EXECUTIVE ENGINEER PWD MALDA ELECTRICAL DIVISION
O/O THE EXECUTIVE ENGINEER PWD MALDA ELECTRICAL DIVISION Singatala Malda PIN 732101
Upgradation of Gazol Rural Hospital to State General Hospital or District Hospital, Gazole RH, Malda - SITC of Fire Detection System.
2026_WBPWD_5014733_1
WBPWD/EE/MED/e-NIQ-27/2026-27
Open Tender
Electrical Work/ Equipment
30 days
Gazole
Please refer Tender documents.
7 documents required · 7 mandatory
₹15,600
29 May 2026
29 May 2026
15 Jun 2026
29 May 2026
12 Jun 2026
5 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable 2 Loops fire alarm control panel ( VDS / UL / FM / ULC/ EN / LPCB approved ) fully networkable with each loop capable of taking minimum 240 devices, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. | ||||||
| 1.01 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. (Approved Make: Edward / Honeywell / Siemens). | 1 | Each | 10 | ₹10 | BI01010001010000000000000515BI0100001114 |
| 2 | Supply, Installation, testing and commissioning of Analog Addressable Intelligent Multi-detector(Heat cum Smoke) ( VDS / UL / FM / ULC/ EN / LPCB approved ) with twist lockable removal base including connections as per specifications complete as reqd and having IP as per recommended standard. (Approved Make: Edward / Honeywell / Siemens). | 107 | Each | 10 | ₹1,070 | BI01010001010000000000000515BI0100001115 |
| 3 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / FM / ULC/ EN / LPCB approved )soft addressable type. (Approved Make: Edward / Honeywell / Siemens). | 10 | Each | 10 | ₹100 | BI01010001010000000000000515BI0100001116 |
| 4 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db) cum strobe (strength of light 10 cd) complete with inbuilt isolator & IP65 base and (VDS / UL / FM / ULC/ EN / LPCB) approved. (Approved Make: Edward / Honeywell / Siemens). | 6 | Each | 10 | ₹60 | BI01010001010000000000000515BI0100001117 |
| 5 | Supply & Laying of 2 Core 1.5 sq.mm FRLS armoured copper Cable (For Loop) (Make. Finolex / RR Kable / Polycab) on the surface of the wall. | 2,000 | Mtr | 10 | ₹20,000 | BI01010001010000000000000515BI0100001118 |
| 6TERMS & CONDITIONS | ||||||
| 7(i) Rate should be quoted inclusive of all applicable taxes and Duties etc including GST. (ii) The Agency must procure the materials for the Manufacturer / OEM or from their authorized sales channel, so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. iii) Documents that authenticate such procurement from the manufacturer /OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work / submission of bill. iv) If any refurbished material is supplied and installed, penal action will be taken as per existing rules. | ||||||