| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAccepted-AOC 22 1685 ST JACOB CHURCH LANE PAMBAIMOOLA EDACOCHIN ERNAKULAM KERALA 682010 | ERNAKULAM | ERNAKULAM | KERALA | 682010 | ₹1.1 Cr | L1 | Accepted-AOC REASONABLE LOWEST BIDDER |
| 2 | L2₹1.1 Cr+₹3.5 L (3.25%)Rejected-Finance 42 608A PULLOMPARAMBIL HOUSE MANDAKARA ROAD KOCHI 682 018 | ERNAKULAM | KERALA | 682018 | ₹1.1 Cr+₹3.5 L (3.25%) | L2 | Rejected-Finance NOT BEING LOWEST BIDDER |
| 3 | L3₹1.5 Cr+₹44.4 L (41.3%)Rejected-Finance | ₹1.5 Cr+₹44.4 L (41.3%) | L3 | Rejected-Finance NOT BEING LOWEST BIDDER |
Tender Value
₹99 L
EMD Value
₹1.7 L
Closing Date
14 Aug 2023, 6:00 pmClosed
CHIEF ENGINEER RND SECUNDERABAD
CHIEF ENGINEER RND PICKETSECUNDERABAD
PROVN OF TEST FACILITY SET UP FOR PROJECT INDIGENOUS OBSTACLE AVOIDANCE SONAR IOAS UNDER ASSP AT NPOL KOCHI
2023_MES_600562_1
86119
Open Tender
Civil Works
Lump-sum
365 days
KOCHI
AS PER NIT
8 documents required · 8 mandatory
₹1,000
ASSISTANT GARRISON ENGINEER I RND KOCHI
₹1.7 L
Yes
20 Oct 2023
2 Jun 2023
21 Aug 2023
2 Jun 2023
14 Aug 2023
31 Jul 2023
3 Jun 2023 - 20 Jun 2023
Amount
Schedule 'A' Part - I (BUILDINGS AND STRUCTURES) This Schedule (contains under mentioned Sl. item No. 1.01 to 1.03) is not prepriced by MES and the prepriced rate indicated in Col - 5 as `0.00 indicates this fact only.The tenderer is required to quote their rates in Column 6.
Lumpsum price worked out by the contractor for Construction of Test Facilities for Indigenous Obstacle Avoidance Sonar(IOAS) including Construction of RCC UG Water Tank complete all as shown on drawings and as per specification.
Construction of LLDPE Septic tank designed to carry sewage and sullage water, excavation in any type of soil PCC 1:4:8 below the vent shaft connection etc for 30 users complete all as specified and directed and as per specification.
Construction of Soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combedmasonry with top ring of M-25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes ofRCC/DWC complete filled with brick bats of size 1.80 x 3.00mtr depth complete all as specified and directed and as per specification
Lump sum price worked out by the Contractor for “EXCAVATION, EARTHWORK, SITE CLEARANCE AND AREA DEVELOPMENT ” as listed in Schedule ‘A’ Part - II representing _______ % ______________ percent Above / Below the lump sum price of ₹88,034.35 inserted by the MES in Schedule ‘A’ Part - II
Lump sum price worked out by the Contractor for “ ROAD / PATH / CULVERT / HARD STANDING ” as listed in Schedule ‘A’ Part - III representing __________ % ____________ percent Above / Below the lump sum price of ₹ 76,989.16 inserted by the MES in Schedule ‘A’ Part - III
Lump sum price worked out by the Contractor for “ SEWAGE DISPOSAL ” as listed in Schedule ‘A’ Part - IV representing __________ % ____________ percent Above / Below the lump sum price of ₹89,477.90 inserted by the MES in Schedule ‘A’ Part - IV
Lump sum price worked out by the Contractor for " EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part - V representing _______ % __________________ percent Above / Below the lump sum price of ₹59,325.60 inserted by the MES in Schedule ‘A’ Part - V
Lump sum price worked out by the Contractor for "EXTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Part - VI representing _______ % __________________ percent Above / Below the lump sum price of ₹2,06,798.11 inserted by the MES in Schedule ‘A’ Part - VI
Lump sum price worked out by the Contractor for "AIR CONDITIONING” as listed in Schedule ‘A’ Part - VII representing _______ % __________________ percent Above / Below the lump sum price of ₹18,685.60 inserted by the MES in Schedule ‘A’ Part - VII
Lump sum price worked out by the Contractor for“INTERNAL WATER SUPPLY ” as listed in Schedule ‘A’ Part - VIII representing _______ % _________________ percent Above / Below the lump sum price of ₹43,670.93 inserted by the MES in Schedule ‘A’ Part - VIII
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Part - IX representing _______ % _________________ percent Above / Below the lump sum price of ₹1,93,192.55 inserted by the MES in Schedule ‘A’ Part - IX
Schedule 'A' Part - X This Schedule is not prepriced by MES and the prepriced rate indicated in Col - 5 as ₹0.00 indicates this fact only. The tenderer is required to quote their rates in Column 6. This Schedule constitutes Sl. Item No. 11.00 to 33.00
Supply & fix NRV/ Reflux valve of size 100 mm nominal swing double flanged cast iron conforming to IS- 5312 complete all as specified and directed.
Supply and fixing of Ductile iron pipe with spigot and socket ends, vertically cast, class K-7, in any length, laid in trenches of size100mm dia with and including all fittings such as bends, elbows, tees, short pieces etc., in trenches complete all as specified and directed.
Supply and fixing water level indicator switch single phase 220 volt AC supply 50 HZ having LED for showing water level step by step indication by glowing the LED including PVC insulated cable for connecting the water level indication switch in operator room to connecting kit water sensor in reservior comprissing of the following:-(i) Water level indication switch - 01 Nos (ii) Flexible industrial cable copper conductor PVC insulated PVC sheithed 1100 V conforming to IS -694 of size 0.5 Sqm (16/0.2), 12 core incluuding GI wire for suspension fixing of PVC cable from O/H reseviore to Pump house building Make : Rallison / Plaza (iii) Contacting kit for dipping in water of reservoir for sensing of water level switch - 01 Set of 8 Nos (iv) copper cable 3 core of size 23.0076 of suitable length for electrical connection of water indicator including top plug - 01 set
Cutting the exisitng GI /CI pipe of size 80 mm dia, inserting tee of size 80 x 80 x 50 mm for taking branch connection including necessary threading, earth work, returning, refilling etc complete all as specified and directed.
Material & labour for Construction of brick masonry valve pit of internal dimension 60 x 60 x 60 cm depth with sub class 'B' bricks in CM (1:4) and 10 mm thick plastering in CM (1:4), PCC (1:4:8) type D2 (Using 40 mm graded broken stone aggregate) as in foundation lean concrete, PCC (1:4:8) type CI (using 20 mm graded broken stone aggregate) as in bedding and copping MS frame with 40 x 40 x 6 mm angle iron and 6 mm thick MS sheet cover plate with locking arrangements, hinges and two coats of synthetic enamel paint over one coat of red oxide primer including preparation of surface, two coats of white wash on plastered surface (exposed to view) including necessary excavation in soft loose, soil, returning filling in and removal of surplus soil to a distance not exceeding 50 m complete all as specified and directed.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25M deep below normal ground level) connecting to the galvanised iron strip 32x 6mm size by means of bolts, nuts, check nuts and washers of galvanised iron and 32 x 6mm earth lead protected by provision of GI light grade pipe 40mm bore including provision of concrete pit in PCC 1: 2:4 type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of RCC (1: 2:4) reinforced with XPM (weight not less than 4Kg/SqM) and frame of ange iron 25 x x25 x 3mm with lugs-02 Nos and with 6mm dia MS bar handle made to shape , GI medium grade 20mm bore pipe for watering perforated bottom 1.50M long placed on top edge of earth plate , common salt and chrcoal filling, test point with fixing arrangements, funnel , wire mesh and earth work in hard/ dense soil , returning filling in and removal of surplus soil to a distnce not exceedig 50Mtr all as per electricl plate No. 3 of SSR 2009 Part -I and connecting to earth test point all as specified .
Supply, install, test and commissioning of Outdoor type double door LT Feeder piller box made out of 3.0 mm thick CRCA sheet outdoor type totally enclosed weather dust and vermin proof as per IS, CPRI Approved with front opening suitable locking arrangement having copper bus bar of 400 Amps capacity RYB and full for neutral duly colour coding PVC sleeves fixed on insulators, including connecting incoming and outgoing cables necessary PCC 1:3:6 in foundation and made out of 50 mm x 50 mm x 6 mm angle iron grouted at ground above 30 cm from ground level with comprising of the followings etc complete with all as specified and directed by Engineer-in-Charge. (Note: Cost of necessary internal wiring bus bar to MCCBs/MCBs/Enclosure connections etc. shall be deemed to be included the unit rate.
Incoming: (a) MCCB 250 Amp 4 pole 36 KA Ics=100% of Icu with spreader & rom -01 No. (b) Indication Lamp Red/Yellow/Blue - 03 Nos (c) SP MCB 6A -03 Nos (d) MFM Metr with CT- 01 No Outgoings. (a) MCCB 200 Amps, 4 pole,25 KA Ics=100% of Ics with spreader & rom -01 No (b) MCCB 125 Amps 4 pole 16 KA Ics=100% of Ics with spreader & rom -01 No. (c) MCCB 63 Amp 4 pole 16 KA, 415 Volts , Ics=100% of Ics with spreader & rom -01 No.
M&L for extending the extisting LT panel board at Sub Station III with 2.0 mm thick CRCA sheet Factory made In door type totally enclosed weather dust and vermin proof as per IS , CPRI Approved, with front and rear opening suitable locking arrangement with necessary copper bus bar of capacity 400 Amps capacity RYB and full neutral duly colour coding PVC sleeved fixed on insulators so as to match with the existing LT panle board/Distribution panel by connecting to existing bus bar by using rigid copper bus bar by opening the one side of existing panel /bus bar including necessary supporting frame /channel fix through existing cable trench from ground with following:- (a) MCCB 250 Amps 4 pole,36 KA, Ics=100% of Icu with spreader & rom -01 No Make :MDS Legrand /L&T (b) Provision for outgoing cable of size up to 95 sq mm from the extended portion of LT distribution panel
S& F Vertical type MCCB DB 8 Way 415 Volts, 50 Hz, double door IP 43 protection powder coated factory made door earthing, isolated neutral bar insulated bus bar assembly suitable for and including MCCB 125 Amps ,4 Pole,16 KA as incomer and fixed in flush/ recessed mounting on wall at suitable height including making cable connections complete all as specified and as directed
All as per item 19 above but vertical type MCCB DB 4 way and with MCCB 63 amps, 4 pole, 16 KA all as specified and directed
S& F Industrial surface/wall mounting socket 32 Amp 3P + N + E-FP with plug 32 Amp IK 08 protection and sockets enclosure cabinet IP 43 protection 8 MOD fixed on surface/wall with including incomming MCB 32 Amp 4P 10 kA breaking capcity FP all as specified and directed
S & F LED Highbay/mediumbay light fitting 150 W , minimum efficiency of 150 lm/watt and pressure die cast housing with minimum 6 KV surge protection and IP 66 ingress protection, energy saving fixed on roof/ceiling , height not less than 9.0 Mtrs from ground level for area lighting with necessary fixing arrangment i.e. suitable size MS clamp , nuts & bolts, for lights complete as per site requirement all as specified and directed.
M&L for Earthing complete with using galvanised steel earth plate 600 mm x 600 mm x 0.6 mm thick electrode , buried directly in ground ( earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal groungd level .connected to 25 mm x 4 mm galvanised iron strip as earth lead by means bolts ,nuts, check nuts and washers all as shown in electrical plate No.3 connected to earthing test point all as specified or indicated including testing on completion necessary complete all as specified and as directed Note: Quated rate by the contractor is deemed to be inclusive of necessary excavation ,earth work ,PCC pit ,RCC cover ,funnel with watering pipe 20 mm bore light grade ,GI protection pipe 40mm dia light grade upto 7.5 m length.
Supply, Install , testing and commissioning of 1.5 TR capacity, 230V, 50 Hz, single phase split type Air conditioning unit 5 star rating , inverter type com plete with drive motor, air cooled condenser with all accessories varied speed and dual rotary compressor, including fixing the outdoor units as per manufactures recommendation and fixing of indoor (high wall) unit on wall, providing and making interconnection, including refrigerent piping with nitryle rubber insulation and control cable from indoor unit to outdoor unit up to a distance of 3.0 mtr, power cabling ( Max 3.0 mtr from isolator/ enclosure) to unit, first charging of refrigerant gas ( R32) incl cordless remote, drain piping of 25mm dia for connecting drain lines from indoor unit to maximum of 3.0 mtr to nearest drain points, outdoor support stand etc complete all as specified and directed.
Supply and fix automatic electronic voltage stabilizer of 4.0 KVA capacity ,wall mounting type having features such as Intelligent time Delay system, Low and High Voltage Cut-off Protection, latest IC Technology to protect from power fluctuations, Thermal over load protection, wide input variation between 170V to 270V with output voltage stablized at 220 to 240V, with accuracy of +/- 2.5% suitable for 1.5 TR split type Air conditioner complete all as specified and as directed by the Engineer -in -Charge.
Design, Supply, Install, Testing and Commissioning of Electrically operated over head travelling ( EOT)crane Single Girder of capacity 01 Ton load conforming to IS : 3177 (latest revision ) suitable for Class II duty having span of 9.00 metre (approximate), , height of lift 6 mtrs, travel length 16 Mtr (approx) suitable for operation on 415 V, 3 Phase, 4 wire , 50 HZ including Runway beam and Runway rail fabricated out of suitable structural brams( ISMB) duly powder coated on both sides with necessary fixing arrangement with Hoist speed 3.0 mtrs/min,Cross travel speed 10.0 mtrs/min, Long travel speed 15.00 mtr/min. withmicro drive through clutch and geared motor of suitable capacities with control panel, power and controlling cables, confirming to to relevent IS, controlled by pendent push buttons station and radio remote control switch of operation, with and including steel wire rope 8 mm dia, operation system hoist/Cross travel/ Long travel/ electrically operated with pendent DSL system of Shorouded bus bar type, with following specifications complete all as specified and directed.
(f) Wire rope 6 x 36 made of Fiber or Hemp core material of size 8mm dia having number of falls 4 confirmong to IS:2266 and tensile strength 1770 N/mm2. Rope drum will be fabricated type stress releived or seamless pipe duly machined and grooved to accomodate full length of rope in one layer. The drum should be mounted on antifriction ball / roller bearings. All Butt welded joints ( both compression/ tension and flanges/ web joints) shall be subjected to 100% X-Ray testing and X-Ray films to be produced for evaluation (g) Hook is made of EN 3A material type C' shank supported on anti friction thrust bearing and the sleeve pulleys shall be made out of malleable cast iron or fabricated confirming to IS:3815 (h) Gear box shall be totally enclosed type and oil bath lubricated. Gear box bodys shall be fabricated from MS plate/ cast iron as per IS 210. All gears shall be EN8 material finished teeth cut on accurate hobbing machine. Pinions shall be EN-19/24 meterial and heat - treated. All gears and pinions shall ground type so as to reduce noise levels to the minimum. Gear modules shall conform to IS: 3681 and ratings of gear shall be established as per IS: 4460.(j) Control panels indoor type, made of 2 mm thick CRCA sheet, coated with powder coated paint consiting V3F drive, MCCBs/MCBs, contactors, measuring meters, relays, connectors, busbars if required complete.Standard protection devices for overload and short circuit shall be provided.
(k) Complete wiring with flexible PVC insulated multistranded 1100 v grade copper conductor unarmoured cable of suitable sizes confirming to IS 7098 (Part I) 1988. (l) End trucks shall be equipped with spring / rubber buffers and rail sweep for bridge travel. The rail sweep shall be such that it can brush away any object that may fall on the runway. The buffers shall be of substantial design and suitable for engaging the stops at the end of run way. (m) S&F pendent push button station at an operating voltage of 110 V and IP 65 protection along with radio control remote.(n) S&F 2 Nos.of 70 watts LED lamp & light fitting shall be provided under the bridge and 1 No shall be provided under CT Trolley (o) Hoist shall be provided with both rotary and counter weight type ( Over hoistng and over lowering)Shunt , adjeustable type limit switches. Limit switch shall be provided for both CT& LT. Two way lever type for CT both direction and LT BOTH direction.(p) PVC Flexible festoon type travelling cable system supported on MS trolley moving on C- Rail for cross travel.(q) DSL system with 100 Amps PVC shrouded bus bar type (r) Complete painting of crane with two coats of Enamel paint ( colour - Golden Yellow) after cleaning and one coat of red oxide primer painting , and writing the details of crane, like capacity, date of installation, load test details etc.(s) Full length platform shall be provided at the one end for maintenance purpose and two short length platforms shall be provided on the other side.(t) Hoist 3.00 metre per minute, cross travel 10.00metre per minute and long travel 15.00 metre per minute alongwith micro speed of 10% of main speed to be achieved through VVVF drive for all three motions.(u) Red indication lamp fitting aviation type for indicating crane movement - 01 No (v) Radio remote system with all accessories should be multi speed steps of operations w) Pendent should be of Die cast Aluminium lr hard un breakable plastic having push buttons for each motion and it shall be hanged in the middle of bridge gider with crome plated steel chain & duly covered with sleev.
NOTE:(i) Supply and install of gantry rail is inclusive in the qouted rate .(ii) The rate quoted is inclusive of DSL GI shrouded busbar type of suitable capacity to operate in such a way that crane should work simulteneously if required. (iv) The contractor should take electric supply to the cranes from the incoming cable which will be provided. The rate quoted shall be inclusive of DBs, cables upto DSL of crane and connections cost. No extra payment shall be paid by the department. (v) The original span length shall be taken at site and the design calculation, all technical drawings & specifications of motor, control gear, travelling mechanism, hoisting mechanism, rope, hook and other components shall be submitted by the contractor duly vetted by NIT/ Govt Engineering College before fabrication of crane.
Supply and fix ceiling fan 1200mm sweep, single phase, 26 Watts, BLDC type, 5 star rated complete with down rod, blades, canopy etc including electric connection by providing three core copper cable from ceiling rose to fan and writing MES number with black paint complete all as specified and directed
Supply and fix exhaust fan 230mm sweep with louver ,single phase, matalic body and fixing arrangement on wall by providing suitable hole including electric connection by providing three core copper cable from ceiling rose to fan and writing MES number with black paint complete all as specified and directed
Supply laying and spreading of riddled earth in trenches for cable protection complete all as specified and directed.
Supply and fix LED tube light fitting 20 watt, 4 feet, surface and wall mounted batten with aluminium housing and integrated electronic driver, pre-wired including electric connection by providing three core copper cable complete.
Supply and fix LED tube light fitting 10 watt, 2 feet, surface and wall mounted batten with aluminium housing and integrated electronic driver, pre-wired including electric connection by providing three core copper cable complete.
Supply and fix LED security light fitting 36 watt, made up of pressure die cast housing with toughened glass and high power LEDs with IP 65 protection complete with electronic driver, pre-wired including providing GI bracket of suitable size bent to shape and fixing arrangement on wall surface with fixing clamps including electric connection with three core copper cable complete all as specified and directed
M & L for Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6mm thick burried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge of the plate vertically to a depth of not less than 1.5 mtr deep below normal ground level connection to and including 4mm dia (8 SWG) GI earth wire by means of GI bolts, nuts, check nuts, washers, thimble etc earth lead protected by 15mm dia light grade up to 7.5mtrs or up to test point/ connecting to DB including providing charcoal and salt all arround the earth plate up to 15cm thickness all as per electrical plate No 3 of SSR Part-I including watering arrangement with GI pipe 20mm dia medium grade and excavation and earth in any strata, returning , filling, ramming and remove of soil to a distance not exc 50 mtr distance and testing on completion.
WELTRONENGINEERINGSERVICES
Albert Rebello and Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .