| Sl No | Description | Qty | Unit | M/S HINA ELECTRICALS L2 | kumaon and hills strument engnering services L1 |
|---|---|---|---|---|---|
| 1.00 | M& L for opening up the top cover of transformer and taking out the transformer oil in a separate container after disconnecting the HT/LT side electric connections from both the primary & secondary side of the transformer of any type/description (indoor/out door type) installed on pole/floor, for carrying out necessary repair/rewinding to HT/LT side after shifting the transformer to contractors work shop including taking out complete core assembly, megger testing the defective winding portion/taking out , cleaning the laminated core and rewinding with appropriate gauge/winding wire/strip winding of existing description for transformer of capacity 63 KVA to 150 KVA including assembling & testing on completion & installation the same at the site complete all as specified and directed.
Note:- (i) Placing/removing stand by transformer in the place of defective transformer under repair will be the responsibility of the contractor, stand by transformer of same rating and capacity will be provided by the Contractor till refixing / replacing of repaired transformer. Quoted rate shall be deemed to include hiring charges of standby transformer till commissioning of repaired transformer and satisfaction of Engineer in Charge.If standby Transformer not provided within 4 hours of breakdown , a penalty recovery will be done from RAR bill as follows: a) For first day Rs 5000 b) For second day Rs 1000 c) For next every day Rs 1000
(ii) Oil shall be collected by the Contractor for refilling.
(iii) The repair work under each transformer shall be ordered by GE in writting after visual inspection on opening of transformer.
(iv) Winding of coil with copper winding wire shall be measured and paid separately under respective item.
(v) Transportation chagres are inclusive in the quoted rates
(vi) The cost for the dehydration of transformer oil if required and other major items shall be measured and paid separately.
(vii) The cost of insulation material such as paper,cotton tape, latheriod sheet, cork sheet ,gasket etc are inclusive in the coated rates.
(viii) Proper Shut down to be taken by the contractor before execution of work. | 1 | Each | 15,000 ₹15,000 | 25,000 ₹25,000 |
| 2.00 | All as per Item No 01 here-in-before but capacity 160 to 400 KVA. complete all as specified & directed | 1 | Each | 20,000 ₹20,000 | 30,000 ₹30,000 |
| 3.00 | M&L for preparing old painted surface of transformer 11/0.433 KV outdoor/indoor/pole mounting of capacity 63 to 150 KVA by cleaning removing the old paint including scratching with wire brush etc. After disconnected HT/LT side connection from both primary and secondary side of transformer and apply one coat of synthetic enamel spray paint of smoke grey colour to outer body of the transformer and writing of letter HT/LT and SM/MES Nos and making all HT/LT electric connectiones complete all as specified and directed by Engineer - in - charge.
Note:-1. The compressor, spray machine and other required necessary equipment/T&P shall be arrange by the contractor and no extra cost shall be paid to the contractor for this effect. | 6 | Each Job | 500 ₹3,000 | 1,800 ₹10,800 |
| 4.00 | All as per item No. 3 here in before but capacity of transformer 160 KVA to 200 KVA complete all as specified and as directed | 6 | Each Job | 600 ₹3,600 | 2,000 ₹12,000 |
| 5.00 | All as per item No. 3 here in before but capacity of transformer 250 KVA to 400 KVA complete all as specified and as directed | 4 | Each Job | 1,000 ₹4,000 | 2,500 ₹10,000 |
| 6.00 | M&L for preparing old painted surface of transformer 33/11 KV outdoor type of capacity 5000 KVA by cleaning removing the old paint including scratching with wire brush etc. After disconnected HT/LT side connection from both primary and secondary side of transformer and apply one coat of synthetic enamel spray paint of smoke grey colour to outer body of the transformer and writing of letter HT/LT and SM/MES Nos and making all HT/LT electric connectiones complete all as specified and directed by Engineer - in - charge.
Note:-1. The compressor, spray machine and other required necessary equipment/T&P shall be arranged by the contractor and no extra cost shall be paid to the contractor for this effect.
2. Proper Shut down to be taken by the contractor before execution of work. | 2 | Each Job | 25,000 ₹50,000 | 9,000 ₹18,000 |
| 7.00 | Supply and filling up silicagel in breather of different capacity of transformer complete all as specified. | 20 | Kg | 250 ₹5,000 | 220 ₹4,400 |
| 8.00 | M&L for Dehydration and filtering the transformer oil of any type of transformer 11 KV/433 V, 33KV/11 KV, 33KV/433V with dehydration machine to achive required di-electric strengh of the oil up to 52 to 60 KV at a gap 2.5 mm complete all as specified and directed.
Note:- Dehydration machine and other required necessary equipment shall be arranged by the contractor and no extra cost shall be paid to the contractor on this effect. | 3,500 | Ltr | 15 ₹52,500 | 5 ₹17,500 |
| 9.00 | Supply and filling New transformer oil in sealed container for topping up the level of oil having dielectric strength 60 KV during filling after initial filtration conforming to relevant IS-335 complete all as specified and directed. | 1,200 | Ltr | 250 ₹3 L | 220 ₹2.6 L |
| 10.00 | Labour & transportation for shifting of 11/0.433 KV transformer from one location to another location with in cantt area and making connections and testing complete all as specified and directed. Note : Safe transportation of transformer for shifting is responsibility of contractor. | 1 | Each Job | 2,500 ₹2,500 | 1,200 ₹1,200 |
Updated dates
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
4 May 2026, 6:00 pmClosed
CWE (HILLS) PITHORAGARH
HQ CWE (HILLS) PITHORAGARH POST OFFICE - BHARKATIA DISTRICT - PITHORAGARH STATE - UTTARAKHAND PIN 262520
CA NO. CWE/HILLS/PGH/181 OF 2025-2026 REPAIR /MAINT /OVERHAULTING OF DISTRIBUTION TRANSFORMERS, CIRCUIT BREAKERS, 33/11 KV SWITCH YARD EQUIPMENTS, BATTERY CHARGING SYSTEM AT DEVKATIYA AND PITHORAGARH UNDER GE PITHORAGARH
2026_MES_759264_1
89367/25-26/E8
Open Tender
Civil Works
180 days
PITHORAGARH
Class - D
9 documents required · 9 mandatory
₹500
GE (MES) PITHORAGARH
₹58,000
Yes
11 May 2026
6 Apr 2026
11 May 2026
6 Apr 2026
4 May 2026
20 Apr 2026
All as per Item No 01 here-in-before but capacity 160 to 400 KVA. complete all as specified & directed
M&L for preparing old painted surface of transformer 11/0.433 KV outdoor/indoor/pole mounting of capacity 63 to 150 KVA by cleaning removing the old paint including scratching with wire brush etc. After disconnected HT/LT side connection from both primary and secondary side of transformer and apply one coat of synthetic enamel spray paint of smoke grey colour to outer body of the transformer and writing of letter HT/LT and SM/MES Nos and making all HT/LT electric connectiones complete all as specified and directed by Engineer - in - charge. Note:-1. The compressor, spray machine and other required necessary equipment/T&P shall be arrange by the contractor and no extra cost shall be paid to the contractor for this effect.
All as per item No. 3 here in before but capacity of transformer 160 KVA to 200 KVA complete all as specified and as directed
All as per item No. 3 here in before but capacity of transformer 250 KVA to 400 KVA complete all as specified and as directed
M&L for preparing old painted surface of transformer 33/11 KV outdoor type of capacity 5000 KVA by cleaning removing the old paint including scratching with wire brush etc. After disconnected HT/LT side connection from both primary and secondary side of transformer and apply one coat of synthetic enamel spray paint of smoke grey colour to outer body of the transformer and writing of letter HT/LT and SM/MES Nos and making all HT/LT electric connectiones complete all as specified and directed by Engineer - in - charge. Note:-1. The compressor, spray machine and other required necessary equipment/T&P shall be arranged by the contractor and no extra cost shall be paid to the contractor for this effect. 2. Proper Shut down to be taken by the contractor before execution of work.
Supply and filling up silicagel in breather of different capacity of transformer complete all as specified.
M&L for Dehydration and filtering the transformer oil of any type of transformer 11 KV/433 V, 33KV/11 KV, 33KV/433V with dehydration machine to achive required di-electric strengh of the oil up to 52 to 60 KV at a gap 2.5 mm complete all as specified and directed. Note:- Dehydration machine and other required necessary equipment shall be arranged by the contractor and no extra cost shall be paid to the contractor on this effect.
Supply and filling New transformer oil in sealed container for topping up the level of oil having dielectric strength 60 KV during filling after initial filtration conforming to relevant IS-335 complete all as specified and directed.
Labour & transportation for shifting of 11/0.433 KV transformer from one location to another location with in cantt area and making connections and testing complete all as specified and directed. Note : Safe transportation of transformer for shifting is responsibility of contractor.
M & L for Rewinding (Double paper covering) of HT coils of any size and type of transformer including cleaning the burnt out insulating materials, brazing and rewinding with appropriate turns and size of super enamelled copper winding wire including filling insulation paper etc all as specified in particular specifications. Note :- (i) Burnt coils shall be handed over to the contractor by the Engineer-in-Charge through issue voucher for rewinding giving reference of transformer i.e. make Capacity, MES/SM number of transformer etc. (ii) Weight, number of turns, gauge, insulation of winding wire shall be as per OEM. ((iii) Work of rewinding work shall be carried out throught OEM or their authorised vendor only. (iv) Old winding copper wire shall be contractor property and necessary amount as per schedule of credit shall be deducted from the contractor due payment.
M & L for Rewinding/Reinsulation of LT coils of any size and type of transformer including cleaning the burnt out insulating materials, brazing and rewinding with appropriate turns and size of super enamelled copper winding wire including filling insulation paper etc all as specified in particular specifications. Note :- (i) Burnt coils shall be handed over to the contractor by the Engineer-in-Charge through issue voucher for rewinding giving reference of transformer i.e. make Capacity, MES/SM number of transformer etc. (ii) Weight, number of turns, gauge, insulation of winding wire shall be as per OEM. ((iii) Work of rewinding work shall be carried out throught OEM or their authorised vendor only. (iv) Old winding copper wire shall be contractor property and necessary amount as per schedule of credit shall be deducted from the contractor due payment.
M&L in replacement for air breather assembly complete with fresh blue colour silica Gel suitable for indoor/outdoor transformer capacity 63 to 150 KVA as existing size complete all as specified & directed by Engr-in-charge.
All as per item No 13 here in before but transformer capacity 160 KVA to 5000 KVA. complete all as specified & directed
M&L in repair & replacement of PRV (Pressure Relief Valve) of outdoor transformer capacity 5000 KVA, 33/11 KV as existing size & model complete with its connected wiring and control all as specified & directed by Engr-in-charge.
M&L for servicing of Buchholz Relay of outdoor transformer capacity 5000 KVA , 33/11 KV as existing size & model complete by connected wiring , oil levels , lekage arresting and checking of oil level complete all as specified & directed by Engr-in-charge.
M&L for replacement in repair of thermo meter(oil temperature gauge) for 11 KV indoor/Outdoor type transformers upto capacity 400KVA omplete all as specified and directed.
Supply & fix in replacement drain valve of existing size all as specified & directed.
S&F in replacement HT porcelain bushing (set of three) of suitable size for transformer 63 KVA and upto 100 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement of HT porcelain bushing (set of three) of suitable size for transformer above 100 KVA and upto 400 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement LT porcelain bushing (set of four) of suitable size for transformer 63 KVA and upto 100 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement LT porcelain bushing (set of four) of suitable size for transformer above 100 KVA and upto 400 KVA including washers nuts, bolts & complete all as specified and directed.
S&F in replacement HT bush stud rod (set of three) made out of copper with brass nuts and washers of required length including connecting up with HT coil of transformer 63 KVA and upto 100 KVA capacity complete all as specified and directed.
S&F in repairs HT bush stud rod (set of three) made out of copper with brass nuts and washers of required length including connecting up with HT coil of transformer above 100 KVA and upto 400 KVA capacity complete all as specified and directed.
S&F in repairs LT bush Stud rod (set of four) made out of copper with brass nuts and washers of required length including connecting up with LT coil of transformer 63 KVA and upto 100 KVA capacity complete all as specified and directed.
S&F in repairs LT bush stud rod (set of four) made out of copper with brass nuts and washers of required length including connecting up with LT coil of transformer above 100 KVA and upto 400 KVA capacity complete all as specified and directed.
S & F rubber seal for transformer HT/LT studs complete for any capacity of transformer complete all as specified and directed.
Supply and fix in repair off load tap changer suitable for transformer capacity pto 400 KVA as per existing make & model complete all as specified and as directed.
Maintenance, servicing of 33 KV indoor control and relay panel of 33 KV Make- Schneider by checking wiring from outdoor VCB to indoor control panel, tightening of loose connections, U/S indicator with holder, thimble, replacement of unserviceable wiring/part including testing, and checking of tripping system of 33 KV control panel through all protective relays installed on each C&R panel including testing and adjust/ repair the alarm circuit as per time current characteristics by primary injuction test at 60%, 75%, 100% plug including well cleaning and decarbonizing of relay contacts complete all as specified and directed.
Maintenance, servicing and complete overhauling of 11 KV VCB indoor type floor mounted of existing make/ type/mode/capacity including diassembling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts reassembling of parts including well cleaning the complete panel board,main busbar,decarbonizing all joints busbar CTS,PTS, spouts metal parts and making VCB perfect operating in manual and electric mode and calibration & checking of tripping system of 11 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented inservice by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert from authorised agency of state electricity board or authorised engineer and agency of authorised company of VCB,s including submission of calibration certificate complete all as specified and directed.Note:- Spare parts required to make VCB functional will be measure and paid separately under respective items.
Maintenance ,servicing and complete overhauling of 11 KV RMU of make -ABB 630 Amp capacity SF6 gas insulated outdoor type & indoor type including diassembling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts reassembling of parts including well cleaning the complete panel board,main busbar,decarbonizing all joints busbar CTS,PTS, spouts metal parts and making VCB perfect operating in manual and electric mode and calibration & checking of tripping system of 11 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented inservice by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert from authorised agency of state electricity board or authorised engineer and agency of authorised company of VCB,s including submission of calibration certificate complete all as specified and directed.Note:- Spare parts required to make VCB functional will be measure and paid separately under respective items.
M & L for for silicone coating heat resistance and moisture resistant painting of VCBs bus bar compartment chamber of inside HT panels and complete VCBs HT panels painting from outside of 11 KV VCB of existing make/ type/mode/capacity by diassembling of BUS BAR chamber and complete removal of moisture and rusting from inside all joints busbar spouts metal parts and making VCB perfect for painting from inside and outside complete all as specified and directed. Note:- (i) Spray gun machine shall be used for painting.
Supply & Fixing for replacement of following spare parts of HT 11 KV/33KV VCB as approved by GE and Engg in charge all as directed. (Make of VCB : Schneider/C&G/Areava/ABB)
11 KV VCB trolley fixed contact of spout incoming/ outgoing side suitable for VCB & RMU as per existing make & model
11 KV Spouts of VCB epoxy cast resin type as per existing model of VCB & RMU
11 KV Bushings of VCBs & RMU as per existing make & model
11 KV Vacuum Interrupter bottle type indoor type as per existing make & model
33 KV Vacuum Interrupter outdoor type as per existing make & model
Shunt Tripping coil
Volt meter 0 to 15 KV digital type
Ammeter 0/20 to 100/200 Amp digital type
Breaker control switch 10A 660V
Connector for auxiliary switch
DYDAC control, heavy duty connector plug 24 PIN for 11 KV Indoor type VCB
11 KV VCB trolly female jaw incoming/ outgoing side suitable for crompton make VCB & Schneider make complete all as specified and directed.
Electronic hooter
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NO blockl, 22mm dia Red colour
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NC blockl, 22mm dia Green colour.
Integrated LED pilot lamp suitable for operating at ( AC/DC) Red colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) yellow colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) blue colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) green colour
Toggle switch assembly
Fuse holders assembly british pattern fuse links as per IS,13703 2A
Fuse holders assembly british pattern fuse links as per IS,13703 5A
Fuse holders assembly british pattern fuse links as per IS,13703 32 A 3W, 500V
TNC control switch
Panel Heater Thermostat Switch
Closing coil
Auxillary relay for buchholz relay, oil temp, winding temp trip 24/110V DC as per exsting complete all as specified and directed.
Master relay 24/110V DC as per existing complete all as specified and directed.
Remote local switch as per exsting complete all as specified and directed.
Supply, installation,testing and commisioning of 33 KV, outdoor PT, Oil cooled 33KV/110 Volt complete all as specified and directed.
Supply, installation,testing and commisioning of 33 KV outdoor CT oil cooled 200/100/5+5 complete all as specified and directed.
S&F in repair of strip type heater 40/60 watt approx 4"/6" in length including replacement of burnt internal wiring & thermostat & cut out complete all as specified and directed.
Supply, installation,testing and commisioning of control/charging motor in replacement of 11 KV, VCB type complete all as specified and directed.
Supply and fixing,testing,commisioning of Digital type Feedar Protection Relay model MiCom P111 or Easergy of Make Schneider or equivalent , 33KV/11 KV with Aux supply of 20 to 110V AC/DC with 2 NO+2NC contact of existing make including neccesary wiring complete all as specified and directed. Note: All T&P& accesories for testing is carried out by contractor and no extra payment to be done for Testing.
Supply and fixing,testing,commisioning of electro mechanical type Under & Overvoltage protection relay for 11 KV of Make- Alstom or equivalent make including neccesary wiring complete all as specified and directed. Note: All T&P& accesories for testing is carried out by contractor and no extra payment to be done for Testing.
M&L for repair ,testing,of control cable/wiring between 33/11 KV VCBs and power transformers including replacement of unserviceable and damaged cable/wire with suitalbe size with connector and thimble complete all as specified and directed. Note: Control cable made up of copper will be measured and paid separately.
Supply & laying of XLPE insulated , armoured heavy duty electric cable with solid copper conductor of size 2.5 Sqmm 4 core 1100 volts grade complete all as specified and directed.
Maintinance of 33 KV yard comprising of cleaning dust and dirt from the insulators and all the channels bracing support structures and painting the yard with one coat of synthetic enamel paint as required and writing the designation of equipments in english alphabets/letters as specified and mainly the following:- (i) Bus bar Structure of Transformer 33 /11 KV of capacity 5 MVA-02 Nos (ii) Bus bar structure of Transformer 33 /0.433 KV of capacity 63 KVA-01 Nos (iii)Structure and equipment of 33 KV VCBs-04 Nos (iv)Structure of LA set and equipment of VCB-05 Nos (v)Structure of isolator and equipment of VCB-05 Nos (vi) Gantry structure complete busbar system-01 No (vii) Iron Gate -02 Nos (viii) All remaining structure misc-01 lot (ix) Rolling shutters (x) Fire Stand-01 No (xi) Street light poles of Yard
M&L for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petrolium jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.
Supplying and Fixing in repairs, male/moving contact/ rotating blade of HDE copper silver plated of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc complete all as specified and directed.
Supplying and Fixing in repairs, Fixed Contacts, made of HDE copper, silver plated, of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc. complete all as specified and directed.
Supplying and fixing of terminal pad for Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity complete all as specified and directed.
M&L for lightining arrester expulsion type ( set of three as per existing make/model/capacity to be fixed on existing structure) complete with all fitting, transmission class, discharge capacity 65 kilo amps suitable for 33000 volts incl taking down old one etc complete as specified and directed
Supplying and Fixing in repairs, PG clamps for tightening and joints of 33 KV switch yard ACSR conductor with proper SS nut bolts and washers etc complete all as specified and directed.
S&F in replacement pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 33000 volts grade complete all as specified and directed.
M&L for disc type insulator, poprcelain, vitreous in single disc assy for tension with tension clamps for conductors, working pressure 33000 volts of specified size complete all as specified and as directed.
Supply , installation, testing and commissioning in replacement of air- break off load line isolator switch rotating type manually gear drive mechanism operated highest system voltage 36 KV rated current 1250 Amps triple pole with earthing device each pole consist of insulating pedestals 03 Nos on galvanized steel base as per BSS /IS incuding rotating blade of HDE copper and fixed contacts of same material , spring loaded arcing horns of adequate section to brake magnetizing current of transformer as directed with adequate 50mm dia GI operating pipe for operation from ground level and operating handle complete with both off and on positions complete all as specified and directed.
Supply, installation, testing and commissioning of the indoor type current transformer HT 11 KV ratio 100/50/5+5 of input VA-15 type KCT-02 conforming to IS-2705 Part-I of 1981, 50 HZ, HSV-12 KV accuracy limit factor ACP-10 insulation level class-1, 28/75 short time terminal current and hrs duration 13.1 KA for 3 second suitable for VCB Make Schneider , Crompton of 400/600 Amp capacity complete all as specified and directed.
Supply, installation, testing and commissioning of the indoor type current transformer HT 11 KV ratio 50/25/5+5 of input VA-15 type KCT-02 conforming to IS-2705 Part-I of 1981, 50 HZ, HSV-12 KV accuracy limit factor ACP-10 insulation level class-1, 28/75 short time terminal current and hrs duration 13.1 KA for 3 second suitable for VCB Make Areva of 400 Amp capacity complete all as specified and directed.
S&F in repairs cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type end joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 sqmm complete all as specified and directed.
Supply, jointing and testing in replacement of outdoor type cable end termination joint ,heat shrinkable) suitable for aluminium conductor cable of size 120 Sqmm x 3 Core, 11000 Volts grade.
All as per srl item No. 56 here-in-before but for cable size of 95 Sqmm 3 core.
Supply jointing and testing in replacement of indoor type cable end termination joint (heat shrinkable) suitable for aluminium conductor cable of size 240 Sqmm x 3 Core, to 300 Sqmmx 3core 11000 Volts grade.
Supply jointing and testing in replacement of indoor type cable end termination joint (heat shrinkable) suitable for aluminium conductor cable of size 120 Sqmm x 3 Core, 11000 Volts grade.
All as per srl item No. 59 here-in-before but for cable size of 95 Sqmm 3 core.
Supply jointing and testing in replacement of straight through joint (heat shrinkable) suitable for aluminium conductor cable of size 120 Sqmm x 3 Core, 11000 Volts grade.
All as per srl item No. 61 here-in-before but for cable size of 95 Sqmm 3 core.
Supply & top up distilled water in capacity of 5 Ltr cane for filling in batteries in Battery Bank complete all as specified and directed.
Servicing and maintenance of Floating Cum Boost/Trickle Battery Charger Bank cum tripping unit including replacement of U/S indicating lamp and meter complete all as specified and directed.
Supply & Fixing in replacement of recharable sealed Lead Acid Battery maintenance free of capacity 2 Volt 150 AH model C10 for breaker Panel Charger to provide 110 V DC supply to 33 & 11 KV VCBs complete all as specified and directed.
Clearing away all grass vegetation ,saplings, shrubs, brush wood undergrowth roots and trees not exceeding 30 CM girth (measured one metre above ground level) and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearance soft/loose soil and getting out including sprinkling anti vegitation chemical for complete area with spray machine complete all as specified & directed.
M & L for hardcore of broken stone or boulders gauge of 40mm to 63 mm , deposited, spread and levelled in layers n exc. 15cm thick for 33/11 KV switchyard complete all as specified
Taking down XLPE cable 11KV of size 120 Sqmm 3 core for reuse serviceable XLPE cable 11 KV after meggaring from existing position or another position from underground trenches/under road/under path or from poles complete all as specified and directed by Engineer-in-Charge. Note :- Excavation, earthwork, and Relaying serviceable XLPE 11 KV cable shall be measured and paid for separately under respective item of this schedule.
All as per ser item No. 68 here-in-before but for HT cable size of 95 Sqmm 3 core. 11 KV complete all as specified and as directed.
Re laying only in situ or in other new place of serviceable XLPE 11 KV cable of sizes as retrieved from Serial item No 97 & 98 above after meggaring complete all as specified and as directed. ( Note: Excavation , earth work, sand cushionning, bricks /cable cover etc shall be measured seperately under respective item of Sch.)
Excavation in trenches in any type of soil by not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth below ground level for trenches of cable and foundation of poles and getting out complete all as specified .
Excavation in trenches for each additional 1.5m or part there of in depth beyond the first 1.5 m in depth and 1.5 mtr wide and getting out in any type of soil complete all as specified.
Returning, filling in, any type of soil and spreading in layers not exceeding 25cm thick each layer including watering & well ramming complete all as specified.
Removal of surplus soil to a distance not exceeding 50 mtr & depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified .
Supply and laying of un reinforced pre cast concrete cable protection cover class HVP type - 1 flat with size 300mm x 180mm x 40mm laid across the cable (i.e width of cover along the length of cable) for cable protection.
All as per ser item No 75 here-in-before but using old cable cover obtained by taking out under respective items above.
Material and labour for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches complete all as specified and directed and sand cover to under ground cable complete all as specified .Note:Punned thickness of sand willbe measured only.
Supply and fixing / laying of galvanized iron pipe of 80 mm nominal dia light grade fixed to poles with clamps nuts, bolts and washers or laid under road crossing or fixed to wall complete all as specified and directed. Note : The cost of MS clamp, nut, bolt, washer and GI fittings etc shall be inclusive in the item rate.
M& L for cutting of floor/wall/road/footpath for removal of HT U/G cable of any size/description and making good the same as per existing specification after relaying the same or new cable and all as specified & directed.
Supply and laying of HT underground cable XLPE insulated, screened with extruded semiconducting compound in combination with copper tape (0.3 KA for 1 sec) cores laid up, inner PVC sheathed, galvanized steel strip armoured, overall PVC sheathed electric power cable with stranded compact aluminium conductor 11000 volts grade 120 sq mm 3 core confirming to IS:7098 (Part-II) with latest amendements, suitable for earthed system laid in duct/trench/along pole etc including making connection.Make- Gloster, Polycab, Havells Note : 1. The end termination joint shall be measured and paid separately under respective items. 2. Excavation, earth work, sand cushioning and brick protection will be measured and paid separately under respective items.
All as per srl item No. 80 here-in-before but for cable size of 95 Sqmm 3 core. Complete all as specified and as directed
Repair to earth pit & earth pit cover of 33/11 KV Switchyard by using PCC 1:2:4 and plastering in CM 1:3 complete including excavation, returning filling and removal etc complete all as specified and directed.
M&L for earthing complete with galvanised or steel earth plate electrode of size 60cm x60cmx6mm thick burried directly in ground vertically ( to a depth not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to strip 32x 6 mm size with nuts, bolts , check nuts , washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI medium grade with funnel and wiremesh all as shown in electrical plate No. 5 of SSR -1991 Part I and connecting to arthing test point,main switch board and testing on completion including PCC chamber concrete 1:3:6 type C-2 and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 all asshown in electrical plate in No 5 of SSR(Pt-I)1991 complete all as specified and dirfected by Engineer-in-charge.
Ditto as per srl item no 112 above but with GI earth lead wire of 4mm dia as earth conductor and protection pipe of 15 mm dia for earthing of poles and lightening arrester incl connection with the equipment.
Supply and fixing/laying of galvanized iron strip of size 32x6 mm as earth continuity conductor provided in between earth test point terminal and upto the equipment incl nuts, bolts and washers complete all as specified and directed.
Supply and fixing in replacement of danger notice plate of 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out of flat iron 25x3 mm, nuts-bolts, of approved size for HT 25 x 20 cm and all as directed.
Supply and fixing of Cable route markers made of galvanised iron with embossing of HT Cable or LT Cable, supporting MS angle of 75 cm long, for HT cable route marking duly embedded in and incl PCC (1:3:6) foundation up to 30 cm incl excavation and earth work.
Supply and laying in replacement of HT high voltage insulation mat size 2MX1M made of elastomeric polymers material having a high insulation registance thus imparting total saety to human being from any leakage current having high insulation registance of class A of size 2.5 mm thick and 1 m width suitale for 11 KV confirming to IS-15652 : 2006 including pasting of mat with SR-998 by adding thinner as per requirement complete all as specified and directed.
Supply and laying in replacement of HT high voltage insulation mat size 2MX1M made of elastomeric polymers material having a high insulation registance thus imparting total saety to human being from any leakage current having high insulation registance of class A of size 3.0 mm thick and 1 m width suitale for 33 KV confirming to IS-15652 : 2006 including pasting of mat with SR-998 by adding thinner as per requirement complete all as specified and directed.
Supply and Fix HT insulation tapes ISI Marked for terminating high voltage cables for insulation sealing of connection of wire and cable for bus bar insulation, transformer terminal insulation etc
Supply and Fix in replacement of Fuse wire for HT line from rating 5 Amp to 100 Amp complete all as specified and directed.
Supply and Fix in replacementCross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint
Material and labour for PCC 1:3:6 type C-2,using stone aggregate 40mm graded as in foundation of stays and coping of poles including necessary form work where required and fair finish to the exposed surfaces all as specified & directed.
Material and labour for PCC 1:4:8 type D-2, using stone aggregate 40mm graded as in foundation for electric poles and making of cable duct including necessary form work where required and fair finish to the exposed surfaces all as specified & directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.20 MB
PS181.pdf
Tender Documents • 1.94 MB
BOQ_850440.xls
BOQ • 4.44 MB
Download all tender documents and submit your bid