Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.4 LAccepted-AOC POST OFFICE ROAD DHARMANAGAR DHARMANAGAR NORTH TRIPURA | NORTH TRIPURA | TRIPURA | 799250 | ₹31.4 L | L1 | Accepted-AOC all ok |
| Sl No | Description | Qty | Unit | NIKHIL DAS L1 |
|---|---|---|---|---|
| 1.00Cost of Materials: | ||||
| 2.00 | XLPE CABLE (HT) 3Cx95 sq. mm | 0.22 | KiloMeter- km | 8,00,000 ₹2.1 L |
| 3.00 | Rewireable Porcelain Cut out 300 Amp | 3 | Nos. | 1,400 ₹4,956 |
| 4.00 | 11KV Disc Insulator (45KN). | 90 | Nos. | 150 ₹15,930 |
| 5.00 | 11KV Polymer Pin Insulator | 120 | Nos. | 150 ₹21,240 |
| 6.00 | 11 KV Stay insulator | 42 | Nos. | 55 ₹2,725.80 |
| 7.00 | 11KV Gang Operated Switch (Polymeric type) | 2 | Set | 10,000 ₹23,600 |
| 8.00 | LIGHTINING ARRESTOR 9 KV, 5KA Polymeric L/A | 3 | Nos. | 550 ₹1,947 |
| 9.00 | Stay set complete | 42 | Set | 600 ₹29,736 |
| 10.00 | GI Stay wire stranded stay wire 7-4mm | 0.21 | Metric Ton-MT | 90,000 ₹22,302 |
Tender Value
₹37.2 L
EMD Value
₹74,448
Closing Date
3 Feb 2026, 12:00 pmClosed
The Dy. General Manager, ED- Kumarghat
O/O The Dy. General Manager, ED- Kumarghat, Kumarghat, Unakoti, Tripura
Extension of HT line including installation of 1 X 200 KVA Distribution Sub-Station for providing 3-phase service connection to Mini Tea Processing factory at Machmara Tea Estate under Machmara ADC Village of Pecharthal RD Block.
2026_POWER_69394_1
DGM/ED-KGT/2025-26/13
Open Tender
Electrical Works
90 days
As per NIT
As per NIT
3 documents required · 3 mandatory
₹9,440
Yes
₹74,448
12 Feb 2026
20 Jan 2026
3 Feb 2026
20 Jan 2026
3 Feb 2026
22 Jan 2026
20 Jan 2026 - 21 Jan 2026
Cost of Materials:
XLPE CABLE (HT) 3Cx95 sq. mm
Rewireable Porcelain Cut out 300 Amp
11KV Disc Insulator (45KN).
11KV Polymer Pin Insulator
11 KV Stay insulator
11KV Gang Operated Switch (Polymeric type)
LIGHTINING ARRESTOR 9 KV, 5KA Polymeric L/A
Stay set complete
GI Stay wire stranded stay wire 7-4mm
M.S. ANGLE (65x65x6) mm Angle
M.S. CHANNEL (75x40x40x6) mm Channel
M.S. CHANNEL(100x50x50x6) mm Channel
PCC pole 9m long
11 KV Drop out Switch DOF Polymeric 3ph
11 KV Covered Conductor (70 SQMM)
Aluminium Lugs 95mm sq
LT Grade Armoured Cable, 1Cx120 sqmm
Insulated Tension Mid Span JointRepair Sleeve for 11 kV Covered Conductor 70 sqmm
Insulating Piercing Connector for 11 KV CC to CC 70 sqmm
Non-metallic helical ties for covered conductor 11 KV
Wedge type dead end clamp
11 KV 70 sqmm covered conductor End seal caps, heat or cold shrink type
11 KV Disc insulator Tension Hardware , 45 KN suitable for stringing Covered Conductor inc all accessories
Cost of Erection:- Supply of 60Kg Salt & 55Kg Charcoal ( For 1 Pit).
Laying of one number PVC insulated and PVCsheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Trench Size: Width-350mm, Hieght- 1200mm / Sand(couhioning): Hieght-250mm, Width- 350mm/ Protection: Double layer Bricks Upto 120 sq. mm
Coiling of excess Single/3core/3 /z Core, upto to 400sqmm, HV/MV, XLPE insulated, armoured power Cable direct into earth including excavation of earth upto a depth of 1500mm (Size pit should be 2250mm X 2250mm or as per site requirement.) including 1st class bricx protection of two layer (at brick soling 300 mm. Fine sand (Local quary) for cushioning/bed and refilling and ramming the excavated soil as per direction of Engineer in charge.
Erection of 9.0mtrs length of P.C.C POLE at any kind of soil upto a depth of 1/6 th of pole height, including excavation of earth, refilling the pit with with soil upto the ground level, ramming and making complete in all respect
Erection of Stay set direct in earth complete with 19mm x 1800 mm long stay rod, anchor plate of size 300 x 300 x 8 mm ,thimble, turn buckle, 7/3.15 mm dia G.I Standed stay wire and stain insulator etc. with Supply of M.S.Clamp,Nuts & Bolts etc. as required. and making complete in all respect
Erection of M.S.Angle Cross-Arm,1.0 to 2.5 Mtr.Long 65 x65 x 6 mm ( Excluding the cost of BackClamp, Nuts & Bolts)
Erection of M.S.Channel Cross-Arm,0.3 to 1.2 Mtr.Long75 x40 x 40 x 6 mm ( Excluding the cost of Back Clamp, Nuts & Bolts)
Erection of M.S.Channel Cross-Arm,1.3 to 2.8 Mtr.Long75 x40 x 40 x 6 mm ( Excluding the cost of Back Clamp, Nuts & Bolts)
Erection of 11KV Pin insulator along with Pin.
Erection of 11KV Single Disc insulator set along with necessary fittings
Earthing with G.I pipe 2.5mtr. Long and 40mm dia, including excavation, refilling with alternate layer of salt & Charcoal as per drawing (excluding supply of G.I.Pipe, Salt & Charcoal, Gi wire, nuts &boIts, etc. as required)
Laying of 8 SWG GI wire at 300mm below the ground level for earthing of Sub-Station equipments from the earth electrode
Febrication of Cross-Arms by MS Channel/MS Angle as per specification
Erection of 9KV,5KA single pole metal oxide gapless type LA , including necessary connection complete as per technical specification
Erection of 11KV DOF unit set of three nos. including necessary connection complete as per technical specification.(Excluding the cost of back clamp, Nuts & Bolts)
Erection of 11KV 200 Amp. GOS unit set of three nos. including necessary connection complete as per technical specification. (Excluding the cost of back cIamp,Nuts & Bolts)
Installation/Positioning of 11/0.430KV,3-Phase 200KVA to 250KVA of Distribution Transformer on Pole with necessary connections & fitting fixing of all allied accessories components as required for making complete in all respect for energizing.
Providing Three Phase Service Connection with laying PVC cable from nearby Electrical pole to Premises upto 35mtr. in length supported by G.I.Wire,Reel Insulator i/c fitting fixing of Energy Meter as required
Carriage of 11/0.430, 3-Phase 200KVA/ 250 KVA by Mechanical Transport from the Site / Store/ Worshop to working site Vis-a-vis including loading, unloading and placing on base, as required, a) Upto the lead range 25KM From MMD Store to Sub Division Store
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Trench Size: Width-350mm, Hieght-750mm / Sand(coshioning): Hieght-250mm, Width-350mm/ Protection: Double layer Bricks Above 95 sq. mm upto 185sqmm
Laying of one number PVC insulated and PVCsheathed / XLPE power cable of 11 KV grade of all size in the GI Pipe/HDPE for riser including tieup ofPipe with pole by the help MS Flat Clamp (excludingcost of Clamp and Nut&Bolts) as requiredUp to 400 sq. mm
Supply of febricated clamps of assorted size of MS flat (50 x 6 mm) with double coat of red oxide primercoating
Supply of M.S.Nuts & Bolt i/c Washer of assortedsize ISI Marked machine made
Providing of Pre-cast cement concrete cable identification route marker (1 cement: 2 coarse sand: 4 graded stone aggregate 6mm nominal size) reinforced with 1.6 mm dia mild steel wire including centring and shuttering, roughening cleaning, fixing and finishing in cement mortar 1:3(1cement : 3 fine sand) etc. complete, excluding the plastering of jambs, sills and soffits as per design, drawing and specification of TSECL. The marker snail be embossed "DANGERS: TSECL, ELECTRIC POWER CABLE” with Black colour letter {both side) The visible part shall be painted with Yellow colour japan paint. (1 cement: 2 coarse sand 4 graded stone aggregate 6mm nominal size) reinforced with 1.6 mm dia mild steel wire including centring and shuttering, roughening cleaning, fixing and finishing in cement mortar 1:3(1cement : 3 fine sand) etc. complete, excluding the plastering of jambs, sills and soffits.
Supply of 2.5mtr. Long , 40mm dia G.I.Pipe Make: TATA/ JINDAL)
Supply Erection of S/S Fencing as per Specification
110 mm dia, Wall thickness: minimum-6.5mm, maximum- 7.3mm
Supplying and Making Outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required Up to 150sqmm
Civil work for construction of Transformer base and Fencing of Hard drawn steel wire fabric as per requirement and direction of Engg. In Charge
Stringing of 11 KV coverd conductor 70 sqmm (Weasal) in/c positioning , removing of cable from cable drum etc as required as Technical Specification.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 8.07 MB
Tendernotice_2.pdf
PDF • 0.60 MB
BOQ_70610.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid