Executive Engineer Dinajpur Division
Executive Engineer Dinajpur Division N S Road Mohanbati, 733134
Internal electrification works office room weigh bridge room and security room and pump panel and supply installation pump motor set for proposed 15 TPD Municipal Waste Processing Plant under SWM project within Dalkhola Municipality
2026_MAD_983578_1
08/EE/DJP/MED/2025-26 (1stCall)
Open Tender
ELECTRICAL WORKS ORG
Percentage
Dalkhola
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹37,050
Yes
9 Jul 2026
5 Jan 2026
27 Jan 2026
8 Jan 2026
24 Jan 2026
8 Jan 2026
Internal Electrification work for Structural plant and Compound of Proposed 15 TPD Municipal Waste Processing Plant under SWM Project within Dalkhola Municipality (Dist-Uttar Dinajpur)
Supply ,Installation and commissioning of L.T. Floor mounted Service cum Distribution Pillar Box made of suitable size [1372mm x 914mm x 607 mm depth as required made by 3.15 mm thick on top & 2.5 mm thick on body by CRCA sheet providing of 3 – phase aluminium bus-bar system and heavy gauge iron angle / flat channel to be used as and where required and necessary making requisite compartment to be provided in it with cable allay system for outgoing cables and including supplying and fixing of the following accessories to be provided as per direction and as per requirement and making suitable size of copper wires and cables for inter-connection and as per direction of E.I.C. Legs of the P.B. will be 900 mm. in length by made upto of ( 40 x 40 x 5 mm ) M.S.angle with suitable base plate . Legs of the P.B. will be erected at 300 mm. below the G.L. with cement concreate ( 6:3:1). Rest portion covered by 5"' brick wall with plastering & net cement & bottom portion filled by silver sand . [ Both side opening system incl. locking arrangement ] [ The panel board should be painted with powder coated paint grey colour including hylam sheet , heat sink sleeves , bus-bar , isolator , rubber gasket and lifting lugs etc. ] { Mainly Service Panel cum Distribution P.B.}
1. IN COMING :- 1.a. 415 V , 250 amp. FP,4 pole on load front operated Change Over switch with sheet steel enclosure on angle iron frame as per G.S. (1 no) [ Havells make ]
1.b. 415 V, 250 A. TPN.SFU with sheet steel enclosure on flat/angle iron frame incl. S&F 3 no's DIN type HRC fuse .-- (2 no's - Service side & incomming side ) Havells make. ( 250 Amps main Switch has been considered according to the unit basis load consumption ) [ Havells make ]
1.c. 500 v, 315 A . Vertical type Al. Bar with 4 no’s Al. Bar ( 4 x 50 mmx 10 mm.size ) mounted on DMC Isolator as per direction of EIC [ Av. Length 0.85 mts. Approx ]- 1 set.
1.f. R/Y/B indicatin LED lamp [ L&T / ISI make ] --1 item.
OUT GOING :-
1.g. 415 V, 200 A.TPN.SFU.with sheet steel enclosure on flat iron frame with S & F 3 no’s DIN type HRC fuse as perrating & G.S.... [ For Mini Panel board ------ 4 sets ] [HAVELLS make]( Inside shed at the plants ) For each Unit basis .[2 Units - Wet & Dry Waste ]
1.h. 415 V, TPN SFU, 63 A, with sheet steel enclosure on flat/ angle iron frame on structural frame with nuts, bolts etc. incl. S&F 3 no’s DIN type HRC fuse as per G.S.. [ For Office room HTPN + Fire Pump & Spare] ----03 no's [HAVELLS]
1.i. 240 V, 32 A. TPN.MCB, breaking capacity 10 KA & C curve on Din Rail with sheet steel enclosure type Switch for Spare. ---1 no [HAVELLS make ]
1.j. E.I Danger Board [ 20 cm x 30 cm ] ---1 no
1.k.Cubical Service Panel Board .Size - 1372 x 914x x 607 mm.)
1.L. Inter-connection charges with necy. Cables & wires with socketing & finishing as require and locking arrangement.
Mini Panel Board :-15 TPD Supply ,Installation Industrial type L.T. Floor cum Wall mounting M.S. Panel board made of suitable size [1500mm x 1200mm ] and heavy gauge iron angle / flat channel(40 x 40 x 6 mm) & (25x3mm) to be and fixing of the following accessories to be provided as per direction and as per requirement and making suitable size of copper wires and cables for inter-connection and as per direction of E.I.C
2.a. S & F 415 V,200 A.TPN SFU, with sheet steel enclosure on flat iron frame on structural frame with nuts, bolts etc. incl. S&F 3 no’s DIN type HRC fuse as per G.S.. [ For Mini Panel board ------ 1 set ] (Havells make)( Inside shed at Both End )
2.b. 500 v, 200 A . Al. Bar with 4 no’s Al. Bar ( 4 x 25 mmx 5 mm.size ) mounted on DMC Isolator as per direction of EIC [ Av. Length 0.85 mts. Approx ] (1 set)
2.c. S & F double door 2 + 6 way MCB D.B with IP- 42/43 protection incl. 40 A .DP.MCB isolator and 6 no's 10 A. MCB to be fitted on Hylam board incl. necy. interconnection with suitable size of copper wires and neutral link & provision for earting attachment as per G.S. ( Havell's make ) -- 1set [ 1073 + 1008 + 208 = 2289.00 ]
2.d. S & F 240 V, 20 A , Plug & Socket single door MCB protected board fixed on MS Sheet. With earting arrangement. ----2 nos. [Provision for Per Mini Panel 2 sets of Plug Board ]
2.e. S & F E.I. Danger Board [ Size – 20 cm x 30 cm ] –1 no
2.h. R/Y/B indicatin LED lamp [ L&T make ] (1 item)
2.j. Fabrication cost by CRCA sheet box with front side 3 mm. thick Hylam board [ 4 sq.ft.]with 8 no's Pin type Cu.stud [ 2 sets ]for flexible cable connection with 2 no's 40 A FP.MCB control cut-out / Isolator for the stud connection. [ Havells make ]
2.k.Industrial Panel fabrication cost + Inter-connection + Painting + Transportation etc.
Supply & Fixing double door Horizontal TPN . MCB . D.B. for MCCB incommer with IP-42/43 protection , on angle iron frame on wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per G.S. [ 4 - way , Havell's ] For Office Room ( FP Isolator 40A Isolator + 12 no's SP.MCB ) [ 2419 + 676 + 2016 = 5111.00]
S & F 415 V, TPN SFU, 32 A, with sheet steel enclosure on angle iron frame on wall with nuts, bolts etc. incl. S&F 3 no’s DIN type HRC fuse as per G.S.. [ For Weighbridge control room ] ----01 no. [ Havells make ]
S & Fixing 240 volt , 200 watt Indoor Type LED light fittings for Structural shade [ height of the shade – 34 ft.approx ] with suitable clamping arrangement for holding the fittings necy. Connection by suitable size copper wire & incl. earthing attachment as per direction of E.I.C. Analysis enclosed [ Philips / Bajaj Make ] – Green Prime GEN-2 Highbays - BY616p-LED 200S-5700 NB PSU GR & NUKE Bihnk 200 W WH NB TG SD
S & Fixing 240 volt , 150 watt Indoor Type LED light fittings for Structural shade [ height of the shade – 34 ft.approx ] with suitable clamping arrangement for holding the fittings with necy. Connection by suitable size copper wire & incl. earthing attachment as per direction of E.I.C. Analysis Enclosed [ Philips / Bajaj Make ] – Green Prime GEN-2 Highbays - BY615P-LED 150S-5700 NB PSU GR & NUKE Bihnk 150 W WH NB TG SD
Supply of 240 volt , 120 watt watt Outdoor Street LED light fittings fitted on outside Vertical Structure frame and also fitted on G.I. Pipe bracket and necy. connection by suitable size copper wire & incl. earthing attachment as per direction of E.I.C.Analysis Enclosed [ Philips / Bajaj Make ] – Smart Bright - BRP033LED 120 CW SLR PSU SPD. & EDGE NXT Enxt P 144L WH CRTG SD 120 W 5700K
Supply of 240 volt , 90 watt Outdoor Street LED light fittings fitted on outside the wall of the building and also fitted on G.I. Pipe bracket and necy. connection by suitable size copper wire & incl. earthling attachment as per direction of E.I.C. Analysis Enclosed [ Philips / Bajaj Make – Smart Bright Essential BRP033 LED 90 CW SLR PSU SPD & EDGE NXT Enxt P 108L WH CRTG SD 90 W 5700K
S & Fixing 240 volt , 185/200 watt LED Flood light luminaries fittings fitted on outside Vertical Structure frame by G.I. clamp and necy. connection by suitable size copper wire & incl. earthing attachment as per direction of E.I.C. [ Bajaj Make GLEAM GRAND - Gleam-G F 240L WH NB AS PC SD 200W
S & F G.I water proof looping cable /wire box having hinged GI top cover having 4 mm. thick with rubber gasket lining , railway type mechanical locking arrangement ,earthing terminals with lugetc. For 3x 2.5 sq.mm. PVC insulated copper wire through 20 mm. PVC.Rigid pipe comprising of one 240 V Fuse unit ,one NL on porcelain insulator etc. and housing the same inside the wall and necy. net cement finish and necy. connection as per G.S. [ [ 1 no for Security Room + Weigh Bridge Room + 1 no for Gate pillar for Glow sign Board and 2 no's for Office Room. ] Size – 200 x 150 x 100 mm
Supplying of 1.1 KV. Grade XLPE/ PVC/AL cable [ Make – Polycab/ Havells / Gloster ] of the following sizes cable :-
a. 1.1 KV. Grade 3.5 core 70 sq.mm PVC/Al. armoured cable. [ From Service Pilier Box to Mini Piller Box ]
b. 1.1 KV. Grade 2 core 6 sq.mm PVC/Al. armoured cable [ From Service Piller Box to Office Building , security Room & Weigh Bridge + Street Light etc. ]
b. 1.1 KV. Grade 4 c X16 sq.m PVC/AI,armoured cable for Pump panel Board.
Laying of one No. cable above 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.
(a) 3.5 X 70 sq.mm
(b) 2 X 6 sqmm
(b) 4 X16 sqmm
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring etc. incl S & F cable sockets, insulateds, & soldering materials etc. & necy connection as per G.S [ As per IS Code ]
(a) 3.5 X 70 sqmm
(b) 2 X 6 sqmm
(b) 4 X 16 sqmm
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required (a) 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC
Fixing outdoor type LED light fittings on structural frame and pole including S&F 40 mm dia x 1.68 mts. long GI Pipe (ISI-Medium) bracket with 40 mmx10 mm thick, MS clamp etc. and providing wiring with 2x1/1.40 PVC insulated and sheathed copper wire (single core) from loop box at the base of pole to light fiting through pole & bracket (without control switch) including making connections & painting
S & F sheet metal loop box/inspection box (16 SWG) of size (225 X 200 X 65 mm) with bakelite top over & fitted on structural frame & below steel structure with clamping system incl S & F 2 nos copper bar for loop in, loop out system & making earthing attachment & painting as per direction of EIC
S & F Acrylic letter scripted in English/Bengali size & matter of letter as per approved drawing by EIC ,font side of the letter to be made 6 mm thick imported (white - 0.40) uv stabilized excellent to self display,Make-Acast, Mitsubishi, all letter will be raised minimum 2" to be fixed by special type of sollution (total sqm of each letter to be measured based on its front surface area) ,incl. 26 gauge galvanised iron sheet for back panel with one coating of white paint.
Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
Connecting the equipments to earth busbar including S & F 8 SWG. G.I.earth (Hot Dip) wire on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6 mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. With 25x25x3mm angle iron support 200x50x1.25mm (18SWG)
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 50 mm dia.
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dx 80 mm long GI bolts, double nuts, double washers incl. S &F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:ISI-Medium GI pipe
Internal Electrification& Pump Operational F.P.Box work for Structural plant and compound of Proposed 15-TPD Municipal Waste Processing Plant under S.W.M. Project within Kaliagunj Municipality Electrification works :- [ Office Room , Lab , Weighbridge Control Rooms and Security Rooms ]
Distribution wiring in 22/0.3 ( 1.5 sq.mm ) single core stranded FR PVC insulated & unsheathed single core stranded copper wire ( Brand approved by EIC ) in 19 mm. bore ,3 mm. thick polythine pipe ( for horizontal & vertical run in wall and ceiling portion through prelaid polythine pipe ) complete with all accessories embedded in wall to light / fan / call bell points with modular type switch ( Brand approved by EIC ) fixed on Modular G.I.swich board with top cover plate flushed in wall incl. mending good the damages to the original finish . [ 2 x 22/0.3 (Ph. &N ) and 16 SWG GI as ECC . (Average Run -6 mt.) --- [PWD. Sch. P- E-20 / I- 2 ]
Distribution wiring in 22/0.3 ( 1.5 sq.mm ) single core stranded FR PVC insulated & unsheathed single core stranded copper wire ( Brand approved by EIC ) in 19 mm. bore ,3 mm. thick polythine pipe complete with all accessories embedded in wall to 240 v , 6 A , 5 pin plug point incl. S&F 240 v , 6 A . 5 Pin Modular type plug socket & Modular type switch Brand approved by EIC ) incl. S & F earth continuity wire , fixed on 4 Module G.I.switch Board with ¾ Module top cover plate flushed in wall incl. mending good the damages to original finish . 2x22/0.3 ( Ph& N ) and 1 x 22/0.3 as ECC . a) On Board –
b) Average Run – 3.0 mts. ---[PWD. P – E-20 / I – 3
S & F Sheet metal Main switch on flat iron frame on wall ( Havells Make ) [ For Security & Weigh Bridge Room ] a. 240 V, 15/16 A . D.P. with fuse on L &N.[ S/R ]
b. 240 V , 32 A . D.P. with fuse on L &N .[ O.R & WB --- [ PWD. Sch .P – D-1 / I – 1a. ]
S & F double door SPN.MCB ( 2 + 6 ) way. Distribution Board Enclosure with IP – 42/43 protections, concealed in wall after cutting the wall & mending good the damages to original finish include. Interconnection charges with suitable size of copper wire and neutral link & provision for earthing attachment. [ Havells make – DHDPSNODRW06 ] – [ PWD. Sch. P – D-10 / I- 13 ] ( Office Building )
S & F 240 / 415 V, MCB, Isolator on Din rail of existing Db.s and necy. connection – [ PWD. Sch. P- 5/6 / I – 6 ] a. 40A.D.P. Isolator.SPN.DB.(6-way-SPN) ( Havell’s make )
S &Fixing 240 V / 415 Volt MCB of Breaking capacity 10kA & characteristics on din rail of existing DB’s and necessary connection 6 – 32 a . SP. MCB .+ HTPN ( Havells make ) [PWD.Sch. P- D-6 / I – 7 ]( 12 no’s for HTPN + 6 no’s for 6 – way. SPN )
S & Delivery LED batten Tube Light fittings complete ( Philips make. Model – TMC501P 1 x T –LED 2 2 watt. P3241) [ I & WD –P- 113 / I – 5.3 F- 22 ]
S & F 240 V,18 W decorative LED Surface Mounted Sleek down Light with AL die –cast body and diffuser. (Make –Bajaj) Cat no:- DOVEE Down Light (Bajaj Make)BZSLO nxt 18L LED WH.S.D. [ Fixing – Rs.56.00. PWD. P- C-2 / I -13 ]Filips – Page – 45 ( Rs.1950.00 x 0.847= Rs. 1651.65x 0.8 = Rs.1321.32 + Rs. 59.92 F.C = Rs.1381.24
Fixing only LED Tube light fittings complete with all accessories directly on wall / ceiling as per direction of EIC. – [ PWD. Sch. P – C- / I – 14 a. ]
S & Delivery 12 watt LED bulb ( Philips/ Havells /Crompton ] make . Model – New Adore 12 Watt, B-22/ E- 27 CDL Ball Lamp ) as per direction of EIC . [ I & WD – P- 114 /I – 5.. F- 26.1 ]
Fixing only 12 watt LED lamp at Holder . [P.W.D - P- C-2 / I – 11 ]
S & Delivery of 240 V, A.C. Ceiling fan of Crompton/ Havells/ Bajaj make of 1200 mm. sweep. Model – Cool Breeze, Brown colour complete set. [ UD & MA. Sch. P- 23 / I – 70 ]
Fixing only ceiling fan complete with blades, canopy, fork. rubber bush etc. incl. S& f connecting wire for down rod up to 30 cm. incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sq.mm. flexible copper wire. – [ P.W.D -P – C-3 / I – 21 a. ]
S & fixing Modular type fan regulator [2 - Module type] Brand approved by EIC , on existing sheet metal switch board incl. making necy. Connection etc. as per G.S. [ P.W.D - P- E-18 / I – 10 ]
S & delivery 250 V, Metal Exhaust Fan -9” ( 225 mm ) sweep single phase complete with all accessories incl. louver shutter . [ Model :- Crompton / Havells / Bajaj -Trans Air] [ UD & MA – P- 14 / I - 6 ]
Fixing only exhaust fan after making hole in wall and mending good the damages and net cement finish etc. as practicable as possible and providing necy. Length of PVC insulated copper wire and making connection of 9” ( 225 mm ) sweep Ex. Fan. – [P.W.D.- P- C-4 / I – 28 b. ]
S & Fixing 240V, 6 A , 3 – Pin Modular type plug socket ( Brand approved by EIC ) with 6 A, Modular type switch , without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S & switch board and cover plate and making necy. connections with PVC, Cu wire and earth continuity wire as per G.S. [ PWD. Sch. P- E-18 / I – 9.a ]
Pump P.B :- [ Water supply ] a. Supply & Installation of Feeder Pillar of size :- 1200 mm x 600 mm x 450 mm outdoor type , stand mounting , dust and vermin proof with IP -55 protection . The panel shall be made of 14 SWG [ 2 mm. thick ] Cold Rolled Close Annealed ( CRCA ) Sheet Steel , shall have powder coated finish to required shade after pretreatment and standard enamel paint . Cable entry shall be the bottom and through a detachable gland plate. Stand for mounting shall be made of 50 mm x 50 mm x 4 mm. M.S. angle. Feeder pillar shall have Pad –locking arrangement. [ Capacity 3 H.P – 10 H.P ) [ Normal water supply & Fire system -Operation Pillar Box ]
In-commer :- 415 Volt ,63 A TPN.S.S . Enclosure type (Havells make ) -1 no. [ Schedule rates ] (Sch. D-1 / I – 1.b. )
Outgoing :- 415 Volt, 63 amps. Al. 4 –bars , BBC etc. as per schedule –1 set. ( D-12/I-19b )
415 Volt, 40A, Pole MCB.Isolator(Havells make)-1 no(D-6/I-6)
415 volt, 3. Phase DOL compact Starter unit complete set. ( WRIDD/CE. Approved Rate )
240 volt, 32 A. D.P.. Main switch [ Havells make] ( Schedule D- 1 / I – 1 ) Spare
Danger Board [ Size – 15 cm x 10 cm ] [ Sch. – D-13 / I – 21.a ]
• Fabrication Cost.( UD & MA – P- 7 /I-39 )complete work.
Inter-Connection charges
Distribution wiring in 1.1 Kv. Grade single core stranded Fr. PVC insulated & unsheathed copper wire ( Brand approved by EIC ) in 20 mm. dia. PVC heavy gauge polythine ( approved make ) cutting channel of 40 mm x 40 mm size on wall and mending good the damages incl. necy. nails as required as per G.S. ( from PBDB to A.C Power Point ) [ PWD. Schedule – P- E-2 ,9. / I -3,1/s ,v, ]
A. 2 x 56/ 0.3 ( 4 Sq.mm ) + 1 x 36/ 0.3 (2.5 sq.mm ) ECC .[ For A.C ]
B. 2 x 36 / 0.3 ( 2.5 Sq.mm ) + 1 x 22/0.3 (1.5 sq.mm ) ECC.
Supply, installation, testing & commissioning of wall mounted type 3 - Star , Non-Inverter type 1.5 TR Split AC unit complete with all accessories, mounting brackets ,remote controller pipe, drain pipe, etc complete work as per direction of EIC.(Make- Voltas ) [ I & WD – P- 118 -/ I – 5.3 . H- 8.0.3 ] (Office room & Lab)
S& F 240V ,25 A. Modular type Starter ( Brand approved by EIC )with 25 A Modular Switch type DP MCB (C -curve) and 4 Module GI Module type Switch board with 4 Module top cover plate flushed in wall incl. S&F Switch board and cover plate and making connection with PVC.CU wire and earth continuity wire etc.(Future Provision one No) [PWD . P- E- 19/ I-18]
S & F 240 v, A.C. Buzzer ( Anchor ) on H.W. board incl. S & F H.W.Board. [ P.W.D – P- D-13 / I – 20.b.]
Earthing with 50 mm. dia. ISI make – Medium Quality GI pipe 3.64 mm. thick x 3.04 mts. Long and 1 x 4 SWG GI (Hot Dip ) wire ( 4 mts. long ) ,13 mm dia x 80 mm. long G.I. bolts, double nuts , double washers incl. S & F 15 mm. dia. GI pipe protraction ( 1 mt . long ) to be fitted with bitumen partly under the ground level and partly above the ground level driven to an average depth of 3.65 mts. Below the G.L. as per G.S. [ P.W.D. Sch. P- G-I / Item – 2.a ]
Installation of Pump-Motor Set of Proposed 26 TPD Municipal Fresh Waste Processing Plant under S.W.M. Project within Kaliagunj Municipality. [ Dist :- Uttar Dinajpur . Pump Installation & Fire support system
Supply , fitting & fixing G.I. Pipes of “TATA – make “ with all necessary accessories , specials viz. socket , bend , tee, elbow, union, cross , nipple , long screw , reducing socket , short piece etc. fitted with holder bats clamps , well cover including cutting pipes , making threads , fitting , fixing as required with jointing materials and two coats of painting with approved paint in any position above ground level. [ For Vertical Column pipes & upto header]--- ( 50 mm. dia. Medium Quality ) [ PWD . sch. Page – 2 / I – 1. F. ]
Supply & fixing 50 mm. dia. C.I. double flanged Swing Type Non- return valve generally conforming to IS:5312 of approved Brand /ISI / [ PN- 16 Rating ] complete with Bronze body & wedge Stainless Steel spindle , gland packing , rubber gasket etc. [ Analysis Enclosed ] CPWD – P-787 , Code - 4265
Supply & fitting and fixing 50 mm. dia. gunmetal wheel valve of approved Brand/ ISI make.[ Tested- 21kg/sq.cm.] [ For water delivery lines, Fire line, Office Building & wash out line. [PWD. sch. Page -5 / I – 5 ]
Supply & fitting and fixing 25 mm. dia. gunmetal wheel valve of approved Brand/ ISI make.[ Tested- 21kg/sq.cm.] [PWD. sch. Page -5 / I – 5 ]
Supply & Installation of Three Phase 415 v, 3 H.P. (2.2 Kw) 7 stage submersible pump-motor set suitable for 150 mm. dia. bore well having Head--33 mts. discharge 175 lpm . The discharge outlet size will be 65/50 mm. dia. ( Make- KSB Cora -18 C /07 G +UMAI 100-2.2/22 ) or ( Make – Bhagirathi Ganga – 6BGR -7 Model) or ( Make - Crompton – 100 W7RQ3TP-65 ) [ Analysis enclosed ]
Supply & laying submersible cable for pump-motor set. Size 3 core x 2.5 sq.mm flat.[ Make –Polycab / Havell’s / Finolex ] [Co’s Analysis Enclosed ]
Supply , fitting and fixing in position of G.I. Tata make.( Medium ) quality for underground works with all necessary accessories , viz. socket , bend , tee, union , cross elbow , nipple , short piece , flange , plug etc. including cost of jointing materials , cutting pipes , making threads, cutting trenches up to 1.5 mts. below surface in all sorts of soil and refilling the same as per direction with two coats of painting on G.I. pipes and specials with bituminous paint complete in all respect as per G.S. [ sch. Page -3 /I – 2 ] a. 50 mm. dia G.I.pipes .
b. 25 mm. dia. G.I. pipes
Supply & fixing S. S. Single Head Hydrant valve complete for 63 mm. dia. [ ISI / Approved make ] CPWD. P- 785, Code – 4202 / U.D & M.A – P- 44 /i- 8.4 / PWD – P- 17 /I- 19.G.
Supply & fixing 65 mm x 50 mm. reducing socket for Hydrant pipe line. [ sch. Page – 18 / I – 19 iii. L ]
Supply & fixing Fire Fighting Hose Real [ RRL Hose] of 15 mts. long , 63 mm. dia . with instantaneous couplings and hose shall be stored inside the Hose cabinet. CPWD. P- 785. Code -4209 + Non- Schedule ( Cabinate ) [ Make – Force Industries / A..N..Ex flame Fire Protection PVT..Ltd./ Fyrax India ] [Analysis Enclosed ]
Supply of S.S. short branch pipe with Nozzle. [ Make – OMEX- IS – 903 ] Analysis Enclosed ( Pyro Guard / Trade India / OMEX IS903 )
Arrangement for 4 way Header assembly with S & f necessary 50 mm.x 50 mm. dia. fittings as per direction of E.I.C. [ All fittings are TATA make / ISI ] a. G.I. Tee
b. G.I. Short Piece./ Nipple -75 mm.long
c. G.I. Socket.
d. G.I. Long bend ( 90 deg. )
e. G.I. End Cap.( 50 mm. dia. )
Supply & Fixing Fire bucket [ 9 Lts.] – [ ATASEE – IS – 2546 / Attack Fire / BuyTm Industries ]
S & F 40 mm. dia. G.I. pipe (TATA- Medium ) ISI mark submersible cable protection pipe with necy. Bend, Union , Socket etc. as per requirement with supporting clamp. [ Length – 5 mts. From the well. Approx. ] ( PWD. Sch. P- 3 / I -2 v )
S & F G.I. Column pipe M.S. holding clamp size – 12 x 50 mm with necy. nuts, bolts & washers etc. for submersible Pump set.
S & F anti snapping safety device for the P/M set with nylon rope binding at both side of the clamp as per direction of E.I.C. ( if required ).
S & F split type 12 mm. thick M.S. fabricated suitable for well cover with holes for column pipe & submersible cable etc. as per direction of E.I.C.
Construction of supporting pillar [ Size – 300 x 300 x 900 mm height ] for resting Header lines for easy operation with net cement finish as per direction of E,I,C.
Making 4 – way Header line by ( 80 mm.dia x 1.5 mts Long ) G.I.( Medium ) ISI mark pipe with 4 no’s 80 mm x 50 mm dia & 1 no.80 mm x 40 mm dia. reducing socket incl. cutting of pipes , welding , threading etc. as per direction of E.I.C. ( Analysis Enclosed ) [ PWD. Sch. P- 18 / I – 19(iii)L & P-3 / I- 2 ]
Painting the total plumbing lines by weather proof epoxy paint dark green colour ( ISI mark ) branded paint after preparation of surface as per direction of E.I.C. [ Lump Sum Rate ]
ADD 18% GST
Add 1% Cess
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.27 MB
BOQ_2399963.xls
BOQ • 0.54 MB
drawingdalkhola.pdf
Tender Documents • 1.18 MB
2911ii.pdf
Tender Documents • 1.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .