Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹47.8 LAccepted-AOC 39 BASANT VIHAR RAKKAR COLONY UNA H P 174303 | UNA | UNA | HIMACHAL PRADESH | 174303 | L-1 | Accepted-AOC lowest bidder | |
| 2 | L-2₹49.8 L+₹2.0 L (4.13%)Rejected-Finance | L-2 | Rejected-Finance Higher bidder | |
| 3 | L-4₹50.1 L+₹2.3 L (4.86%)Rejected-Finance NIL | L-4 | Rejected-Finance Higher bidder | |
| 4 | L-4₹51.4 L+₹3.5 L (7.42%)Rejected-Finance BARKOT UTTARKASHI | RUDRA PRAYAG | UTTARAKHAND | 246141 | L-4 | Rejected-Finance Higher bidder |
Tender Value
₹62.1 L
EMD Value
₹1.6 L
Closing Date
9 Jun 2021, 1:00 pmClosed
Lokesh Thakur
S.E(OP) Circle, SHimla
SOP to M.C Town Hall Building, the mall Shimla in Electrical Section Ridge under ESD, Ridge, Shimla-1
2021_HPSEB_47219_1
DB-Tenders/No-04(SOP MC Town Hall Building)/2021-2
Open Tender
Supply and Erection
Turn-key
180 days
Shimla
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
Sr. Executive Engineer, Electrical Division No-II
₹1.6 L
1 Jul 2021
10 May 2021
10 Jun 2021
10 May 2021
9 Jun 2021
10 May 2021
Amount
Design, Manufacture, Supply, Erection, Testing & Commissioning in supervision of OEM of CSS (Compact Substation)- distribution net work consisting of 250KVA,11/.4KV outdoor compact transformer mineral Oil type with level 3 losses as per IS-1180, totally factory assembled (non walk in type) consisting of 3 WAY RMU completely non-motorized (2 Nos Isolators + 1 No Breaker VCB) with copper busbar, SF6 insulated preferably with site replacable cable bushing, for 250KVA DTR , nominal voltage of 12 KV,short-time current rating of 21 KA for 3 seconds, Making Capacity 52.5KA, Impulse withstand voltage to earth between poles-95KV peak alongwith right angle boot Touch Proof termination Kits, with HT metering of 0.5 accuracy Class CT 60-30/1 Amps, PT 11KV 110 volt and HT meter compatible to HPSEB TOD tariff make Secure/L&T/HPL) on HV side, and having 1 No incomer of 400 Amps 36KA & 2 Nos outgoing 250Amps, 35/36KA MCCB 4 Pole on LV side with aluminium busbar of rating 630A and having all necessary wiring and space for FRTU (FRTU supply not in scope) for future compatibility with SCADA system complete in all rescept as per the direction of Engineer incharge. Make:ABB/SCHNEIDER/GE(ALSTOM)/SIEMENS/L&T
Design, Manufacture, Supply, Erection, Testing & Commissioning in supervison of approved OEM make, 12kV 630 Amps 21KA for 3 Sec. SF6 insulated, BIL 38 KV/95 KV peak, both side extensible, outdoor duty 4 way, manually operated Ring main unit ( 4 LBS ) consisting of copper busbar in SF6 insulated with right angle boot Touch Proof termination Kits. The RMU design should preferably support site replaceable HT cable bushing. All the necessary wirings and space for FRTU to be given along with RMU for future compatibility with SCADA system (Supply of FRTU is not in scope). The scope is including Plinth/Angle iron Stand as per OEM design complete in all rescept as per the direction of Engineer incharge.Make:- ABB/ SCHNEIDER/GE (ALSTOM)/ SIEMENS/ CGL/ C&S
Supply, Erection, Testing & Commissioning of Copper Earthing for neutral of transformer with copper earth plate 600mm x 600 mm x3 thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 Mtr. long etc with charcoal/coke and salt as required to complete the job including copper strip of size 40x 6mm from equipment to earthing complete in all rescept as per the direction of Engineer incharge.
Supply, Erection, Testing & Commissioning of GI Earthing for body earthing HT Panel & Transformer with GI plate 600mm x 600 mm x3 thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 Mtr. long etc with charcoal/coke and salt as required to complete the job including GI strip of size 40x 6mm from equipment to earthing complete in all respect as per the direction of Engineer incharge.
Prov. & fixing fire retardant/ extinguishing Electrical Insulated Synthetic Mat of size 3.00mm thick+10% confirming to IS; 15652 :2006 & metering requirements of SI; 3043, IS 5216 ( Part 1, 2 &3), IS 8437 and 479 Pub-1, Testing of Breakdown Strength,tensile/Elongation ageing properties, insulation resistance effects of acid alkaline diesel and transformer oil, leakage current test, fire test etc. having minimum width of 1000mm + 20mm. All allied material such as PU- resin, chemi bond (hardner) Aspl. PVC adhesive, liquid primer etc. suitable for all voltage not exceeding 66KV system with HT Trolley movment complete in all rescept as per the direction of Engineer incharge.
Supplying, Installation, testing & commissioning of 11kV XLPE 3x300mm2 armoured cable including DWC HDPE Corrugated pipe 150mm Dia ,per ISI specifications and latest ammendment thereof .excavation and refilling of trench:(B-0.500X H-1.00mtr) including cable tray and MS Angle iron to be used in open space near station complete in all rescept as per the direction of Engineer incharge.
Supplying, Installation, testing & commissioning of Heat Shrinkable End Termination Kit suitable for 11kV XLPE 3x300mm2 armoured cable as per ISI specifications and latest ammendment thereof CPRI tested complete in all rescept as per the direction of Engineer incharge. Make:3M/Denson/Rychem/Frontech.
Supplying, Installation, testing & commissioning of Heat Shrinkable Straight through Jointing Kit suitable for 11kV XLPE 3x300mm2 armoured cable as per ISI specifications and latest ammendment thereof CPRI tested complete in all rescept as per the direction of Engineer incharge.Make:3M/Denson/Rychem/Frontech.
Supplying, Installation, testing & commissioning of 1.1KV grade XLPE 3.5 Core 240mm2 LT cable with thimble, including DWC HDPE Corrugated pipe 150mm Dia ,per ISI specifications and latest ammendment thereof .excavation and refilling of trench:(B-0.500X H-1.00mtr) including cable tray and MS Angle iron to be used in open space near station as per ISI specifications and latest ammendment thereof complete in all rescept as per the direction of Engineer incharge.
Supplying, Installation & testing Fire extinguisher 01 nos. 6kg CO2 Cylinders and 01 no. 9kg AFFF Mechanical Foam Cylinder as per ISI specifications and latest ammendment thereof complete in all rescept as per the direction of Engineer incharge.
Supplying, Installation of Route and Joint indicating stone as per ISI specifications and latest ammendment thereof complete in all rescept as per the direction of Engineer incharge.
ECS ENGINEERING CHD PVT LTD
Nivesh Engineering and Power Solutions
AARNA ELECTRICAL AND CO
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .