| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.4 LAccepted-AOC | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹8.6 L+₹2.2 L (34.7%)Rejected-AOC | L2 | Rejected-AOC Being not lowest |
Tender Value
Refer Docs
EMD Value
₹12,800
Closing Date
9 Dec 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
HQ CWE (Hills) Dehradun
HQ CWE (Hills) Dehradun
SPECIALREPAIR/REPLACEMENT OF 250 KVA TRANSFORMERNEAR SANTOSHO MATA MANDIR LANSDOWNE
2020_MES_394965_1
87036/LDN/E8
Open Tender
Electrical and Maintenance Works
Item Rate
GE Lansdowne
Class E category bii
7 documents required · 7 mandatory
₹500
Yes
GE Lansdowne
₹12,800
Yes
28 Dec 2020
12 Nov 2020
11 Dec 2020
12 Nov 2020
9 Dec 2020
26 Nov 2020
60 days
Amount
Supply, install, testing and commissioning distribution transformer 11/0.433 KV outdoor type plinth mounted, copper wound AC 3 Phse, 50 Hz oil immersed naturally cooled delta connected on primary side (11 KV HV side) & star connected on secondary side (433 V LV side) in accordance with vector group Dyn-11 with neutral brought out on secondary side with tapping at ± 2.5% ±5% ±7.5% off load tap changer gear in steps of 2.5% continous rating of cap 250 KVA including initial oil fill to appropriate level & all standard fitting all as per IS 1180 Pt 2014 and IS-2026 mounted on and incl platform of size 2.5 Mx2.5Mx1.5M high (outer dimention) built with 150 mm thick PCC 1:5:10 type E2 foundation extending 150 mm on both sides of wall, 350 mm thick of brick masonary built in CM 1:6, 450 mm below GL & 950 mm above GL duly plastered in CM 1:4 on exposed faces & finishing in same mortar as the work proceeds in faces in contact with soil /floor of 50 mm PCC 1:2:4 type B-1 laid in bays over 100 mm thick broke stne boulders hardcore over approved earth filling complete all as specified and directed. The unit rate for each transformer includes the cost of following accessories/fittings :-
(a) Rating and terminal marking plates, non detachable (b) Earthing terminals with lugs-02 Nos (c) Lifting lugs for main tank and top cover (d) Thermometer pocket with cap along with dial type thermometer-01 No (e) Externally hand operated OFF circuit tap, changing device with locking arrangement. (f) Oil conservator tank with fitting hole, drain plug, prismatic oil level gauge. (g) Silica gel dehydrating breather charged with silica gel. (h) Top filter valve with plug (j) Drain valve with plug (k) Air Vent. (l) Explosion vent. (m) Earthing terminals with lugs-02 Nos (n) Lifting hooks. (o) Unidirectional reversible roller-04 Nos. (p) HV bushing-03 Nos. (q) LV bushing-04 Nos. (r) Radiators. (s) Arcing horn on HT side-03 Nos. (t) Terminal connection on the HV bushing. (u) Additional neutral separately brought out side, LV cable end box with bush insulator for neutral earthing. (v) First fill of Transformer oil upto appropriate level. (w) Base channel 100x50 mm, 460 mm long with holes to make them suitable for fixing on a platform or plinth . Note : 1. The Trasformer shall be ISI marked with min energy efficiency level 3 as per IS 1180 (Pt-I) : 2014. 2. Any other accessories/work which is required to be provided as per relivent IS but not specified above will be provided by the firm without any extra cost to the Department MAKE : BHEL/ABB/AREVA/INDOTECH/SIEMENS/VOLT AMP/BHARAT BIJILEE /Rajsthan Transformer/ITE Gurgaon
Disconnecting incoming and outgoing connection of existing 250KVA Transformer and shifting and deposting to MES EM store yard including demolition of existing PCC platform and removing debris etc from site complete all as specified and as directed
S&F galvanised strip 32x6mm burried in ground complete all as specified and as directed
Earthing complete with galvanised steel earth plate eletrode 600 x 600 x 6.0 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected by 32 x 6 mm GI strip as earth lead by means of brass nuts and bolt, thimbles, check nuts, washers including concrete chamber of PCC 1:3:6 type c-1 using 20 mm graded stone aggregate, with fair finish, internal surface of concrete chamber shall be given internal dia 300mm x 300mm, 15mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320 x 320 x 80 mm size (1:2:4) Type B1 using 20 mm graded stone aggregate, adequate quantity of common salt, charcoal etc all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including and provision of GI strip upto 7.5 mtr long with 40 mm dia light grade GI pipe protection and watering pipe of GI 20 mm bore, medium grade, including all excavation and earth work and connecting the earthing strip to an earthing test point/panel including testing on completion complete all as specified and directed by Engr-in-Charge. (i) RCC pit cover shall be precast of RCC (1:2:4) type B1, 80 mm thick reinforced with XPM weighting not less than 4 Kg/Sqm in lieu of CI cover. (ii) Cost of additional GI strip more than 7.5 meter will be measured and paid seperately under relevant item.
M/S BANSAL ELECTRIC WORKS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .