Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.2 LAccepted-AOC RAJKOT ROAD AIR FORCE STATION HALWARA 141106 PUNJAB | HALWARA | LUDHIANA | PUNJAB | 141106 | ₹22.2 L | L1 | Accepted-AOC Being lowest |
| 2 | L2₹22.7 L+₹46,568 (2.10%)Rejected-Finance MANDIR ROAD NEW ABADI AKALGARH AIR FORCE STATION HALWARA TEH RAIKOT DISTT LUDHIANA PB 141106 | LUDHIANA | LUDHIANA | PUNJAB | 141106 | ₹22.7 L+₹46,568 (2.10%) | L2 | Rejected-Finance other than lowest |
| 3 | L3₹28.6 L+₹6.4 L (28.8%)Rejected-Finance | ₹28.6 L+₹6.4 L (28.8%) | L3 | Rejected-Finance other than lowest |
Tender Value
Refer Docs
EMD Value
₹53,040
Closing Date
30 Sept 2024, 6:00 pmClosed
GE (AF) Halwara
GE (AF) Halwara
SPECIAL REPAIR TO AUTOMATIC ACB CONTROL PANEL AT MAFI SUBSTATION AND PROVISION OF BORE WELLS IN TECHNICAL AREA AT AF STN HALWARA
2024_MES_668547_1
GE/HAL-33/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Halwara
MES ENLISTED CONTRACTOR CLASS D CATEGORY b(i)
8 documents required · 8 mandatory
₹500
GE (AF) Halwara
₹53,040
Yes
2 Nov 2024
2 Sept 2024
2 Oct 2024
2 Sept 2024
30 Sept 2024
16 Sept 2024
Amount
Supply, installation, testing & commissioning in replacement floor mounted, cubical type, Automatic ACB control LT panel, indoor type, factory made, powder coated, CPRI approved, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 HZ electric supply system, made out of 50mm x 50mm x 6mm angle iron frame and 3.15 mm thick CRCA sheet side covers with front and back hinged doors with proper locking arrangement, width of panel as per manufacturer design, rubber gasket on front and back to make it dust and vermin proof, including aluminium busbar sleeved with heat shrink sleeve colour coated for phase, 4 wire electric supply system including busbar chamber, danger notice plate, wiring with suitable size of copper cable, mounted on PCC 1:2:4 type B-1 (With 20 mm graded stone agregate) foundation block of suitable size upto 40 cm above gound level complete with & including the following accessories :- (a) 04 Strips of aluminium bus bar with insulation colour sleeves RYBN of capacity 2000 Amp fixed on PVC heat shrinkable insulator heavy duty as per panel design-01 set, complete fixing on SMC / DMC insulators & supports. (b) ACB 1250 Amp 4 pole EDO 50KA with display-06 Nos (Incoming-01 No, DG set 01-01 Nos, DG set 02-01 Nos, Outgoing-01 Nos and spare ACBs-02 Nos). ACB shall confirm to IEC60947/IS 13947 (Part 1 & 2). The minimum breaking capacity should be 50 KA. The service short circuit breaking capacity (Ics) should be equal to ultimate breaking capacity (Icu) and short time withstand capacity (Icw) with Ics=Icu=Icw. The Icw value is for 1 sec.
Note :- 1. The layout diagram of AMF Panel shall be submitted by the contractor for approval of Accepting Officer before placing order for procurement. 2. Rates quoted by the contractor will deemed to be included the cost of syncronisation with existing PLC panel any other major or minor spare required for successful functioning of the panel installed at MAFI Sub Stn. 3. Specifications of Automatic ACB control LT panel, Indoor type to be as per CI 8.23 of IS 8623:1993 (Part-I). 4. The ACBs shall be pragrammed in such a way that on failure of commercial supply, the integration with existing panel must be able to give command and process both the DG set installed at site with only healthy supply of one DG going for further utilisation. 5. The Panel must be synchronised for CAT-II mode of operation. 6. All other existing features must be fully functional and tested to the entire satisfaction of Engr-in-Charge. Cost of all other add ons required for the successful installation, testing & commissioning of the said item shall deemed to be included in quoted rate. 7. Contractor shall submit purchase Voucher, e-way bill and test certificate while claimimg payment of ACB control Panel.
M&L for Mechanical drilling for main bore well 150 mm dia below ground level upto a depth of 100 meter in any kind of soil complete including comprising the following :- (a) M&L Column pipe PVC 125 mm dia heavy duty grade for casing of bore well complete including all fittings-100 RM. (b) Supply installation,testing and commissioning of submersible pump set 2 HP, single phase, 240 volts, 50 HZ outer dia of pump set 40 mm and including suitable size of starter-01 Each. (c) S&F PVC insulated copper conductor flat type submersible cable 4 sqmm 2 core 1100 volt grade including clip for fixing of cable -65 RM. (d) S&F PVC pipe medium grade size 40 mm dia including long size of socket- 50 RM (e) S&F NRV valve size 40 mm dia Each = 01 Nos. (f) S&F gunmetal gate valve of size 40 mm dia each=01 Nos (g) MCB SPN 40 Amp-01 Nos. (h) Supply and fixing single phase 2.0 HP relay 8.9-13.5 contactor rating 16 Amp SPS with 2 P contactor + overload relay (Ammeter+Voltmeter) wiogh 160-220 V AC coil Suitable for Submersible motor upto capacity 2 HP-01 Nos
Supply and laying steel water tubing GI medium grade with all fittings laid in trenches or fixed to wall etc for 25 mm dia bore, complete all as specified and directed.
All as per item No 3 above but 40 mm dia bore.
All as per item No 3 above but 50 mm dia bore.
Supply and fixing Gun metal gate valve size 25mm with iron wheel head screwed both ends for iron pipes, complete all as specified and directed.
Supply and fixing Gun metal gate valve size 40mm with iron wheel head screwed both ends for iron pipes, complete all as specified and directed.
Supply and fixing Gun metal gate valve size 50mm with iron wheel head screwed both ends for iron pipes, complete all as specified and directed.
Supply, laying, jointing, testing and commissioning of cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, laid in trenches, fixed by means of MS saddles on or fixed on poles including connection with proper lugs for the size 16 SQmm 2 core, complete all as specified and directed. Note :- Excavation and earth work shall be measured and paid seperately.
Excavation in trenches in soft or loose soil, not exceeding 1.5 metre deep and not exceeding 1.5 metre wide and getting out, complete all as specified and directed.
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25 cm thick in soft/loose soil, complete all as specified and as directed.
Removing surplus excavated soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point, complete all as specified and as directed.
Kular and Company (BID ID -3120889)
BEHL AND COMPANY (BID ID -3120416)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .