Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.5 CrAccepted-AOC 103 HARIAKSH PLAZA HOSPITAL ROAD BHUJ KUTCH GUIARAT 370001 | BHUJ | KUTCH | GUJARAT | 370001 | ₹2.5 Cr | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹2.7 Cr+₹15.4 L (6.08%)Rejected-Finance | ₹2.7 Cr+₹15.4 L (6.08%) | L2 | Rejected-Finance NOT BEING L1 |
| 3 | L3₹2.8 Cr+₹28.0 L (11.1%)Rejected-Finance V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | ₹2.8 Cr+₹28.0 L (11.1%) | L3 | Rejected-Finance NOT BEING L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical not having Cat c(vii) |
| 5 | Rejected-Technical | - | - | Rejected-Technical not having Cat c(vii) |
Tender Value
₹2.3 Cr
EMD Value
₹3.1 L
Closing Date
6 Apr 2022, 6:00 pmClosed
CE CG GOA
CE CG GOA 403806
PROVISION OF SEWAGE TREATMENT PLANT AT CGDHQ1 PORBANDAR
2022_MES_510228_1
82021/E8
Open Tender
Civil Works
Lump-sum
365 days
PORBANDAR
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹3,000
GE (I) (CG) PORBANDAR
₹3.1 L
Yes
14 Oct 2022
24 Feb 2022
8 Apr 2022
24 Feb 2022
6 Apr 2022
30 Mar 2022
Amount
SCHEDULE "A" Part - I (BUILDING WORKS) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-II ( EARTH WORK AND SITE CLEARANCE) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-III (INTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-IV (INTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-V (SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-VI (ROAD/CULVERT/HARDSTANDING) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-VII (AREA DRAINAGE) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-VIII (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-IX (EXTERNAL ELECTRIC SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART -X (MISCELLANIOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.' E ' signifies this fact only.
RAW SEWAGE TRANSFER PUMP Submersible, non-clogging, raw sewage transfer pump having continuous duty rating, cast iron casing, stainless steel impeller and stainless steel shaft complete directly coupled with induction motor 415 V, 3- Phase, 50 Hz of suitable capacity with 2900 RPM, IP 68 protection, class F insulation including installation, foundation as per OEM specification, electrical connection etc. all complete as specified in technical / particulars specification of following capacity:-
Submersible, non-clogging, Raw Sewage Transfer Pump (RSTP1) having 25 m3/hr at 10 MWC head (1 W + 1 S) for peak sewage flow.
Submersible, non-clogging, Raw Sewage Transfer Pump (RSTP2) having 6.5 m3/hr at 10 MWC head (1 W + 0 S) for average sewage flow.
Supply, Installing, Testing and Commissioning of Ultrasonic Level Transmitter at wet well sump with complete electric connection up to Main LT panel of treated water pump house in STP compax. Range : 0-2 meters Accuracy : 0.5 % minimum Supply Voltage : 24 V dc Output : 4-20 mA NOTE:- Cost of cable connection from LT panel to control panel is deemed to be included in the unit rate quoted. Make : Banner / ABB / Emerson / Kroshne Marshall
SEWAGE TREATMENT PLANT:- Supply, Installing, testing and commissioning (SITC) of sewage treatment plant based on principle of aerobic attached growth non clogging randomly moving bed bio reactor (MBBR) with primary, secondary and tertiary process domestic sewage treatment plant having capacity 100 m3/day, along with interconnecting equipment, lot of piping, valves, instrumentation, pumping and blower equipment and including all civil work such as foundation, platform, plinth for pump, blower and filtration unit etc. comprising following accessories / equipment as per the OEM specification and attached drawing to achieve the indicated parameters mentioned elsewhere in the tender documents complete all as specified and directed by engineer-in-charge. NOTE:- [i] All civil works, viz. excavations & earth work, PCC, masnory, foundation platform, plinth, etc. required for installation shall be measured and paid separately. (ii) The piping work alongwith valves to be executed as per Drawing No CE(CG)GOA/P&D/12/2020 sheet 01/01 (iii) Cost of pipe & valves is deemed to be included in quoted rate [iv] Rates quoted shall be deemed to inclusive of following (Item Nos. 16.00 to 24.00)
PRIMARY TREATMENT SYSTEM SS-304 perforated screens with suitable lifting arrangement (size 400 mm X 400 mm X 3.5 mm (L X W X T) with 10 mm openings
Manual overflow type oil skimmer
SECONDARY TREATMENT SYSTEM Submersible, non-clogging, Anoxic Feed Pump (P1) having having 5 m3/hr at 12 MWC head, continuous duty rating, cast iron casing, stainless steel impeller and stainless steel shaft complete directly coupled with induction motor 415 V, 3- Phase, 50 Hz of suitable capacity with 2900 RPM, IP 68 protection, class F insulation including installation, foundation as per OEM specification, electrical connection,etc complete all as specified in technical/particular specification (1 W + 1 S)
Package MSEP 100 KLD STP- tank of size 9.23 m X 2.2 m X 2.2 m having twin lobe rotary Air Blowers (B1) capable of delivering 200 m3/hr of atmospheric air at 0.37 kg/cm2 pressure, driven through "V" belt or directly coupled through flexible coupling to a TEFC motor suitable for 415±10% V, 3- Ph, 50 Hz AC supply. (1 W + 1 S)
Air piping (100 mm NB) comprising of pipes droppers / laterals with MS (epoxy coated) header complete with all fittings viz. tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc.
Air dispersion system for equilization tank & anoxic / MBBR tank & sludge holding tank with fine & coarse bubblers
Prefabricated MSEP sewage treatment plant comprising of inbuilt compartments of aeration zone, lamella settling zone with FRP plates and chlorination zone for disinfection with all required valves piping.
Sodium Hypochlorite dosing system consisting of one HDPE tank (DT1) of 150 litres capacity, positive displacement diphragm dosing pump (DP1) having variable flowrate of 0-6 LPH @ 5.5 kg/cm2 along with motor suitable for operation at 230 V, 1- Ph, 50 Hz. supply and complete with necessary polypropylene piping, valves, strainers, low level switch and injection fittings. The pump shall have speed & stroke control.
Non clogging type centrifugal Anoxic Recirculation Pumps (P2) capable of 20 m3/hr discharge at 12 MWC head and having solid handling capacity of minimum 32 mm size particles having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller (with wiring), etc. (1 W + 1 S)
TERTIARY SYSTEM Centrifugal Filter Feed Pump (P3) capable of 5 m3/hr discharge at 35 MWC head having solid handling capacity of minimum 5 mm size particles CI casing & impeller complete with all accessories, motor suitable for 415±10% V, 3- Ph, 50 Hz AC supply, pressure gauge with isolation cock, isolation valve, NRV on delivery line, strainer at suction. mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve, etc. (1 W+ 1 S)
MSEP vessel for pressure sand filter of ø 600 mm & 1875 mm HOS (shell & dishend thickness 4.0 mm minimum) suitable for test pressure of 5.0 kg/cm² and working pressure of 3.5 kg/cm², including media (pebbles, sand, silex, fine sand, fine silex), standard fittings viz. pressure gauge, sampling cock, backwash including frontal piping & valves, etc.
MSEP vessel for Activated Carbon Filter (ACF) of ø 800 mm & 1875 mm HOS (shell & dishend thickness 4.0 mm minimum) suitable for test pressure of 5.0 kg/cm² and working pressure of 3.5 kg/cm², including media (activated carbon with supporting media), standard fittings viz. pressure gauge, sampling cock, backwash including frontal piping & valves, etc.
SLUDGE DEWATERING SYSTEM Non clogging type centrifugal Sludge Transfer Pumps (P4) capable of 3.5 m3/hr discharge at 10 MWC head having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller to control, etc. (1 W + 1 S)
Filter Press Feed Pump (P5) capable of 1 m3/hr discharge at 45 MWC head with all accessories.
Filter press as of size 5 mtr X 2 mtr X 0.8 mtr with following specification (i) Type - plate and frame (ii) Plate - poly propelene (iii) Frame - mild steel (iv) Filter cloth - suitable size (v) Fluid handled - sludge (vi) Nature of solids - Biological (vii) Sludge quantity - 41 Kg/Batch (viii) Sludge concentration - 1%
Electric Panel Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type " CONTROL PANEL" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 2.0 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed.
The MCC shall comprise of the following: [a] Busbar Chamber: [i] Copper busbar of rated capacity 150 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
[xi] 20 A, 230 V, SPN MCB - 02 Nos. - (one for pump house light & one for sequrity light)
Supply and laying DI pipes K-9, 100 mm NB all as directed
Supply and laying DI pipes K-9, 80 mm NB all as directed
NOTE: PARAMETER OF USAGE OF TREATED SEWAGE WATER SHALL BE AS PER GUIDELINES ISSUED BY E-IN-C FOR PLANNING & DESIGN OF SEWER NETWORK & STP VIDE LETTER NO. 86435/MISC/E4(U3), DATED 19/05/2017.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI wire of 4.0 mm diameter as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 15 mm diameter, connected to earthing test point, all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. complete as specified and directed by the engineer-in-charge. (for RSTP1 & RSTP2 - 02 Nos. , P1 - 02 Nos., P2 - 02 Nos., P3 - 02 Nos., P4 - 02 Nos., P5 - 02 Nos., B1 - 02 Nos., DP - 02 Nos., LT panel - 02 Nos. Internal wiring -01)
TREATED WATER SUPPLY Supply, installation, testing and commissioning of monoblock, self-priming, single-stage, centrifugal volute type Monoblock type pump with suitable for 450 LPM water flow rate at 18 m head for domestic water supply. [1 W + 1 S] having cast iron casing, enclosed type dynamically balanced phosphor-bronze/SS impeller, high tensile steel shaft, carbon steel stuffing box (sealed by mechanical seal), deep groove ball bearings, TEFC squirrel cage induction motor having IE- 3 efficiency and conforming to IS: 12615- 2018, base plate, mounting channel frame, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting suitable for operation on 3- Phase, 415 V ± 10%, 50 Hz AC supply including foundation as per the manufacturer's recommendation complete all as specified and directed.
Supply, installation, testing and commissioning of PN 1.6 rated 80 mm NB CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories all complete as specified and directed.
S & F of PN 1.0 rated 40 mm NB CI ball valve, screwed female end and necessary accessories all complete as specified and directed.
S & F of PN 1.0 rated 25 mm NB CI ball valve, screwed female end and necessary accessories all complete as specified and directed.
S & F of DI pipe of 100 mm NB class K7 grade and shall be IS marked and it will have inner lining conforming to IS complete all as specified and directed.
S & F of DI pipe of 80 mm NB class K7 grade and shall be IS marked and it will have inner lining conforming to IS complete all as specified and directed.
M&L for DI fittings and fixtures such as bends (iany type, radious and angle) tapers any type (staight, bend, increasing decreasing or double socket etc) Tee pieces single branch, Y junction, double branch, cross (all sockets or socket and spigot) collars, caps and piugs upto 100mm bore.
M&L for cast iron air release valves with two air outlets, 50mm dia bore and fixing up in cast iron water supply mains of dia 100mm bore. Make:- Zoloto/Leader/venus/L&T/Kirloskar
Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type "Water Supply Panel" of suitable size, conforming to IEC 61439-1 & 2, IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 42 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. [Make: Legrand(SIGMA)/L&T (ASCENT)/C&S (VEDS)]
The Water Supply Panel shall comprise of the following: [a] Busbar Chamber: [i] Copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
[b] Incoming: [i] 125 A, 415 V, Ics = Icu = 25 kA, 50 Hz, FP MCCB with adjustable overload settings (0.36- ` X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 Nos.
[ii] LED phase indicators (Red, Yellow, Blue)- 01 Set [iii] Power Measurement Device with Class 1 accuracy, complying to IEC 62053- 22, 64 samples/cycle, 31st harmonic analysis, RS485, calibration LED, third party accuracy test certificate - 01 Nos. [iv] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.
M & L for Construction of fly-ash brick masonary valve chamber of size 1000 mm X 800 mm X 1000 mm (internal dimenssions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/Dense soil 6 mm thick MS sheet cover fixed on 25 mm X 25 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC coaping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc complete all as specified and directed.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised strip of size 32 mm x 6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed.
INTERNAL ELECTRIFICATION S & F 20 W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed.Make: HALONIX Cat-Part No. HLB-08-20-CW-AL or equivalent model of Havells, Philips or Wipro
S & F 10 W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. Make: HALONIX Cat-Part No. HLB-08-10-CW-AL or equivalent model of Havells, Philips or Wipro
S & F 25 W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥ 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high effiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket 1.2 m long with including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and light grade GI pipe (25 mm), including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete all as specified and directed. Make: BAJAJ Cat-Part No. BAJAJ 169829 BCLST 20W LED I or equivalent model of Havells, Philips or Wipro
S & F BEE five star rated energy efficient high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 210 CMM, operating voltage 220-240 V and frequency 50 Hz, including a downroad of suitable size and electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fan complete all as specified and directed. Make: Crompton Cat-Part No. ENTRUST50 or Havells Cat- Part No. ES-50 or equivalent model of Usha or BAJAJ
S & F engery efficient non-metalic fresh air fan having blade sweep 250 mm, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed. Make: Crompton Cat-Part No. VENTILUS 10" or equivalent model of Usha, Havells or BAJAJ
S & F engery efficient metalic exhaust fan having blade sweep 300 mm, air delivery not less than 900 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed. Make: Crompton Cat-Part No. TRANS AIR 12" or equivalent model of Usha, Havells or BAJAJ
S & F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified and directed by engineer-in-charge. Make: Schneider, Legrand, Havells (a) 6 A, SP MCB, C- curve
(b) 16 A, SP MCB, C- curve
(c) 20 A, SPN MCB, C- curve
SEWAGE DISPOSAL M&L for 150 mm dia DWCPE pipe laid in trenches complete all as specified and directed.
M&L for 200 mm dia DWCPE pipe laid in trenches complete all as specified and directed.
M&L for 250 mm dia DWCPE pipe laid in trenches complete all as specified and directed.
S & F 150mm DWC Full Coupler complete all as specified and directed.
S & F 200mm DWC Full Coupler complete all as specified and directed.
S & F 250mm DWC Full Coupler complete all as specified and directed.
M&L for providing porbandar stone masonry built in CM (1:4) all as directed.
M&L for providing 25mm thick setting coat in CM (1:2) trowelled to even and smooth finish all as specified and directed.
Supply and laying SFRC Manhole cover of size as shown in drawings complete all as specified.
EXT ELECTRIFICATION Supply and laying double corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner walll confirming to ISI 14930(Part I and II) for protection of underground cables, of size 63mm outer dia with all fittings, laid in trenches/road/nallah or fixed along wall, poles or laid under floor (including cutting gloor/road and making good to match with existing adjoining surface etc for cable protection all as specified. (Excavation and earth work shall be measured and paid separately). Make:- Rex/Poly/Gemini
Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC to give an output of 20 KVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz + 1% supply, 1500RPM, directly coupled with diesel engine water cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads, control panel & other accessories etc and comprising of following
Diesel Engine: Water cooled turbo charged with after cooler to deliver suitable BHP at 1500RPM under NTP conditions of 88 5614 and conforming to IS 10002, DIN 6271 & 180 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories - Diesel engine of rated speed at full load electric start developing with system with radiator and induding electronic governor control, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling and coupling guard complete. (Make: Cummins/KOEL/Greaves/Mahindra)(a) Radiator with blower fan or heat exchanger with guard.(b) Pipe coupling for engine cooling system piping. (c) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel (ii) Lube oil (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator (n) Exhaust piping made out of STIC C class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (0) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet 30 gauge for the entire length of exhaust pipe. (p) First fill of oil coolant and diesel during commissioning and 12 hours testing (q) Interconnecting copper cabling of adequate capacity batteries control (r) Fuel pipe class STIC 1"/1.5" 12" dia - 01 lot (s) Self starter 12 volts DC, (t) Electric operated electronic governor.(u) Fuel injection pump.
(v) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) battery voltage (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed. (V) Engine hours. (vl) Frequency (vii) Voltage (w) Safety control (Trip and indication) (i) High water temperature (ii) Low lube oil temperature (iii) Over speed stop (x) Base frame: Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads. (aa) Battery-1No. 12 volts DC, 180AH, maintenance free battery with leads & terminals (Make-Excide/Amron) (ab) Fuel tank: 08 hrs, full load diesel storage capacity fuel tank with mounting brackets factory made of 5mm thick HR/MS sheet with level indicator fuel inlet, fuel outlet, air vent, drain plug, in let arrangement for diesel filling fro exterior canopy (without opening its panel) etc complete all as specified and directed. Alternator:- Suitable rated at 20 KVA factor, 416 volte, 3 phase, 4 wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushless excitation, screen protected, drip proof Insulation class HIP-23, self ventilated and conforming to BS: 5000/IS: 4722 suitable for engine as mentioned here in before (Make: KOEL/Crompton Greaves/Stamford) Acoustic Enclosure - M & L for acoustic enclosure for the above 20 KVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audible frequencies as per guide of Central Pollution Control Board and size 3490 x 1340 x 1885mm and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified (i) Sound insulation : 100mm thick Rock wool (Density 64 Kg/Cum). (ii) Outer body: 1.6mm thick CRCA (iii) Door: 1.6mm thick CRCA (iv) Base frame : ISMC 300 (v) Inside illumination : 1 No.- 1 x 18 watt FTL fitting of make Phillips Bajaj/ Crompton. AMF Control panel - Factory fabricated cubicle type, free standing, floor mounted, indoor type, IP-52, AMF control panel, provided with removable rear panels & hinged front panel for easy accessibility fabricated out of not less than 2.0mm thick CRCA sheet including two coats of powder coated paint over a coat of red oxide primer etc and comprising of following:
(i) AMF control circuit with 4 pole MCCB 63 Amps with ultimate breaking capacity Icu-35 KA at 415 volts and microprocessor release conforming to IEC 60947 Part-1 with breaking capacity lcs=lcu at 415 volts of 16 KA, thermal overload setting 70% to 100%, short circuit setting 5 to 10 times-02 Nos, for main supply & DG set supply with HRC back up fuse complete with all DC control relays/Line voltage monitor (LVM) as per OEM specifications incorporating motorised stored energy operating Engine start, stop, three attempt starting facility and failure to start etc (ii) Digital load manager: Three phase 4 wire indicating V.I.PF, KVA, KW, F of Enercon make with serial communication port model No.EM6400 with class 1.0 accuracy meter or equivalent make suitable rating of CT per phase-one No. (iii) Indication lamp R, Y, B with 3 Nos of 2A HRC fuses-10 sets (iv) Bottom gland plate for incoming and outgoing cables (v) Circuit diagram plate, Civil works - All civil works related to foundation, installation of panel and equipment & depth of foundation shall be minimum 300mm with ant vibration pads, or as recommended by manufacturers, Cable from DG set to AMF panel is deemed to be included in the quoted rate. Cable from AMF panel to main panel will be measured and paid separately under relevant items. Note:-The fuel for final testing of 12 hours shall be supplied by the contractor and cost deemed to be included in the above offer. All other necessary equipments like resistance load strip heater of suitable capacity/rating and any other items required for final testing shall be provided by the contractor without any extra cost to department.
RYSA INFRATECH PRIVATE LIMITED
Electromech Engineers
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .