Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹47,715Accepted-AOC PAMKARAM VEEDU CHINKODE P O MALAPPURAM 673645 | MALAPPURAM | MALAPPURAM | KERALA | 673645 | 1 | Accepted-AOC AEE/LIDEW-DIV/MPM/040/24-25 | |
| 2 | 2₹47,715Same as 1Rejected-Finance KARISHOTT HOUSE CHERUVAYKK P O SANTHIDANG K P KRIKOPPARAVISH CHEVIKKULLI KURAKKI P O SUKKOOR BADARATHI WAYANAD 673592 | WAYANAD | WAYANAD | KERALA | 673592 | 2 | Rejected-Finance L2 | |
| 3 | Rejected-Technical 15082236 MOHAMMED ALI C 1508 SUB TREASURY VALANCHERRY | - | Rejected-Technical L3 |
Tender Value
₹51,587
EMD Value
₹1,290
Closing Date
17 Jul 2024, 6:55 pmClosed
EXECUTIVE ENGIEER
Office of the Executive Engineer, LID and EW Division, Malappuram, civil station, Malappuram District Panchayath Building, Malappuram, 676505
Annual Plan-Malappuram District Panchayath Construction of building for Ex service men bavan at Areakode-921-23-General Electrical Work
2024_LSGD_679845_4
DB1/TN/04/24-25
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
MALAPPURAM
Please refer Tender documents.
11 documents required · 11 mandatory
₹590
₹1,290
Yes
23 Sept 2024
10 Jul 2024
19 Jul 2024
10 Jul 2024
17 Jul 2024
10 Jul 2024
Amount
Electrical
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.3:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD27746/2024-2025:Supply and fixing 12W LED bulk head fitting heat resistant prismatic glass cover to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required.
1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD27298/2024-2025:Supplying and Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate
OD27299/2024-2025:Supply, providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD27300/2024-2025:Supply and providing 25x6mm brass nut and bolt etc. as required.
OD27741/2024-2025:Supply and installation of dust and vermin proof, 1 Phase Syntax Meter Board GS-MB-4537-NF and to fix KSEB meters, fuse units, CT etc and to fix KSEB meters, fuse units, CT etc as required including fixing it on wall, making good the damages colour washing etc. as required.
OD27303/2024-2025:Supplying and fixing 32 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board
OD27304/2024-2025:Supplying and fixing 32A, HRC Fuse with HRC Fuse link with connections, in existing meter board
MOHANAN K
JAHFAR
Bidder Name
MOHANAN K
FASAL K V
JAHFAR
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1057396.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .