Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 6 573D BHASKARA BUILDING NADAKKAVU P O UDAYAMPEROOR ERNAKULAM KERALA 682307 | ERNAKULAM | KERALA | 682307 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance H NO 8 1 398 PM 189 PARAMOUNT HILLS TOLICHOWKI HYDERABAD 500 008 | HYDERABAD | HYDERABAD | TELANGANA | 500008 | Admitted-Finance |
| 5 | Rejected-Technical KARUKAPPILLY THATTATHUKUDIYIL BUILDING KOLENCHERY 682311 | KOLENCHERY | ERNAKULAM | KERALA | 682311 | Rejected-Technical Submittted documents does not meet PQC |
Tender Value
Refer Docs
EMD Value
₹25,000
Closing Date
13 Jul 2022, 12:00 pmClosed
SM(Mat)-C
Contracts Dept Corporate Materials FACT Udyogamandal
REWIRING OF LAKE VIEW HOSTEL AT FACT-CD TOWNSHIP, AMBALAMEDU
2022_FACT_695950_1
04026/2022-2023/E25687
Open Tender
Miscellaneous Works
Item Rate
90 days
FACT CD, AMBALAMEDU
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹25,000
Yes
8 Nov 2022
20 Jun 2022
13 Jul 2022
20 Jun 2022
13 Jul 2022
20 Jun 2022
Supply of 240 V, 5/6A, one way modular type switch with ISI mark.
Supply of 240 V, 15/16A, one way modular type switch with ISI mark.
Supply of 240 V, 5 A, 3pin modular type plug socket with ISI mark
Supply of 240 V, 15/5 A,5pin modular type plug socket outlet with ISI mark.
Supply of 240 V,single modular type ceiling fan regulator
Supply of 1/2 M type modular GI box with front plate.Make-LEGRAND/elleys or equivalent .
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-06", switch board. The installation scope shall include chipping the wall/pillar and conceal the switch box ,mounting the front plate after fixing the switches/sockets , wiring the switch board, termination of 1.5/2.5 sq.mm multi stranded cables etc. Separate earth shall be provided to the switch board. The materials such as SS screws,PVC/nylon grips for mounting the switch box etc.shall be supplied by the contractor.
Supply of 3M type modular GI box with front plate.Make-LEGRAND/elleys or equivalent .
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-08", switch board. The installation scope shall include chipping the wall/pillar and conceal the switch box ,mounting the front plate after fixing the switches/sockets , wiring the switch board, termination of 1.5/2.5 sq.mm multi stranded cables etc. Separate earth shall be provided to the switch board. The materials such as SS screws,PVC/nylon grips for mounting the switch box etc.shall be supplied by the contractor.
Supply of 4M type modular GI box with front plate.Make-LEGRAND/elleys or equivalent .
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-10", switch board. The installation scope shall include chipping the wall/pillar and conceal the switch box ,mounting the front plate after fixing the switches/sockets , wiring the switch board, termination of 1.5/2.5 sq.mm multi stranded cables etc.Separate earth shall be provided to the switch board. The materials such as SS screws,PVC/nylon grips for mounting the switch box etc.shall be supplied by the contractor.
Supply of 6M type modular GI box with front plate.Make-LEGRAND/elleys or equivalent .
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-12", switch board. The installation scope shall include chipping the wall/pillar and conceal the switch box ,mounting the front plate after fixing the switches/sockets , wiring the switch board, termination of 1.5/2.5 sq.mm multi stranded cables etc.Separate earth shall be provided to the switch board. The materials such as SS screws,PVC/nylon grips for mounting the switch box etc.shall be supplied by the contractor.
Supply of 8M type modular GI box with front plate.Make-LEGRAND/elleys or equivalent .
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-14", switch board. The installation scope shall include chipping the wall/pillar and conceal the switch box ,mounting the front plate after fixing the switches/sockets , wiring the switch board, termination of 1.5/2.5 sq.mm multi stranded cables etc.Separate earth shall be provided to the switch board. The materials such as SS screws,PVC/nylon grips for mounting the switch box etc.shall be supplied by the contractor.
Supply of 10M type modular GI box with front plate.Make-LEGRAND/elleys or equivalent .
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-16", switch board. The installation scope shall include chipping the wall/pillar and conceal the switch box ,mounting the front plate after fixing the switches/sockets , wiring the switch board, termination of 1.5/2.5 sq.mm multi stranded cables etc.Separate earth shall be provided to the switch board. The materials such as SS screws,PVC/nylon grips for mounting the switch box etc.shall be supplied by the contractor.
Supply of 12M type modular GI box with front plate.Make-LEGRAND/elleys or equivalent .
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-18", switch board. The installation scope shall include chipping the wall/pillar and conceal the switch box ,mounting the front plate after fixing the switches/sockets , wiring the switch board, termination of 1.5/2.5 sq.mm multi stranded cables etc.Separate earth shall be provided to the switch board. The materials such as SS screws,PVC/nylon grips for mounting the switch box etc.shall be supplied by the contractor.
Supply of High lumen, 4 feet LED batten light with all accessories having the following specifications: Color temperature: 6500K, cool white, Lumen output: 2000 lm or more ,Power:20-22W, Operating voltage: 200-250V ,Warranty: 2 years ,Make: Wipro garnet plus 22 or equivalent.
Installations of the item as per the activity code"CDE-PH-1-LV-22", tube fitting. The scope of work shall include supply of materials required for the installation of tube fitting and the erection scope shall include minor civil works like chipping ,drilling ,plastering etc are included in the scope of the contractor.
Supply of wall mounting luminaries with glass/acrylic diffuser and 230 V, B-22 ,9 w LED bulb. The item shall be supplied only after approval of the sample by the Engineer in charge..
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-24", LED luminaries . The luminaries shall be fixed on suitable PVC boxes and the box shall be concealed to the wall. The materials required for the installation and minor civil works like drilling ,chipping ,plastering etc are included in the scope of the contractor. Suitable sized PVC junction boxes required for the installation shall be supplied by the contractor.
Supply of Integral LED Flood light fixture with all accessories (driver unit, heat resistant toughened glass/poly carbonate cover, Power terminals etc.) suitable for mounting on poles (OD 50-60mm),Power consumption -150W maximum, out put lumens-15000(minimum).
Installation and commissioning of item as per the activity code"CDE-PH-1-LV-26", Flood light fixture. The installation shall be on suitable sized G.I pipes and the pipe shall be clamped to the wall. The materials such as G.I pipe,G.I clamps G.I nuts, bolts and washers etc,required for the installation shall be supplied by the contractor. The erection scope shall include drilling the holes, plastering and minor civil works etc.
Supply of 5 star rated ceiling fan with maximum energy consumption less than 35 W ,sweep 1200mm having double ball bearing suitable for 230V,50Hz supply with all accessories like down rod, blade set,canopies,necessary rubber bushings, clamp nuts and bolts etc. incuding guaratee for 2 years.
Installation of the item as per the activity code"CDE-PH-1-LV-28", fan. 3X1.0 sq.mm flexible cables shall be used for connecting the fan and the nearby junction box/ceiling rose.
Supply of heavy duty exhaust fan of sweep 300mm having double ball bearing suitable for 230V,50Hz supply with all accessories like frame, blade set,arms,bkt.s, rubber pad, clamp nuts and bolts, etc. make: Crompton or equivalent
Installation of the item as per the activity code"CDE-PH-1-LV-30", fan. 3X1.0 sq.mm flexible cables shall be used for connecting the fan and the nearby junction box/ceiling rose.
Supply of 650/1100V, PVC insulated, FRLS ISI marked ,multi stranded 1.5 sq.mm copper red/blue/yellow wires.
Supply of 650/1100V, PVC insulated, FRLS ISI marked ,multi stranded 1.5 sq.mm copper black wires.
Supply of 650/1100V, PVC insulated, FRLS ISI marked ,multi stranded 1.5 sq.mm copper green wires.
Installation of the items as per the activity code"CDE-PH-1-LV-32, 33, & 34", copper wires. The installation scope shall include drawing of cables through PVC conduits from switch board to light fittings/fan/plug points/junction boxes and termination of cables at the above points. Cables shall be jointed or tapped only at the junction box/switch boards. Care should be taken to see that not more than 6 cables are taken through a single conduit.
Supply of 650/1100V, PVC insulated, FRLS ISI marked ,multi stranded 2.5 sq.mm copper red/blue/yellow wires..
Supply of 650/1100V, PVC insulated, FRLS ISI marked ,multi stranded 2.5 sq.mm copper black wires.
Supply of 650/1100V, PVC insulated, FRLS ISI marked ,multi stranded 2.5 sq.mm copper green wires.
Installation of the above items as per the activity code"CDE-PH-1-LV-36, 37 & 38", copper wires. The installation scope shall include drawing of cables through PVC conduits from. switch board to light fittings/fan/plug points/junction boxes and termination of cables at the above points. Cables shall be jointed or tapped only at the junction box/switch boards. Care should be taken to see that not more than 6 cables are taken through a single conduit.
Supply of 19/20mm medium type ivory coloured rigid PVC electrical conduit with all accessories such as junction boxes, couplers, bends, tee, elbow ,G.I/PVC saddles, screws, wall/ceiling plugs etc. required for the surface conduit wiring.
Installation and commissioning of the item as per the activity code"CDE-PH-1-LV-40", PVC conduit. The installation scope shall include fixing of PVC conduits and its accessories to the walls / ceilings /columns etc. and neatly clamping at a uniform spacing of 450mm using GI saddles, tagging, drilling holes, minor civil work etc.Suitable sized junction boxes shall be provided at regular intervals. The materials required for the installation such as PVC saddles,screws,nuts and bolts junction boxes etc shall be supplied by the contractor. The erection scope shall include, drilling holes,chiping ,plastering, minor civil works etc.
Supply of 650/1100 V, FRLS grade 4 X 50 sq.mm Al-PVC cable with ISI mark.
Laying and termination of the item as per the activity code"CDE-PH-1-LV-42", cable. The scope of work includes laying of cables through wall/pillars and clamping the cable using 20mm width G.I/Al.strips at an interval not less than 45 cms. The materials such as screws, nuts, bolts ,washers,AL/G.I strips, etc. required for the work shall be supplied by the contractor. The scope of work also include termination of cables at feeder pillar/DB end. The materials such as nuts, bolts ,washers, single compression type cable gland,Al.cable lugs etc. required for the wok shall be supplied by the contractor.
Supply 1C x 50 sq.mm 650/1100 V grade Al-PVC earth cable with ISI mark.
Laying and termination of the item as per the activity code"CDE-PH-1-LV-44", cable. The scope of work includes laying of cables through wall/pillars and clamping the cable using 20mm width G.I/Al.strips at an interval not less than 45 cms. The materials such as screws, nuts, bolts ,washers,AL/G.I strips, etc. required for the work shall be supplied by the contractor. The scope of work also include termination of cables at feeder pillar/DB end. The materials such as nuts, bolts ,washers,Al.cable lugs etc. required for the wok shall be supplied by the contractor.
Supply of 415 V, 3 phase and neutral,6 way double door type distribution board with 160 A TPN HRC SFU as incomer and 18 no's 20A SPMCBs with neutral looping as outgoing. The MCBs shall be of B series ISI certified and rated for 10 kA short circuit capacity. The bus bar shall be made of copper and rated for 125A minimum. The SFU and DB shall be inter connected using 35 sq.mm flexible Cu. cable. The DB shall have separate neutral and earth buses and shall have provision for duplicate earthing also. Suitable sized knock outs shall be provided at the bottom and top side of DB for entry of incomer cables and outgoing PVC conduits. The neutral and earth bus shall be suitable for taking individual leads for each circuit. The enclosure shall have IP43 protection. The gaskets used if any, shall be of neoprene only. Suitable MS adopter box shall be supplied along with SFU by the contractor for the termination of 3.5 x 185 sq mm armoured cable.
Installation of the items as per the activity code "CDE-PH-1-LV-46".The DB and SFU shall be mounted on 35X35x4 mm MS brackets grouted to the wall. The scope of work shall also includes termination of circuit mains on MCBs and,earth/neurtral buses and neatly clamping of cables inside the DB. Spare slots provided for mounting MCB if any shall be properly blanked. The scope of work shall include chipping,fixing,bolting,grouting,replastering, welding, clamping, minor civil works etc. and supply of materials required for the successful completion of the work such cement,rubbles,M-sand ,M.S angles etc.
Supply of 415 V, 3 phase and neutral,6 way double door type distribution board with 63A TPN HRC SFU as incomer and 18 no's 10A SPMCBs with neutral looping as outgoing. The MCBs shall be of B series ISI certified and rated for 10 kA short circuit capacity. The bus bar shall be made of copper and rated for 63A minimum. Suitable sized knock outs shall be provided at the bottom and top side of DB for entry of incomer cables and outgoing PVC conduits. The SFU and DB shall be inter connected using 10 sq.mm flexible Cu. cable. The DB shall have separate neutral and earth buses and shall have provision for duplicate earthing also. The neutral and earth bus shall be suitable for taking individual leads for each circuit. The enclosure shall have IP43 protection. The gaskets used if any, shall be of neoprene only.
Installation of the items as per the activity code"CDE-PH-1-LV-48". The DB and SFU shall be mounted on 35X35X4 mm MS brackets grouted to the wall. The scope of work shall also includes termination of circuit mains on MCBs and,earth/neurtral buses and neatly clamping of cables inside the DB. Spare slots provided for mounting MCB if any shall be properly blanked.The scope of work shall include chipping, ,fixing,bolting,grouting,replastering, welding, clamping, minor civil works etc. and supply of materials required for the successful completion of the work such cement,rubbles,M-sand ,M.S angles etc.
Supply of 650/1100V grade 3.5 x 185 sqmm Aluminium , FRLS cable with ISI mark.
The scope of work shall include excavation of cable trench, digging of under ground cable trench of width 300 mm and depth not less than750 mm, laying the cable from lakeview substation to lakeview hostel kitchen power DB, and providing country bricks along the cable route and then filling back the cable trench with soil and consolidating it to the original level after laying the cable. The trench wherever road cross ,the portion shall be concreted and plastered after soil filling work. The brick shall be supplied by the contractor. The scope of work shall also include laying of cables through wall/pillars and clamping the cable using 20mm width G.I/Al.strips at an interval not less than 45 cms. The materials such as screws, nuts, bolts ,washers,AL/G.I strips, etc. required for the work shall be supplied by the contractor. The scope of work also include termination of cables at both end. The materials required for this work such as nuts, bolts ,washers, single compression type cable gland,Al.cable lugs etc. required for the wok shall be supplied by the contractor.
Supply,installation,testing and commissioning of pipe electrode earth pit as per IS 3043.The work includes excavation of earth pit, installation of pipe electrode, refilling with charcoal & M-sand, construction of inspection chamber with 75 mm thick RCC cover slab, termination of cables etc.The materials required for the work such as 50 mm dia class B ,G.I pipe,G.I strips for terminating the cables,G.I nuts, bolts &washers,Al.lugs,cement,brick,M-snad,etc.required for the work shall be arranged by the contractor.
Supply of 240sq.mm, 1100 V, FRLS ISI marked, PVC insulated unarmoured Aluminium earth cable.
Laying of 240sq.mm PVC insulated unarmoured Aluminium earth cable. The scope of work includes laying of cables through cable trench/wall/floor .The cable shall clamped on the wall using 20mm width G.I/Al.strips at an interval not less than 45 cms. The materials such as AL/G.I strips, G.I nuts and bolts etc. required for the wok shall be arranged by the contractor. However the cable shall be supplied by FACT free of cost.
Termination of the item as per the activity code"CDE-PH-1-LV-53", earth cable at feeder pillar/earth pit. The materials such as Al. lugs,G.I nuts and bolts etc. required for the wok shall be arranged by the contractor.
Supply of 3.5C*185SQ.MM straight joint kit and its execution. Work will be carried out with the licensed cable jointer.
Dismantling of existing electrification in lake view hostel. The scope of this work inludes Dismantling of the old wiring including fans, switches, sockets, old feeder piller, light fittings, etc.and after dismantling all the scrap should be transported to the scrap yard. Transportation of scarp to FACT-CD scrap yard is in contractor scope.
LAMOS TECHNOLOGY SOLUTIONS PVT LTD
BPE BHARATH POWER ENGINEERS PRIVATE LIMITED
Universal ELectricals
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .