Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.5 LAccepted-AOC 27 19 F F D BLOCK CHATTARPUR EXTN SOUTH WEST DELHI DELHI 110075 | SOUTH WEST DELHI | DELHI | 110075 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹41.7 L+₹3.0 L (7.65%)Rejected-Finance 44 NEAR DURGA MANDIR TRIPURI TOABA TRIPURI TOWN PATIALA 147004 PB | PATIALA | PUNJAB | 147004 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹42.7 L+₹4.0 L (10.3%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L3 | Rejected-Finance Other than lowest bidder |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
22 Jun 2023, 5:00 pmClosed
GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
REPAIR MAINT REPLACEMENT OF OH LT CONDUCTOR LT UNDER GROUND CABLE INCLUDING ALLIED WORKS AT SECTOR A UNDER GE UTILITY AMBALA CANTT
2023_MES_598416_1
CA NO GE U AMB T 52 OF 2023-24
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹90,000
6 Jul 2023
25 May 2023
24 Jun 2023
25 May 2023
22 Jun 2023
8 Jun 2023
25 May 2023 - 1 Jun 2023
Amount
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in loose/soft soil and getting out for underground cable/erection of poles, stays etc complete all as specified and as directed by Engineer-in-Charge.
All as per Srl item No.1 here in before but exceeding 1.5 mtr deep but not exc 3.0mtr deep.
M & L for sand cushioning for cable with river washed sand and punning to provide required cover as per SSR part I complete all as specified and as directed by Engineer-in-Charge.
Supplying and laying bricks common burnt clay sub class 'B' old size for cable protection.
All as per Item Ser No 4 here in before but except bricks. Note: Old bricks retrieved from item No 19 & 20 here in after shall be used.
M&L for PCC 1:4:8 type D-2 using 40mm graded aggregate, mechanically crushed stone for mass filling in pole pit and foundation etc including provision of necessary form work to achieve fair finished surfaces complete all as specified and as directed.
M&L for PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as in pole foundation, coping, stay pits etc including provision of necessary form work to aachieve fair finishes surfaces, complete all as specified and directed.
Material and labour PCC 1:2:4 type B-2 using 40mm graded aggregate, mechanically crushed stone for mass filling in pole pit and foundation etc. complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers n.exc 25 cm thick layers complete all as specified and as directed by Engineer-in-Charge.
Removal of excavated material n.exc 50 mtr away and depositing where directed at a level n.exc 1.5 mtr above from starting point complete all as specified and as directed by Engineer-in-Charge.
Dismantling and taking down old unserviceable PCC/Steel pole any type after disconnecting all electrical connection incl clearance of site complete all as the direction of Engr-in-Charge.
Supply , erection of PCC pole 9.0 mtr long in true vertical position 102x172 mm at top 102x279 mm at bottom class-10 incl providing black and white strips with synthetic enamel point 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete all as specified and as directed by Engr-in-charge. Note: Earth work and PCC shall be measured and paid separately. (ii) Description as per direction of Engr-in-Charge will be printed on each pole without any extra cost.
Supply,errection of steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type SP-31 (9 mtrs long) incl providing black and white strips with synthetic enamel point 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete all as specified and as directed by Engr-in-charge. Note: Earth work and PCC shall be measured and paid separately. (ii) Description as per direction of Engr-in-Charge will be printed on each pole without any extra cost.
Supply and fix indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as directed by Engr-in charge. Make 3MDenson/Reychem
Supply and fix indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as directed by Engr-in charge. Make 3MDenson/Reychem
Supply and fix indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-300 Sqmm complete all as directed by Engr-in charge. Make 3MDenson/Reychem
Supply and fix straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as directed by Engr-in charge. Note: Earth work will be measured and paid separately. Make 3MDenson/Reychem
M&L for drilling hole of any size manually as per site requirement, drilling for laying pipes under the road for crossing electrical cables complete all as per direction of Engr-in-charge. Note: Pipe will be measured & paid for separately.
Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc and making serviceable through straight through joints and testing on completion and re-laying the same all as specified and as directed.
Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 25 sqmm 3.5 core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall etc. Note: (i) Earth work, sand, bricks , removing, returning filling Aluminium thimbles/lugs will be paid separately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments , machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per Item Ser No 21 here in before but for 3.5 core 35Sqmm.
All as per Item Ser No 21 here in before but for 3.5 core 50 Sqmm.
All as per Item Ser No 21 here in before but for 3.5 core 95 Sqmm.
All as per Item Ser No 21 here in before but for 3.5 core 120 Sqmm.
All as per Item Ser No 21 here in before but for 3.5 core 185 Sqmm.
All as per Item Ser No 21 here in before but for 3.5 core 240 Sqmm.
Supply and fixing stay assembly complete with all accessories, such as stay plate 230X230X6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc. all as per electrical plate No 1 orr SSR part 1 and as directed incl taking down old unsv. Note: Only excavation and PCC work will be measured and paid separately.
M & L in replacement incl dismantling and taking down old for cross arms, bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primercoat, one under coat and one finishing coat of paint.
M&L in replacement for shackle type porcelain vitreous white or brown insulator including GI straps, washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm height, 90 mm dia, section of strap 30mmx3mm & dia of bolt 12 mm complete all as specified and as directed by Engineer-in-Charge.
M&L in replacement for pin type insulator porcelain vitreous white or brown 1100 volts grade 100 mm height and 65 mm dia with GI spindle two GI washer and one GI nut complete all as specified and as directed by Engineer-in-Charge.
Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as per direction of Engr-In-Charge.
M&L for aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site complete all as specified and as directed by Engineer-in-Charge.
M&L in replacement for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as directed by Engr-in Charge.
Dismantling and taking down old u/s earthing and Material & labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth strip of size 25x4mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, pit cover 50mm thick RCC 1:2:4 type B-1 using 8mm tor steel bars @10cm C/C both ways, 40mm bore medium grade GI protection pipe, watering pipe 20mm bore medium grade, funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified and as directed by Engineer-in-Charge. Note: (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost
Dismantling and taking down old u/s earthing and Material & labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth wire of size 4 mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, pit cover 50mm thick RCC 1:2:4 type B-1 using 8mm tor steel bars @10cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20mm bore medium grade, funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified and as directed by Engineer-in-Charge. Note: (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost
Material and labour for fixing in replacement GI tubing 50 mm bore light grade, on poles,on walls, under floors, road crossing, as reqd at site complete all as directed by Engr-in Charge. Note: Clamps, Nut bolts, saddle etc will be measured and paid separately.
All as per Srl item No.37 here in before but 80 mm dia
Supply and Fixing in replacement MCCB TPN 400 Amps , 415 Volts, 36 KA ,4 POLE, Ics=100% Icu ,overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TPN 250 Amps , 415 Volts, 25 KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit adjustable type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TPN 200 Amps , 415 Volts, 25 KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit adjustable type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TPN 160 Amps , 415 Volts, 16 KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit fixed type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TPN 100 Amps , 415 Volts, 16KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit fixed type incl complete connection with suisuitable spreaders all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TP 400 Amps , 415 Volts, 36 KA ,3 POLE, Ics=100% Icu ,overload adjustable short circuit adjustable type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TP 250 Amps , 415 Volts, 25 KA ,3 POLE, Ics=100% Icu , overload adjustable short circuit adjustable type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge. Make Legrend
Supply and Fixing in replacement MCCB TP 200 Amps , 415 Volts, 25 KA ,3 POLE, Ics=100% Icu , overload adjustable short circuit adjustable type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TP 160 Amps , 415 Volts, 16 KA ,3 POLE, Ics=100% Icu , overload adjustable short circuit fixed type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge.
Supply and Fixing in replacement MCCB TP 100 Amps , 415 Volts, 16 KA ,3 POLE, Ics=100% Icu , overload adjustable short circuit fixed type incl complete connection with suitable spreaders all as per direction of Engr-in-Charge.
M&L for detecting of faullt in cable of any type with fault locator equipment which is capable to supply as per cable of serviceable to cable. Note :- (a) The fault which is detected through cable fault locater will only be paid under this item (b) Charges of cable fault locator and DG set including transportation charges deemed to be included in the quoted rate. (c ) Earth fault locator will be provided by the contractor for even single fault and no dealy on this account will be acceptable otherwise penality will be levied Rs 500/- per day. (d) Necessary testing of cable after making joint will be deemed to be including in the cost of relevent item. However necessary earth work cable cutting making Joint will be paid under relevant item.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4/5 line as per IS complete as per direction of Engr-in-Charge.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 3 line as per IS complete as per direction of Engr-in-Charge.
Removing LT over head conductor from insulator where ever required and restreeching the same without any kink/bend up to premissible sag, binding it on insulator by means of binding wire including fixing line seperator at 3 places where required and directedand tessting LT over head line on completion and all as specified and directed(Each Run of line conductor shall be measured & paid for separately. Seperator shall be paid seperately)
Taking down unsv existing change over & Supply, fixing in replacement off load changeover switches 4 pole 100 Amps , 415 volts , with enclosure complete all as per direction of Engr-in-charge. Make: Hager/Legrand/ Schneider/IndoAsian
Taking down unsv existing change overSupply and fixing in replacement off load changeover switches 4 pole 200 Amps , 415 volts , with enclosure complete all as per direction of Engr-in-charge. Make: Hager/Legrand/ Schneider/IndoAsian
Material and labour for fixing in replacement of stainless steel nuts, bolts, washers of any size required at site incl dismantling old rusted nuts bolts as per direction of Engineer-in-Charge.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 50 sqmm incl dismantling old thimbles of any type.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185 sqmm incl dismantling old thimbles of any type.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm incl dismantling old thimbles of any type.
M & L for cutting of road/PCC footpath/hard standing/interlocking tiles work including excavation for laying cable/pipe and making good surfaces as per existing specification all as specified.
Material and labour for shifting heavy items / excavating / cleaning areas / clearing site by providing crane/hydra/excavators/tractors/trolley etc as required at site complete, all as specified and as directed.
M&L for Chemical spray (DC> 2-26 having container 415ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricates, displaces and seals out moisture release rusted mechanism cleanse etc.
M& L for painting to LT panel board/LT feeder pillar box up to 0.6x.06.x.5 M indoor/out door type of size inner shell & outer shell including angle iron frame by applying two coats of sunthetic enamelled paint over a red oxide primer after cleaning of panel board inner shell & outer shell by means of rubbing by sand paper griding and removing rusted and corrded particles cleaning with cloths including reparing smooth surface for painting all as specified and as directed.
All as per item No 62 here-in before but of size up to 1.0 x.9x.5 M all as specified
All as per item No 62 here-in before but of size up to 1.2x.9x.5 M all as specified
All as per item No 62 here-in before but of size up to 2.0 x1.2 x.5 M all as specified
M & L for maintance of LT feeder pillar /LT panel board any type and size indoor/outdoor by dismandling opening and taking down of all incoming and outgoing cables,cutting burnt edge of the cable what ever is required ,providing thimble lugs of suitable required for different size of cable including taking out loop of the cables, cleaning of bus bars by menas of rubbing grinding etc and providing PVC sleeves of suitable rating on bus bars maintaing colour code (RYB & N) including replacement of bolts nuts & wanshers and reconnecting the all incoming and outgoing connections and testing of panles on full load all as specified and as directed.
Labour only for welding of existing unserviceable door hinges of LT feeder pillar/LT panel board indoor/out door type of different size panels at different size panels at different locations including adjusting the door for smooth opening and closing of the panel boards all as specified and as directed
Material & Labour for surface cleaning of steel tubular poles LT 9 mtrs long including removing rusted particles and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms, bracing, supports, clamps, eye hooks, security light bracket, clamp etc and providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the reparing of coping with cement / PCC.
Material & Labour for cement based paint for PCC pole 9 mtr long including black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms, bracing, supports, clamps, eye hooks, security light bracket, clamp etc incl repairing and painting on coping with cement base white paint complete all as directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the reparing of coping with cement / PCC.
Supply and fixing in replacement garding wire Cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia under overhead ACSR conductor to provide protection against conductor broken complete all as per direction of Engr-in-Charge. Note: (i) Cost of cross arms , nut , bolts, clamps etc are measured and paid separately.
Material & labour for repairing existing earthing any type incl making & cleaning of earth pit, repair of pits, fixing of new funel , pit cover, painting on pit with cement base white paint complete all as per direction of Engr-in-charge. Note: (i) Cost of funel, pit cover, cement work, PCC work and painting etc incl is quoted rate.
Supply and fixing of Earth continuity strip or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 24x4 mm GI strip complete all as directed by Engr-in-Charge.
M & L for spraying chemical on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge
Note for item No 74 (i) The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel drawing shall be got approved before placing of order from Engr-in-Charge/GE. (iv)The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panles through gland. (vi)Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate.
Supply, fabricate, erect , connect, test and commissoning of factory made, CPRI approved,cubical type, outdoor type LT panal board, totally enclosed , dust, weather and vermin proof 1100 Volt grade , 50HZ AC supply made out by 3.15mm thick CRCA sheet steel for load bearing and 2 mm thick for non load bearing, fully compartmentalised, with IP 65 protection all as per conferming to IS 2417 of 1962 complete including the following accessories housed in all as specified and as directed. (a) 4 Nos bus bar of equal size made out of copper strip of suitable size with PVC insulated colour coded heat shrinkabale type sleeves, of rating 400 Amps, mounted on non cracking resin type insulators - 01 Job (b) MCCB, 4 pole, 415 volts, 36 kA, with Fixed Thermal Magnetic release, 250 Amps, - 01 No (Incoming). (c) Interconnection of MCCBs to Busbar with copper strip of suitable size with PVC insulated colour coaded heat shrinkable type sleeves - 1 Job (d) MCCB, 4 pole, 415 volts, 25 kA, with fixed thermal magnetic release, Ics = 100% Icu, 63 Amps, -06 Nos (Outgoing). (e) Protection fuses HRC type of suitable capacity for Panel wiring - 01 Job (f) Digital type Ammeter with sellector switch and Set of CTs - 01 Set (g) Digital type volt meter with sellector switch '0' to '500 Volts - 01 No (h) Indication lamps R, Y & B - 01 Set (j) Provisioning of copper tinned cable glands for incoming & Outgoing cables. - 01 Job (k) Interconnection of metering equipment with PVC insulated unsheathed, single core cables 1100 volts grade of suitable size - 01 Job
Notes- (i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel drawing shall be got approved before placing of order from Engr-in-Charge/GE. (iv)The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panles through gland. (vi)Cost of marking description and matter on the front door as specified and directed by Engr-in-Charge is incl in quoted rate.
M & L for fabrication and replacement of old unserviceable out shell/inner shell cover factory made suitable for different size of panels.feeder pilllar boxes according to site and welding of hinges with outer/inner shell. Provision of locking PVC head bolts for outr/inner shell cover as required at site all as specifieid and as directed.
Material & Labour for Aricircuit Breaker, fixed type, spring operated, mannualy TPN, 4 Pole, 800 Amps, 415 Volt with Thermal magnetic release,(O/L, S/C, E/F protection & confirming to IEC - 60947-2 &3rated breacking capacity / making capacity 50 KA short time current all as specified and directed
Material & Labour for Aricircuit Breaker, fixed type, spring operated, mannualy TP, 3Pole, 800 Amps, 415 Volt with Thermal magnetic release,(O/L, S/C, E/F protection & confirming to IEC - 60947-2 &rated breaking capacity / making capacity 50 KA short time current all as specified and directed
Supply and installation of all in one integrated solar street light 25 Watt compact,aesthetic ecco friendly and modern integrated solar street in extruded aluminium housing with high efficiency mono crystaline silicon photo voltaic panel,high efficency SMD LED 6500K having secondary lens optic for street light distribution ,high performance lithium battery ,MPPT charge controller and intelligent controlmodule/sensor with higher reliability long service life,incl GI pipe not less than 63mm dia upto 4 mtr height for mounting of solar lights,suitable for easy and quick installation pcc 1: 3: 6 type C1(using 20mm stone aggregate) complete all as specified an directed.
Supply and fixing in repair/replacement of Battery 2V,100Ah dry cell type for breaker relays of 66/11 KV HT SF6 & VCBs. Including reparing stand rack for batteries and fixing in switch room floor all as specified and directed by Engr-in-charge
Supply & fixing in replacement of Integral LED Flood light Luminaries 150 Watts consisting of suitable number of LEDs and mounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens, IP 66 protection suitable for mast light mounting, 5700K, LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV , Confirm the tests from auth labs : LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge.
Supply installation testing and commissioning of HT 11KV junction box outdoor type (IP 55) made out of 3.15 mm CRCA sheet welded to angle iron 40x 40x6 mm on all sides slanted slopes with 15 cm projection on all sides with openable shutter on both sides having locking arrangements,totally enclosed, weather proof spray painted internally and externally with two coats of red oxide primer suitable for 11 KV confirming to IP-54, 3 Nos aluminium busbar of capacity 400 amps mounted on HT insulator connected to two No independent earthing lead ( width of the panel not less than 1.00 Mtr) including legs of panel 90 cm height made up of angle iron 50x50x 6mm grouted on PCC 1:2:4 upto 30 cm complete all as specified and directed.
Material and labour for vibratory compactive, precast cement concrete rubber moulded, coloured ( except grey colour), interlocking designer paver blocks in Milano shape, comfirming to IS-15658-2006 of 60 mm thickness, M-35 grade, as in path, harding standing, etc laid over and including 25 mm compacted sand cushioning, including 75 mm thick PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate including surface excavation over area n. exc. 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil and removing excavated soil exc. 50 mtr but n. exc. 250 mtr, complete all as specified and directed by Engineer-in-charge.
Material and labour for preperation of old plastered or unplastered surfaces of walls, pillars cornices etc by brooming down with steel wire brushing,scraping down smoke soot, moulds, moss and effloroscent salts, trading oil and greasy spots etc. and applying two coats of white wash etc complete all as specified and directed.
Note:- Amount of credit of Rs 121578.00 for retrieved materials is mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender.
Mohinder Pal and Sons
Raman Electric Trading Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .