Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.8 LAdmitted-Finance 362 SUBHAS NAGAR PO CLEMENT TOWN DEHRADUN UK | ₹8.8 L | L1 | Admitted-Finance |
| 2 | L2₹9.2 LAdmitted-Finance MOHANPURA MAHAMMADPUR SOUTH CIVIL LINES PO MILAP NAGAR ROORKEE 247667 | ROORKEE | HARIDWAR | UTTARAKHAND | 247667 | ₹9.2 L | L2 | Admitted-Finance |
| 3 | L3₹9.3 LAdmitted-Finance 108 1 SANJAY COLONY GURU ROAD PATEL NAGAR DEHRADUN 248001 UTTARAKHAND | DEHRADUN | UTTARAKHAND | 248001 | ₹9.3 L | L3 | Admitted-Finance |
| 4 | L4₹9.9 LAdmitted-Finance DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹9.9 L | L4 | Admitted-Finance |
| 5 | L5₹10.6 LAdmitted-Finance AMBEDKAR PARK AND RAWAT PG HOUSE WARD NO 10 KHASRA NO 2435 DEHRADUN UTTARAKHAND 248 140 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248140 | ₹10.6 L | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | TARUN ENGINEERING WORKS L4 | A ONE BUILDERS AND ENGINEERS L2 | KAPOOR ELECTRICALS L1 | S.K ASSOCIATE L5 | anant enterprises L6 | M/S K K ENTERPRISES L3 | GLOBALVISION POWER SOLUTIONS PVT LTD L7 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Dismantling unserviceable LT panel /Bus bar of any size from the site and removing existing concrete block complete all as specified and directed | 4 | Each | 500 ₹2,000 | 206 ₹824 | 500 ₹2,000 | 500 ₹2,000 | 1,000 ₹4,000 | 100 ₹400 | 1,500 ₹6,000 |
| 2.00 | Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board of size 1 .2x1.0x0.8 m , Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 400 Amp rated fixed on DMC insulators
INCOMER : (i) MCCB 250 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal magnetic release, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed. 01 Nos. (ii) Multifunction meter = 01 set. (iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos
Outgoing : (a) (i) MCCB 125 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 02 Nos (ii) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 01 No (iii)MCCB 40 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 01 No
(i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be got approved from AGE(I) before fabrication. | 1 | Each job | 1,11,000 ₹1.1 L | 1,66,000 ₹1.7 L | 1,35,000 ₹1.4 L | 1,85,000 ₹1.9 L | 1,50,000 ₹1.5 L | 1,00,000 ₹1 L | 1,25,000 ₹1.3 L |
| 3.00 | Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board of size 1 .2x1.0x0.8 m , Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 200 Amp rated fixed on DMC insulators
INCOMER : (i) MCCB 125 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal and magnetic release, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed. 01 Nos. (ii) Multifunction meter = 01 set. (iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos
Outgoing : (a) (i) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 25 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 02 Nos (ii) MCB TPN 32 Amps, 415Volts, 4 pole 50 Hz, 10 KA 'C' curve complete including phase spreaderall as specified and directed - 01 No.
(i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be got approved from AGE(I) before fabrication. | 1 | Each job | 90,000 ₹90,000 | 1,28,000 ₹1.3 L | 1,10,000 ₹1.1 L | 1,35,000 ₹1.4 L | 1,20,000 ₹1.2 L | 1,05,000 ₹1.1 L | 98,800 ₹98,800 |
| 4.00 | Supply and fixing in repair Bus bar chamber of size 0.7x0.7x0.6 m made out of 3.00 mm thickness sheet metal enclousre totaly enclosed outdoor type, vermin proof, powder coated paint, metal clad with porcelain insulator and colour coated tinned copper bus bar 415 volts, 200 Amps rated, 4 pole for connecting UG cable, fixed on ground and required size of steel clamp, screw, bolt, nut, washers for tightend with pole, in outer site the letters shown Danger 440 volts all as specified and directed by Engr-in-Charge. (Note-: The price for foundation is included in quoted rate). | 2 | Each | 29,000 ₹58,000 | 24,009 ₹48,018 | 20,000 ₹40,000 | 30,000 ₹60,000 | 33,000 ₹66,000 | 25,000 ₹50,000 | 36,500 ₹73,000 |
| 5.00 | Taking out unserviceable / serviceable cable /UG cable of any size upto 240 Sqmm carefully from trenches/poles/ducts/LT panels, OH conductors at different locations all as specified and directed by Engr-in-Charge. | 750 | RM | 20 ₹15,000 | 20 ₹15,000 | 10 ₹7,500 | 10 ₹7,500 | 5 ₹3,750 | 50 ₹37,500 | 20 ₹15,000 |
| 6.00 | Dismantling of ACSR conductor of any type | 0.5 | Qtl | 200 ₹100 | 1,200 ₹600 | 50 ₹25 | 1,000 ₹500 | 400 ₹200 | 50 ₹25 | 4,000 ₹2,000 |
| 7.00 | Supply and laying , fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, insulated, armoured heavy duty electric cable with aluminium conductor, XLPE , 1100 volts grade, cross-sectional area of size 150 Sqmm sqmm 3.5 core with all as specified and directed. by Engr-in-charge.
Note:- (i) The earth work, GI pipe shall be measured and paid sepretely.
(ii) Cable may fixing/ passing through pipe laid in trenches or fixed to pole/ wall or fixed to LT panel etc.
(iii) ACSR conductor, Old UG cable replaced with New UG Cable. | 250 | RM | 999 ₹2.5 L | 900 ₹2.3 L | 990 ₹2.5 L | 900 ₹2.3 L | 1,100 ₹2.8 L | 1,095 ₹2.7 L | 1,650 ₹4.1 L |
| 8.00 | All as per item No. 7 here-in-before but 120 sqmm 3.5 core complete all as specified | 120 | RM | 940 ₹1.1 L | 800 ₹96,000 | 728 ₹87,360 | 750 ₹90,000 | 950 ₹1.1 L | 920 ₹1.1 L | 895 ₹1.1 L |
| 9.00 | All as per item No. 7 here-in-before but 95 sqmm 3.5 core complete all as specified | 80 | RM | 760 ₹60,800 | 680 ₹54,400 | 625 ₹50,000 | 700 ₹56,000 | 750 ₹60,000 | 720 ₹57,600 | 580 ₹46,400 |
| 10.00 | All as per item No. 7 here-in-before but 35 sqmm 3.5 core complete all as specified | 200 | RM | 360 ₹72,000 | 230 ₹46,000 | 250 ₹50,000 | 350 ₹70,000 | 350 ₹70,000 | 320 ₹64,000 | 300 ₹60,000 |
Updated dates
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
23 May 2026, 6:00 pmClosed
AGE (i) RAIWALA
AGE (i) RAIWALA
REPAIR AND REPLACEMENT OF LT OVERHEAD DISTRIBUTION SYSTEM TO UNDERGROUND CABLE AND ALLIED WORK AT ZONE A AND B UNDER AGE (I) RAIWALA
2026_MES_762450_1
8145/26-27/E8
Open Tender
Civil Works
120 days
AGE (I) RAIWALA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
AGE (I) RAIWALA
₹20,000
Yes
28 May 2026
28 Apr 2026
25 May 2026
28 Apr 2026
23 May 2026
10 May 2026
28 Apr 2026 - 9 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling unserviceable LT panel /Bus bar of any size from the site and removing existing concrete block complete all as specified and directed | 4 | Each | - | - |
| 2 | Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board of size 1 .2x1.0x0.8 m , Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 400 Amp rated fixed on DMC insulators
INCOMER : (i) MCCB 250 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal magnetic release, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed. 01 Nos. (ii) Multifunction meter = 01 set. (iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos
Outgoing : (a) (i) MCCB 125 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 02 Nos (ii) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 01 No (iii)MCCB 40 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 01 No
(i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be got approved from AGE(I) before fabrication. | 1 | Each job | - | - |
| 3 | Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board of size 1 .2x1.0x0.8 m , Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 200 Amp rated fixed on DMC insulators
INCOMER : (i) MCCB 125 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal and magnetic release, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed. 01 Nos. (ii) Multifunction meter = 01 set. (iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos
Outgoing : (a) (i) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 25 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 02 Nos (ii) MCB TPN 32 Amps, 415Volts, 4 pole 50 Hz, 10 KA 'C' curve complete including phase spreaderall as specified and directed - 01 No.
(i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be got approved from AGE(I) before fabrication. | 1 | Each job | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
MAKEAPPROVAL.pdf
Additional Documents • 15.01 MB
8145TED.pdf
Tender Documents • 1.26 MB
BOQ_854050.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid