Min. 450mm shall considered. JB dimensions may very as per site condition and
Number of Cable in and out sizing and clear spacing.
(As per Market Rate) 3.00 Nos.. 35000.00
6 SITC of Soft Starter / VFD Panel totally enclosed, Compartmentalized, dust & vermin proof,
Indoor type, minimum degree of protection - IP 42 or better as per IS: 2147, operation on 3-
Phase, 4 Wire, 415V, 50Hz, Neutral effectively grounded, with instrumentation
compartments accomodating LED type indicating lamps, control contactors as per IS:
13947, CT of accuracy class- I as per IS: 2705, relays, meters & control MCBs, air insulated
electrolitic grade Copper bus bar for three phase & neutral system with incomming breaker-
microprocessor based Air Circuit Breakers / Micr. based MCCB (LSIG) with trip free
mechanism, current limiting type as per IS: 8828,Motor Contractor (as per type -2
coordination) auxiliary feeders as per SLD drawings, momentary contact type push buttons,
equipment fittings, bus bars, cable boxes, incoming & outgoing cable connection for 1100V
grade, Aluminium/ Copper conductor XLPE / PVC insulated & PVC sheathed armoured
cable, 10% spare terminals, power wiring using 1100V grade, FRLS insulated copper
conductor wires conforming to IS: 694 & 8130, cable compartments / alleys of minimum
mm size, GI / AL. earth bus bar for entire length. Panel shall be fabricated from cold rolled,
coled annealed (CRCA) sheet steel & minimum thickness of various members shall be as
Base Frame / Channel / Gland Plate: 3 mm, Load Bearing Members / Doors: 2 mm and
Internal Partitions: 1.6 mm.
Sr.No Item Description Qty. Unit Amount in Rs.
180KW Microprocessor based Soft Starter with Internal / External by pass contactor, Door 1.00 No. 751631.00
Mounted Display, Micr. based MCCB (LSIG), Semiconductor Fuses, Line Contactor, cast
resin type CT Cl-1.0, Digital MFM, Digital Ammeter, 415V/230V AC Constant voltage/control
voltage transformer min 250VA, A/M & L/R switch, Start Stop Push Button, Exhaust Fan, &
Minimum 12 Channel Temperature Scanner with RS 485 communication port.etc.
1. The Soft starter rating shall be selected considering Ambient Temperature at 50C or
minimum 120% of the full load rated current of the motor name plate / Approved Data sheet
Which ever is higher. Soft Starter selection calculation shall be submitted for approval
before procurement.
2. 50 KVAr Fixed Type MPP Type Heavy duty capacitor shall be considered to improve PF
with aceesories like A/M switch, Pushbutton, Indication lamp, Capacitor Duty contactor, On
delay Timer shall be considered as part of the panel. Capacitor shall be accomodated in
seperate compartment with cooling fan arrangement.
All Soft strater must be provided with RS485 communication and all necessary Command
and feedback for SCADA operation.
(GWSSB E&M SOR 2022-23, Page No.49, SEC-E Item no. 22.1 i) + Market Rate
Supply, installation, testing & commissioning of 415 V Fully automatic microprocessor 2.00 Nos. 1127940.00
based Variable Frequency drive for pump control application and general specification as
The VFD unit shall have modular construction, 6 Pulse Bridge rectifier, speed control by
means of sensorless vector control (open loop), high torque at low frequencies, locking at
high and low frequency settings, In-built PID control, frequency accuracy of ± 0.1 % (min),
frequency resolution of ± 0.1 Hz (min), protections against; a) overload (motor and drive), b)
short circuit, c) ground fault, d) input / output phase loss (open circuit), e) stalling, f) input /
output undervoltage (momentary power loss restart), g) input / output overvoltage, h) over-
frequency, i) Input surge, j) over temperature of heatsink, k) loss of remote speed signal etc.
The VFD shall also have user friendly programming software & it shall be capable of at least
two level parameter setting with password lock for critical parameters, programming for
I/Os, copy parameters (upload / download) to other identical unit, tuning to energy saving
mode (maximum efficiency), event / fault recording (last 5 faults in non-volatile memory) &
RS 485 communication port (MODBUS RTU protocol) with required software for below
180KW HD VFD with Door Mounted Display, 400A TPN Microprocessor MCCB (LSIG), Input
AC and Output AC Choke as per OEM Recommendation, Indication Lamp, cast resin type CT
Cl-1.0, Digital MFM, Digital Ammeter,415V/230V AC Constant voltage/control voltage
transformer min 250VA, A/M & L/R switch, Start Stop Push Button, Exhaust Fan, minimum
12 Channel Temperature Scanner with RS 485 communication port.etc.
(GWSSB E&M SOR 2022-23, Page No. 49, SEC-E Item no.21 Sr.No.19) + Market Rate
6.3 SITC of Lighting Distribution Board (LDB) as under: 1.00 No. 11488.00
3 Phase 4 Wire 4P, Double door Prewired LDB each for Indoor Lighting & Outdoor Lighting
Suitable to pump house :
Incoming: 40A FP, MCB
32A DP ELMCB (30mA) (3 nos)
20A SP MCB (6 nos.) & 16A SP MCB (6 nos.)
(R&B SOR 2025-26, Item No.3.11.5(B)(b)(ii) + Item No.- 3.10.1(B)*12 + Item No.-3.10.4(b) +
Item No. 3.12.1(ii)*3)
6.4 SITC of Lighting Distribution Board (LDB) as under: 1.00 No. 3307.00
1 Phase 3 Wire, Double door Prewired LDB each for Indoor Lighting & Outdoor Lighting
Suitable to Pump house :
Incoming: 25A DP, MCB with ELCB (30mA)
10A SP MCB (4 nos.)
(R&B E&M SOR 2025-26 item no.3-11-5(iii)) + Item no. 3-12-1(i) + Item no. 3-10-3(A)+ Item
Sr.No Item Description Qty. Unit Amount in Rs.
7 LOW VOLTAGE (LT) CABLES
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium
conductor, galvanised steel flat strip / round wire armoured, extruded PVC type ST2
sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing
cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site
requirement) conforming to IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes
3.5 Core x 240 Sqmm A2XFY Cable ( 4 Run from Tr. to PMCC Panel + 1 Run PMCC to APFC 300.00 Mtrs. 783.00
(GWSSB E&M SOR 2022-23, Page No. 51, SEC-E Item no. 23.2 i)
3.5 Core x 150 Sqmm A2XFY Cable (2 Runs from PMCC to SS/VFD & VFD/SS to JB ) 350.00 Mtrs. 504.00
(GWSSB E&M SOR 2021-22, Page No. 51, SEC-E Item no. 23.2 g)
7.3 4C x 6 sq.mm. A2XFY(X) Cable 40.00 Mtrs. 78.00
(GWSSB E&M SOR 2022-23, Page No. 51, SEC-E Item no. 23.3 c)
7.4 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable 150.00 Mtrs. 81.00
(GWSSB E&M SOR 2022-23, Page No. 52, SEC-E Item no. 23.6 a)
7.5 6 Triad x 1.0 sq mm copper armoured 90.00 Mtrs. 538.00
(As per Market Rate and RA)
8 CABLE END TERMINATION AND CONNECTION:
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic lugs
/ sockets with necessary tools and equipments as specified in specifications and IS. The
glands and lugs / sockets shall be suitable for cable size and type mentioned below & as per
specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also connecting to
common earth bar.
2) The job also includes, if necessary, supply & fixing of extension busbar of same material
on MCCB or panel board terminal / connector to connect more than one no. of parallel
cables or to connect higher size cable to lower size unit. The job also includes earthing the
glands and armour of the cable with common earth bar or flexible copper mesh.
8.1 3.5 Core x 240 Sqmm A2XFY Cable ( 4 Run from Tr. PMCC Panel + 1 Run PMCC to APFC 10.00 Nos. 838.00
(GWSSB E&M SOR 2021-22 Section E, Item no. 28.2 (n) + 27.1(n)*3 + 27.1(k) )
8.2 3.5 Core x 150 Sqmm A2XFY Cable (2 Runs from PMCC to VFD & VFD to JB ) 24.00 Nos. 504.00
(GWSSB E & M SOR 2021-22 Section E, Item no. 28.2 (l) + 27.1(l)*3 + 27.1(i) )
8.3 4C x 6 sq.mm. A2XFY(X) Cable 2.00 Nos. 110.00
(GWSSB E&M SOR 2022-23 Section E, Item no. 28.2 (c) + 27.1(c)*4
8.4 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable 8.00 Nos. 93.00
(GWSSB E&M SOR 2022-23 Section E, Item no. 28.2 (a) + 27.4(a)*4
8.5 6 Triad x 1.0 sq mm copper armoured 6.00 Nos. 280.00
(As per Market Rate and RA)
Supply & laying GI perforated type cable trays with returned edge/ flange, fabricated from
2.0 mm thk sheet steel in the standard length of 2.5 mtrs, duly hot dipped galvanized after
fabrication as per IS 2629-1989 / IS 4759-1984 including accessories such as coupler
plates/ fish plates, bends,tees, reducers, elbows, covers and electro-galvanized hardware
etc, erected on existing support as per specification and instruction of engineer in charge.
(GWSSB E&M SOR 2022-23, Page No.68, SEC-E Item no. 35.2 D(b)
(GWSSB E&M SOR 2022-23, Page No.68, SEC-E Item no. 35.2 D(c)
Supplying & fixing Steel Chequered Plate having 7 mm thickness,duly painted with two 5.00 Sq. 3496.00
coats of black Japan colour. (Average Wt. 61.1 kg/ Sq.Mtr.) Mtrs.
(R&B E&M SOR 2021-22, Page No.307, SEC-D Item no. 10.3.37)
Sr.No Item Description Qty. Unit Amount in Rs.
11 CHEMICAL EARTHING
SITC of Chemical earthing with earthpit of minimum bore dia. 225mm Safe Earthing
Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free
G.I.Pipes having Outer pipe dia of 80 mm having 80-200 Micron galvanising, Inner pipe dia
of 40 mm having 200-250 Micron galvanising, connection terminal dia of 14 mm with
constant ohmic value surrounded by highly conductive compound with high charge
dissipation suitable for following type of applications.
11.1 For Electrical installation up to 11 KV located in other than normal soil i.e. Soft Rock, Marshy 11.00 Nos. 7024.00
-Length of Pipe : 2 mtrs.
-Back filling Compound :1 no. Bag of 25 Kg.
(2 nos. for Tr. Body, 2 Nos. RMU, 2 Nos. PMCC Panel, APFC Panel, 2 Nos.Outdoor JB, 3 Nos.
(R&B E&M SOR 2021-22, Page No. 92, SEC-D Item no. 3.14.10 b)
11.2 For Electrical Installation covering Transformer Neutrals, Lightning arrester Earthing, 4.00 Nos. 10488.00
Instrumentation (like PLC Panel, SCADA)i.e.independent Earthing located in other than
normal soil i.e.Soft Rock, Marshy Soil etc..
-Length of Pipe : 3 Mtrs.
-Back filling Compound :2 nos Bags of 25 Kg.
(2 nos. Each for Neutral of Transformer & LA )
(R&B E&M SOR 2021-22, Page No. 92, SEC-D Item no. 3.14.10 c)
11.3 Providing one bag of 25 kg. Additional back filling compound (BFC) suitable for safe 4.00 Nos. 700.00
earthing device.
(R&B E&M SOR 2021-22, Page No. 92, SEC-D Item no. 3.14.11)
11.4 SITC of 50mm(w) x 6mm(T) etc. sizes as required, HOT dip galvanized GI Strip including 300.00 Kg. 77.00
supply & fixing using GI spacers, saddles when laid inside the building and inclusive of
excavation & refilling of earth when laid outside the building & interconnection with earth
pit & all electro-mechanical equipments.
(50X6 G.I Strip wt.2.4 kg/m, 2.4x125Mt.=300kg.)
(R&B E&M SOR 2025-26, SEC-D Item no. 3.14.2 )
11.5 SITC of 25mm(w) x 6mm(T) etc. sizes as required, HOT dip galvanized GI Strip including 60.00 Kg. 77.00
supply & fixing using GI spacers, saddles when laid inside the building and inclusive of
excavation & refilling of earth when laid outside the building & interconnection with earth
pit & all electro-mechanical equipments.
(25X6 G.I Strip wt.1.2 kg/m, 1.2x40Mt.=60kg.)
(R&B E&M SOR 2025-26, SEC-D Item no. 3.14.2 )
11.6 Supply, laying and erection of 40mm(w) x 6mm(T) etc. sizes Copper Strip including supply & 47.00 Kg. 787.00
fixing of bolts, saddles when laid inside the building and inclusive of excavation & refilling
of earth when laid outside the building & interconnection with earth pit & Tr. neutral. (40X6
Cu. Strip, 1.88 Kg/m, 1.88 x 25mtr.=47Kg.) Copper Bolt,Nuts ,Washers shall be used for
Connecting Earth electrode toindividual eqp. Bitumen shall be used at the place of
(R&B E&M SOR 2025-26, SEC-D Item no. 3.14.3 )
11.7 SITC of HOT Dip Galvanized iron strip wire 8 SWG. 5.00 Kg. 77.00
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 50Mt.=5 Kg.)
(R&B E&M SOR 2025-26, SEC-D Item no. 3.14.5 )
12 INTERNAL WIRING
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI marked
flexible stranded copper conductor wires with medium class min. 25mm. dia. Rigid PVC pipe
and accessories to be erected concealed in / to be run on surface / wall / ceiling with
following sizes as mentioned below. The unit rate wirings shall be with connector, PVC
junction box, wires, holder, ceiling rose, angle holder, switch, sockets, switch board, brass
chromium / cadmium plated machine screws, phase and neutral wires, green Earth
continuity wires etc. as
required to complete wiring from LDB panel to the final outlet termination points. The wiring
shall be as per IS:732, IS:4648 and as per tender specification / IS.
12.1 SITC of Mains wiring with 3 wire 1.5 sq.mm. 200.00 Mtr. 82.00
(R&B E&M SOR 2025-26, SEC-D Item no. 1-4-1(A)(c))
12.2 SITC of Mains wiring with 3 wire 2.5 sq.mm. 150.00 Mtr. 101.00
(R&B E&M SOR 2025-26, SEC-D Item no. 1-4-1(A)(d))
Sr.No Item Description Qty. Unit Amount in Rs.
12.3 SITC of Mains wiring with 4 wire 1.5 sq.mm. 100.00 Mtr. 90.00
(R&B E&M SOR 2025-26, SEC-D Item no. 1-4-1(A)(e))
12.4 SITC of Mains wiring with 4 wire 2.5 sq.mm. 100.00 Mtr. 125.00
(R&B E&M SOR 2025-26, SEC-D Item no. 1-4-1(A)(f))
Point wiring for Light/ Bell with 2-1.5 sq. mm & earthwire of 1.5 sq.mm (Green) both are of ISI
marked 1.1kV grade FRLS PVC insulated multistrand copper wires, in following type of pipe
to be erected concealed in/ on surface on wall/ ceiling complete with 6A Modular type
switch/ bell push & accessories and earth continuity of following type, erected on PVC/
Metallic box, single mounting base frame covered with textured/ metallic front plate
modules erected on/ in wall/ ceiling as per pipe erected, with necessary Lamp holder/ceiling
rose/ H.D.Connector as directed.
12.5 (a) with medium class rigid PVC pipe and accessories erected flushed on wall /Ceiling 5.00 Nos. 445.00
complete CATIII
(R&B E&M SOR 2025-26, SEC-D Item no. 1-2-1(a))
Point wiring for Individual Plug with earthwire of 1.5 sq.mm (Green) both are of ISI marked
1.1kV grade FRLS PVC insulated multistrand copper wires, in following type of to be erected
concealed in/ on surface of wall/ ceiling complete with Modular type switch & 5 pin Plug
erected on PVC/ Metallic box covered with appropriate front
plate modules erected on/ in wall/ ceiling as per pipe erected with following type of
12.6 For 6A Plug with 2-1.5 sq.mm Cu. Wire with medium class Rigid PVC pipe and accessories 2.00 Nos. 471.00
(R&B E&M SOR 2025-26, SEC-D Item no. 1-2-3(I)(a))
Point wiring for independent PLUG with following size mains & earthwire of 2.5 sq.mm
(green) both are of ISI marked 1.1kV grade FRLS PVC insulated multistrand copper wires, in
following type of pipe to be erected concealed in /flushed on wall/ ceiling, complete with ISI
marked 3/5 Pin socket and tissino type switch erected with
earth continuity connection erected on Metal/ PVC box covered with 3 mm thick PC
(Polycarbonet)/ Acrylic sheet.
12.7 6/16A Plug with 2-4 sq.mm Cu. Mains with medium class Rigid PVC pipe and accessories 2.00 Nos. 829.00
(R&B E&M SOR 2025-26, SEC-D Item no. 1-2-3(III)(a))
13.1 AREA Lighting (Flood LIGHT) : 5.00 Nos. 5143.00
SITC of 40W LED Wall mounted LED Flood Light fittings with High power White LEDs
wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w
and corrosion free High pressure die cast aluminum housing with smooth finish powder
coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses
with company mark/name engraved or embossed 120 to 300 V,Power Factor more than
0.95, THD < 20 %, CCT 5000 K to 5700K, Uniformity ratio >0.45, Luminaries efficacy>
lumens/watt . LED driver efficiency > 85 %. ( Each fittings required LM-79 & LM-80
certificates) (IP-65), Surge -4KV Cat-III
For Outdoor use
(R&B E&M SOR 2025-26, SEC-D Item no. 2-16-2-(B)(I))
13.2 AREA Lighting (Flood LIGHT) : 8.00 Nos. 6028.00
SITC of 70W LED Wall mounted LED Flood Light fittings with High power White LEDs
wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w
and corrosion free High pressure die cast aluminum housing with smooth finish powder
coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses
with company mark/name engraved or embossed 120 to 300 V,Power Factor more than
0.95, THD < 20 %, CCT 5000 K to 5700K, Uniformity ratio >0.45, Luminaries efficacy>
lumens/watt . LED driver efficiency > 85 %. ( Each fittings required LM-79 & LM-80
certificates) (IP-65), Surge -4KV Cat-III
For Outdoor use
(R&B E&M SOR 2025-26, SEC-D Item no. 2-16-2-(B)(III))
Sr.No Item Description Qty. Unit Amount in Rs.
14.1 SAFETY ACCESSORIES 2.00 Nos. 6526.00
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with necessary
clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall complete.
(R&B E&M SOR 2025-26, SEC-D Item no. 10-2-26(A)
14.2 Supplying & fixing of floor mounting stand for keeping four nos. of FIRE buckets comprising 2.00 Nos. 933.00
1500 mm in length, 900 mm height frame made out of 30mm X30mm X 4 mm angle iron
with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead
and two coats of approved enamelled silver paint.
(R&B E&M SOR 2025-26, SEC-D Item no. 10-2-6
14.3 Supply and laying of Synthetic Insulating Mat of Class - B / min. thickness 3mm as per 8.00 Sq.Mtr. 763.00
IS:15652/IEC61111 and with good electrical insulation property as per site requirement. (for
(R&B E&M SOR 2025-26, SEC-D Item no. 10-2-3-(a)
14.4 Providing pair of rubber hand gloves ISI make suitable for working on 11KV/22 KV supply 2.00 Nos. 212.00
(R&B E&M SOR 2025-26, SEC-D Item no. 10-2-2
15 LIASONING CHARGES FOR OBTAINING NOC 1.00 Ls. 25000.00
Power Liasoning Charges for obtaining N.O.C from Electrical Inspector / Statutory authority
for Power / Ele. Installation. (Fees shall be paid by tenderer for obtaining N.O.C. from
Electrical Inspector / Statutory authority on behalf of client and shall be reimbursed on
submission of original receipt to Client). Liasoning Charges shall include preparing required
attested documents & drawing for obtaining NOC on behalf of client (Applicable Fees /
deposits shall be reimbursed by Client).
INSTRUMENTATION WORK
Sr Unit Rate Total Rate
Item Description Qty Unit
No (Without GST) (Without GST)
Uninstallation of existing PH & Chlorine Analyzer panel as per tender specification and
Installation, testing and commissioning of existing PH & Chlorine Analyzer panel with
all associated accessories as per tender specification and scope of work.
Supply, installation, fixing, testing and commissioning of 19 mm dia. UPVC pipe,
including UPVC pipe jointing solution (50 ml), 19 mm size Ball Valve with long handle,
Teflon tape, and provision of 0.5 inch (15 mm) dia. GI tapping point on existing MS/HS
3 water line with SS Ball Valve, including all necessary fittings, connectors, jointing 1.00 Job ₹ 30,000.00 ₹
materials, clamps, supports, consumables, labour, tools and tackles, transportation,
testing and all other incidental works, complete in all respects as per tender
specifications, drawings and scope of work, as directed by the Engineer-in-Charge.
Uninstallation of existing Non contact type ultrasonic level transmitter as per tender
specification and scope of work.
Installation, testing and commissioning of existing Non contact type ultrasonic level
5 transmitter with all associated accessories as per tender specification and scope of 1.00 Job ₹ 10,000.00 ₹
Uninstallation of existing Full bore type Electromagnetic flowmeters as per tender
specification and scope of work.
Uninstallation of existing PLC Panel, UPS, Battery, PDB, Local Indicator Panel, CCTV
7 with JB, Gateway panel, router, adaptorand other as per tender specification and scope 1.00 Nos. ₹ 10,000.00 ₹
Installation, testing and commissioining of existing PLC Panel, UPS, Battery, PDB,
Local Indicator Panel, CCTV with JB, Gateway panel, router, adaptorand other with all
associated accessories as per tender specification and scope of work.
Providing and erecting required size HOT deep Galvanised iron strip of size 25*6 mm
9 for earthing of PLC Panel as per tender specification and scope of work. 50.00 Kg ₹ 76.00 ₹
Supply, laying and dressing of 3 Core 2.5 sqmm copper armoured cable as per tender
specification and scope of work.
Supply, laying and dressing of 1 Pair 1.5 sqmm copper armoured cable as per tender
specification and scope of work.
Supply, laying and dressing of 1 Core 6 sqmm copper flexible cable as per tender
specification and scope of work.
Supply, laying and dressing of 4 Core 2.5 sqmm copper armoured cable as per tender
specification and scope of work.
Supply, laying and dressing of 16 Core 1.5 sqmm copper armoured cable as per tender
specification and scope of work.
Supply, laying and dressing of 1 twisted Pair 1.0 sqmm copper flexible shielded cable
15 for modbus(Rs-485 Serial) communication as per tender specification and scope of 200.00 Mtr. ₹ 82.00 ₹
Supply and fitting of perforated type cable tray of size 200 mm*25 mm*2 mm as per
tender specification and scope of work.
Supply and fitting of perforated type cable tray of size 50 mm*25 mm*2 mm as per
tender specification and scope of work.
Supply, laying, installation, fixing, testing and commissioning of complete electrical
cable/conduit system, including supply and laying of HDPE conduit of 50 mm OD;
supply and fixing of PVC conduits of 25 mm OD and 40 mm OD suitable for
electrification work; supply and fitting of double-compression brass cable glands and
suitable copper lugs at both ends of cables for copper armoured cables; supply,
fabrication and installation of Expander, Reducer, Flanges, Socket, Distance Piece and
all other required MS special works, including material, fabrication and labour; supply
18 and fixing of cable route markers including concrete foundation; excavation in soft soil, 1.00 Job ₹ 62,000.00 ₹
laying of conduits/cables and subsequent backfilling and reinstatement of excavated
area, complete with all necessary materials, fittings, accessories, supports, jointing
materials, consumables, labour, tools and tackles, transportation, testing and
commissioning, and all other incidental works, complete in all respects as per tender
specifications, drawings, approved standards and scope of work, as directed by the
Engineer-in-Charge.
Sr Unit Rate Total Rate
Item Description Qty Unit
No (Without GST) (Without GST)
Supply, Installation, testing and commissioning of pipe-in-pipe chemical earthing
19 suitable for RTU Panel as per tender specification and scope of work. 1.00 Nos. ₹ 12,375.00 ₹
Supply, Installation, testing and commissioning of DC Powered Full bore type
20 electromagnetic flowmeter of size DN 600 mm as per tender specification and scope 1.00 Nos. ₹ 5,91,846.00 ₹
Supply, Installation, testing and commissioning of DC Powered Full bore type
21 electromagnetic flowmeter of size DN 450 mm as per tender specification and scope 1.00 Nos. ₹ 4,25,000.00 ₹
Supply, Installation, testing and commissioning of Electrical actuator for BFV of size
DN 600 mm as per tender specification and scope of work.
Supply, Installation, testing and commissioning of Electrical actuator for BFV of size
DN 450 mm as per tender specification and scope of work.
Supply, Installation, testing and commissioning of Mettalic expansion bellow of size
600 mm*300 mm as per tender specification and scope of work.
Supply, Installation, testing and commissioning of Mettalic expansion bellow of size
450 mm*300 mm as per tender specification and scope of work.
Total Amount (Without GST) ₹
Total Amount (Without GST) ₹
SCHEDULE OF QUANTITIES & RATES FOR SITC OF ELECTRICAL, MECHANICAL, INSTRUMENTATION WORKS WITH TWO YEARS OF O&M FOR VMC AT SAYAJIBAUG
HEADWORKS WATER SUPPLY SCHEME
The works of this schedule comprises of the supply of all spare parts as required including the supply of all labour (including reliever to ensure presence of specified type
and no. of manpower per shift), materials, consumables (except electrical power), equipments, tools and tackles and comprehensive operations and maintenance during
the 2 Years of O&M from the date of successful commissioning as shown in table below.
Ite Item of Work Duration Unit Rate per Amount
1.0 Staff Salary - During First year
The works of this schedule comprises of the supply of all spare parts as required
including the supply of all labour (including reliever to ensure presence of
specified type and no. of manpower per shift), materials, consumables (except
electrical power), equipment, tools and tackles and comprehensive operations
and maintenance of during the Five Year of O & M from the date of
successful commissioning as shown in table below:Total staff salary for First
years for Operation and security, repairing and maintenance for the complete year
a Engineer (DEE / DME) - 1 No. (During general shift) 1.00 Months
b Supervisor (12th std.) - 1 No. (During general shift) 1.00 Months
c) Pump operator - (ITI-Wireman / Eletrician) (3 nos. - one for each shift of 8 hrs.) 1.00 Months
d Helper / Labour (9 nos - Three for each shift of 8 hrs.) Rs.681.45 x 365 /12 = 1.00 Months
e Line man / Keyman - 6 Nos. (Two for each shift of 8 hrs.) (Rs.693.91 x 365 /12 = 1.00 Months
f) Watchmen/Security - 3 Nos. (One for each shift of 8 hrs.) (Rs.681.45 x 365 /12 = 1.00 Months
A Total of Manpower for 5 Year (a + b + c + d+e )=23 Persons
2.0 Comprehensive Maintenance
Comprehensive repairing, spares and maintenance of entire works alongwith
administration & management charges including running office, cost of
lubricants, consumables, spares, tools,statutory periodical approvals & testing
MONTH OPERATION MAINTENENCE TOTAL
of eqipments etc. required in all except supply of ele. power and water during O&M
period for First Year of O&M period
B Total of Comprehensive Maintenance for 2 Year
C Other Expenses
3.0 Monthly charges for Central SCADA of Client ( SIM Charges Rs. 200/- per month) 24.00 Month 200.00
E TOTAL OF O&M FOR 2 YEARS (A + B+C)
ROVIDING, SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING OF DIRECT WATER DISTRIBUTION SYSTEM BY BYPASSING THE EXISTING ELEVATED SERVICE RESERVOIR (ESR) AT SAYAJIBAUG WATER TANK, INCLUDING CONSTRUCTION
OF ALL ALLIED CIVIL WORKS, SUPPLY AND INSTALLATION OF PUMPS, MOTORS, PIPING, VALVES, ELECTRICAL PANELS, INSTRUMENTATION, CABL ING, TESTING, COMMISSIONING AND COMPREHENSIVE OPERATION & MAINTENANCE 24 MONTHS.
I/We am/are willing to carry out the work at… ..................... % above/below percent(Should be
written in figures and words) of the estimated rate mentioned above. Amount of my /our
tender works out as under.
Estimated amount put to tender Estimated amount put to tender
Deduct………% below Add………% Above
In words In words
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1.0 SBD- Sayajibaug By-Pass Arrengment.pdf
2.0 General Specifications-Sayajibaug By-Pass Arrengment.pdf
3.0 Electro Mechnical Specification-Sayajibaug By-Pass Arrengment.pdf
4.0 Instrumentation Specification-Sayajibaug By-Pass Arrengment.pdf
5.0 Modified ONM Specification- Sayajibaug By-Pass.pdf
6.0 Vendor List-Sayajibaug By-Pass.pdf
7.0 Price Bid_Sayajibaug By-Pass.pdf
BYPASS ARRAGMENT DWG AT SAYAJIBAUG.pdf
7.0 Revised Price Bid_Sayajibaug By-Pass.pdf
CORRIGENDUM
Corrigendum-I Response to Prebid Queries Sayajibaug.pdf
CORRIGENDUM
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .