Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹75.5 LAccepted-Finance | 1 | Accepted-Finance L-1 | |
| 2 | 2₹79.6 L+₹4.1 L (5.45%)Accepted-Finance | 2 | Accepted-Finance L-2 |
Tender Value
₹49.5 L
EMD Value
₹50,000
Closing Date
27 May 2022, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE
ETC-II, UPPTCL, PAARESHAN BHAWAN, VIBHUTI KHAND, GOMTI NAGAR, LUCKNOW-226010
SUPPLY
2021_UPTCL_648142_5
ETC-II/L/48/2021-22
Open Tender
Supply of Materials
Item Rate
90 days
LUCKNOW
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SE, ETC-II, UPPTCL, LUCKNOW
₹50,000
16 Jun 2022
7 May 2022
28 May 2022
7 May 2022
27 May 2022
7 May 2022
180 days
Amount
Portable circuit breaker analyzer with 06 channel DCRM for measurement of operation testing of Main, PIR and Auxiliary Contacts (wet & dry) of CB as well as recording the close & trip coil currents, dynamic contact resistance measurement of Main & Arcing Contacts as well as Travel measurement (with external travel transducer & fixture) of operating mechanism.
Portable CT-PT analyser instrument set suitable for precise measurement of CT Turn Ratio, Polarity, Knee point voltage, Secondary winding resistance, Demagnetization, Burden, Insulation resistance etc. upto 400kV Class CTs, Ring type CTs mounted in Bus ducts & turret assembly in power transformers and reactors; PT Turns Ratio, winding resistance, polarity, saturation, short circuit impedance test, Insulation Resistance & CVT Ratio, Phase deviation. The kit should confirm to detailed technical specification.
Portable Dew Point & Oil Moisture (PPM) Meter suitable for online measurement of Moisture (Dew Point in “C’ PPMv, PPMw) of gas in gas insulated EHV equipment and transformer oil) in live switchyard upto 765 KV Level, as per IEC 60376 & CIGRE B3.02.01. The instrument should have a range of at least 70 to +30 degC with a resolution of 1deg.C and accurancy of ±2º for Dew Point and 0 to 100ppm with a resolution of 1ppm for moisture in oil. The kit should confirm to detailed technical specification.
AMREST ELECTRICALS LIMITED
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .