CWE AF AMBALA
HQ CWE AF Ambala
SPECIAL REPAIR / REPLACEMENT OF HT EQUIPMENTS AGAINST BER AT AF STN AMBALA UNDER GE (AF) AMBALA
2021_MES_427311_1
CWE/AF AMB/AMB-54/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF AMBALA
For enlisted in MES Class C and category b ii and for unenlisted refer NIT
8 documents required · 8 mandatory
₹1,000
Yes
GE AF AMBALA
₹1.2 L
Yes
24 May 2021
2 Mar 2021
9 Apr 2021
2 Mar 2021
7 Apr 2021
24 Mar 2021
2 Mar 2021 - 18 Mar 2021
Amount
Taking out / dismantling of old unserviceable HT TEE / VL isolating oil immersed switch HT / Switch fuse oil emersed HT / Ring main HT of any ampere rating from the existing sub station buildings and deposited to MES store yard of GE complete all as specified and directed.
Supply, fixing, testing, commissioning and desiging of non extensible SF 6 gas insulated 6 way 11 KV ring main unit outdoor type with gas tank IP 67 protection & outdoor enclosure – IP 54 Protection with 1 No 11 KV vacuum circuit breaker for incoming and 05 Nos VCB for outgoing shall be nominal voltage 12 KV 630 Amp, 21 KA/3s. The complete switch gear shall be tested for internal arc of 21 KA FLR for 1 Second. HT Compartment - (Circuit Breaker) -I/C feeder & O/G feeder (i) This function - unit consists of a vacuum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and the earthing function. The circuit breaker unit is equipped with an over current time released for the protection.
(i) VCB 12 KV 630 Amp, 21 KA. (ii) Stored energy mechanism for manual operation with integrated earthing switch. (iii) Self powered electronic numerical protection relay providing over current and earth fault protection. (iv) Ring core current transformer for protection & metering as per specification CT Dual core ratio 100/50/5 Amp-01 No for incoming and 50/25/5 Amp- 05 Nos for outgoing, CIass-1.0 accuracy for metering & 5 P 10 for protection, burden - 2.5 VA (v) Capacitive voltage indication fixed type - LCD display. (vi) ON, OFF, Trip indication on the front mimic of the panel. (vii) Cable box for termination of cable up to 300 Sqmm. (viii) Cable cover standard. (ix) Emergency trip push button. (x) Digital multifunction meter to measure Amp, Volt, Frequency, PF, KWh & KVAR. (xi) Operation counter. (xii) Shunt trip coil - 24 Volt DC. (xiii) Set of 12 KV right angled cable boots (terminal protector) (xiv) Operation voltage - 11 KV. (xv) Rated lightening withstand - 75 KV. (xvi) Copper Bus bar - 630 Amp. (xvii) 2x12 volt battery with battery charger for motor operation (xviii) Space heater with thermostat.
Supply, fixing, testing, commissioning and desiging of non extensible SF 6 gas insulated 5 way 11 KV ring main unit outdoor type with gas tank IP 67 protection & outdoor enclosure – IP 54 Protection with 1 No 11 KV vacuum circuit breaker for incoming and 04 Nos VCB for outgoing shall be nominal voltage 12 KV 630 Amp, 21 KA/3s. The complete switch gear shall be tested for internal arc of 21 KA FLR for 1 Second. HT Compartment - (Circuit Breaker) -I/C feeder & O/G feeder (i) This function - unit consists of a vacuum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and the earthing function. The circuit breaker unit is equipped with an over current time released for the protection.
(i) VCB 12 KV 630 Amp, 21 KA. (ii) Stored energy mechanism for manual operation with integrated earthing switch. (iii) Self powered electronic numerical protection relay providing over current and earth fault protection. (iv) Ring core current transformer for protection & metering as per specification CT Dual core ratio 100/50/5 Amp-01 No for incoming and 50/25/5 Amp- 04 Nos for outgoing, CIass-1.0 accuracy for metering & 5 P 10 for protection, burden - 2.5 VA (v) Capacitive voltage indication fixed type - LCD display. (vi) ON, OFF, Trip indication on the front mimic of the panel. (vii) Cable box for termination of cable up to 300 Sqmm. (viii) Cable cover standard. (ix) Emergency trip push button. (x) Digital multifunction meter to measure Amp, Volt, Frequency, PF, KWh & KVAR. (xi) Operation counter. (xii) Shunt trip coil - 24 Volt DC. (xiii) Set of 12 KV right angled cable boots (terminal protector) (xiv) Operation voltage - 11 KV. (xv) Rated lightening withstand - 75 KV. (xvi) Copper Bus bar - 630 Amp. (xvii) 2x12 volt battery with battery charger for motor operation (xviii) Space heater with thermostat.
Supply, fixing, testing, commissioning and desiging of non extensible SF 6 gas insulated 4 way 11 KV ring main unit outdoor type with gas tank IP 67 protection & outdoor enclosure – IP 54 Protection with 1 No 11 KV vacuum circuit breaker for incoming and 03 Nos VCB for outgoing shall be nominal voltage 12 KV 630 Amp, 21 KA/3s. The complete switch gear shall be tested for internal arc of 21 KA FLR for 1 Second. HT Compartment - (Circuit Breaker) -I/C feeder & O/G feeder (i) This function - unit consists of a vacuum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and the earthing function. The circuit breaker unit is equipped with an over current time released for the protection.
(i) VCB 12 KV 630 Amp, 21 KA. (ii) Stored energy mechanism for manual operation with integrated earthing switch. (iii) Self powered electronic numerical protection relay providing over current and earth fault protection. (iv) Ring core current transformer for protection & metering as per specification CT Dual core ratio 100/50/5 Amp-01 No for incoming and 50/25/5 Amp- 03 Nos for outgoing, CIass-1.0 accuracy for metering & 5 P 10 for protection, burden - 2.5 VA (v) Capacitive voltage indication fixed type - LCD display. (vi) ON, OFF, Trip indication on the front mimic of the panel. (vii) Cable box for termination of cable up to 300 Sqmm. (viii) Cable cover standard. (ix) Emergency trip push button. (x) Digital multifunction meter to measure Amp, Volt, Frequency, PF, KWh & KVAR. (xi) Operation counter. (xii) Shunt trip coil - 24 Volt DC. (xiii) Set of 12 KV right angled cable boots (terminal protector) (xiv) Operation voltage - 11 KV. (xv) Rated lightening withstand - 75 KV. (xvi) Copper Bus bar - 630 Amp. (xvii) 2x12 volt battery with battery charger for motor operation (xviii) Space heater with thermostat. Note for item No 2.00 to 4.00 : - The rate for making foundation for RMU of size as per recommendation by manufacturer and the cost of excavation, brick work, concrete etc shall be included in the quoted rate. The drawing for foundation as per manufacturer design & shall be approved by GE.
Supply, installation, commissioning and testing of transformer step down, 11 KV/433 volts as per IS-1180-2014 (Level- III), outdoor type, copper wound, suitable for AC, three phase, 4 wire, 50 Hz system of capacity 160 KVA, oil immersed having Vector group DYN-11, naturally cooled type with and including first filling of transformer oil, delta connection on HT side, star connection on LT side, manually, operated, off-load tap changer on HT side to vary secondary voltage to + 7.5% & -7.5% in three steps & above of 2.5% each, cable end box at HT & LT side, LT side cable box shall also be fitted with suitable size of cable glands for making connections with all the accessories and the under mentioned fittings complete all as specified and directed:- (a) Rating plate and terminal marking plate. (b) Two earthing terminal for body earthing and two additional for neutral brought out on a bushing. (c) Lifting lugs. (d) Drain valve with plug or cover plate. (e) Dehydrating breather. (f) Oil level indicator with aluminium and maximum marking. (g) Cooling radiator. (h) Thermometer pocket. (j) Conservator. (k) Oil filling hole with cover. (l) Thermometer 100mm dial/stem type with metal guard having maximum temperature indication with resetting.
(m) Silica gel breather duly filled with silica Gel. (n) Any other fittings as recommended by the manufacturer of efficient functioning of the transformer. Notes: - (i) The cost of platform/foundation as per manufacturer’s recommendation shall be included in the quoted rates and the drawing of the foundation shall be got approved by GE before construction. (ii) The transformer shall be of latest star rated and energy conservation (Energy conservation Binary Corps) for which necessary test certificate of manufacturer shall be produced by the contractor. (iii) Transformer manufacturer shall be in possession of licence from bureau of Indian standard. (iv) The fitting & accessories of the transformer shall be conforming to is 3639 : 1996. (v) The transformer shall be tested as per IS for all routine tests in the factory premises in the presence of rep of Accepting officer on the receipt of request from the contractor in addition to routine tests . The transformer shall be tested for 10% over load at factory premises for minimum 01 hour after full load cycle of 08 hours. (vi) The Transformer shall be tested by SEI/EI/AEI beore commissing. (vii)All the test results shall be produced before RAR. All necessary arrangements i.e. Co-ordination with the manufacturer & testing officer, arranging equipments and material to facilitate testing at the manufacture’s premises etc. shall be borne by the contractor.
Supply and fixing in replacement cable jointing kit for 11 KV earthed grade cable, indoor type, end termination heat shrinkable type joints with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm including cutting complete all as specified and as directed.
Supply and fixing in replacement cable jointing kit for 11 KV earthed grade cable, indoor type, end termination heat shrinkable type joints with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including cutting complete all as specified and as directed.
Supply and fixing in replacement cable jointing kit for 11 KV earthed grade cable, indoor type, end termination heat shrinkable type joints with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm including cutting complete all as specified and as directed.
Supply and fixing in replacement cable jointing kit for 11 KV earthed grade cable, outdoor type, end termination heat shrinkable type joints with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm including cutting complete all as specified and as directed.
Supplying, laying, jointing, testing and commissioning in replacement HT XLPE cable heavy duty), 11000 volts (earthed), insulated, screened, sound compacted aluminium conductor, screening with extruded semi conducting layers, insulation screening with copper tape covers laid up with PVC (ST-2), extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 Part II with amendment, size cross sectional area 95 Sqmm, 3 core, laid in trenches /pipes /ducts /along poles/ walls/ equipment etc complete all as specified and directed.
Supply, laying, jointing, testing and commissioning in replacement HT XLPE cable(heavy duty), 11000 volts (earthed), insulated, screened, sound compacted aluminium conductor, screening with extruded semi conducting layers, insulation screening with copper tape covers laid up with PVC (ST-2), extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 Part II with amendment, size cross sectional area 120 Sqmm, 3 core, laid in trenches /pipes /ducts /along poles/ walls/ equipment etc complete all as specified and directed.
Supply, laying, jointing, testing and commissioning in replacement HT XLPE cable(heavy duty), 11000 volts (earthed), insulated, screened, sound compacted aluminium conductor, screening with extruded semi conducting layers, insulation screening with copper tape covers laid up with PVC (ST-2), extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 Part II with amendment, size cross sectional area 240 Sqmm, 3 core, laid in trenches /pipes /ducts /along poles/ walls/ equipment etc complete all as specified and directed. NOTES for item No. 10.00 to 12.00 : (i) Cable shall be of manufacturing date not earlier than Dec 2020. All the cable shall be embossed with year of manufacturing, meterage at every metre, in addition to its own standard markings as per IS i.e. Size, voltage etc. (ii) Excavation & earth work, sand cushioning, protection pipes, end termination joints & protection covers shall be measured and paid separately. (iii) No straight through joint shall be permitted in less than single drum length. (iv) The contractor shall produce original purchase vouchers duly machine numbered alongwith excise duty gate pass of factory for verification and record. (V) Cable shall also be tested in the presence of Rep of GE after laying in the trench before returning filling in the trench.
Excavation in trenches not exceeding 1.5mtr wide and not exceeding 1.5mtr in depth for foundation etc or for walls, shafts, manholes not exceeding 10 Sqm on plan or for laying pipes/cables etc and getting out, in soft/loose soil complete all as directed.
Removal of excavated soil to a distance not exceeding 50 mtr & depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed.
Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm thick each in soft/loose soil complete all as specified and as directed.
Supply and laying in replacement un-reinforced precast concrete cable cover , Class HVP type-1 ,peak size 300mmx180mmx40mm, laid flat for protection of cable , adjacent to each other, perpendicular to central axis of cable complete all as specified and as directed.
Material and labour in replacement GI pipe 80 mm bore , light grade as in trenches, under road,under floor, fixed to wall with fixing arrangement with suitable size of MS clamps made from 40x3 mm size flat iron including nuts,bolts & washers or along the pole with fixing arrangement etc for cable protection complete all as specified and as directed .
Material and labour in replacement earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to GI earth lead strip 32x6 mm upto 7.5 mtrs long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly including watering pipe GI 20 mm bore, light grade including protection pipe GI light grade 40mm bore , wire mesh, funnel,lugs, salt, charcoal dust, excavation & earthwork in soft/losse soil and refilling pit chamber with PCC 1:2:4 type B1 using 20 mm graded mechnically crushed stone aggregates , RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates pit cover slab 50 mm thick reinforced with 8 mm dia TMT bars @ 15 cm c/c both ways including necessary form work all as shown in electrical plate No 3 of SSR part-I (2009), including testing on completion on site complete all as specified and as directed. Notes :- (i) Any variation in length of earth lead and protection pipe of earth lead shall be adjusted through DO. (ii) On testing if the earth resistance is not obtained, earthing will be generated at No extra cost ,till the desired earth resistance is obtained. (iii) The chamber shall be constructed atleast 0.5 mtr away from the earth electrode.
Supply, installation & fixing in replacement factory made, HT feeder pillar box, cubical, water proof, vermin proof, powder coated painted of size 1200x1200x1200mm, out door type with front and rear opening with locking arrangement, fabricated out of 3.15mm thick MS sheet supported on 50x50x6mm thick angle iron frame and grouted in PCC 1:3:6, type C, of block and 50 cm above ground level, fitted with and including HT 11 KV base type insulations on and including fitting with suitable size of MC and HT 11 KV aluminium bus bars three phase system hyaving provn for cable gland for incoming 01 No and 01 out going cables complete all as specified and as directed. Note:- (i) Necessary earthwork and PCC included in quoted rates. (ii) Feeder pillar shall be approved by GE
Deduction of Total of Sch of credit amount Rs 67100.00
R D Bansal
Raman Electric Trading Co
Baliyan Electrical Works
Electromech Engineers
Leo Air and Power Solution pvt Ltd.
Rajindera Enterprises
M/S BALWINDER SINGH
SHARMA ELECTRICAL ENGINEERS
Esha Engineers
SATISH AND CO
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .