Loading…
Loading…
Tender Value
₹59.6 L
EMD Value
₹1.2 L
Closing Date
12 Oct 2026, 11:00 am
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
ELECT G
15 conditions · 2 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Technical Eligibility Criteria: (a)The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii)Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or (iii)One similar work costing not less than the amount equal to 60% of advertised value of the tender. (b) (1)In case of tenders for composite works (e.g. works involving more than one distinct component, such as Civil Engineering works, S&T works, Electrical works, OHE works etc. and in the case of major bridges - substructure, superstructure etc.), tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works each costing not less than the amount equal to 30% of advertised value of each component of tender, or (ii)Two similar works each costing not less than the amount equal to 40% of advertised value of each component of tender, or (iii)One similar work each costing not less than the amount equal to 60% of advertised value of each component of tender. Note for b(1): Separate completed works of minimum required values shall also be considered for fulfillment of technical eligibility criteria for different components. (b)(2)In such cases, what constitutes a component in a composite work shall be clearly pre- defined with estimated tender cost of it, as part of the tender documents without any ambiguity. (b) (3) To evaluate the technical eligibility of tenderer, only components of work as stipulated in tender documents for evaluation of technical eligibility, shall be considered. The scope of work covered in other remaining components shall be either executed by tenderer himself if he has work experience as mentioned in clause 7 of the Standard General Conditions of Contractor through subcontractor fulfilling the requirements as per clause 7 of the Standard General Conditions of Contract or jointly i.e., partly himself and remaining through subcontractor, with prior approval of Chief Engineer in writing. However, if required in tender documents by way of Special Conditions, a formal agreement duly notarised, legally enforceable in the court of law, shall be executed by the main contractor with the subcontractor for the component(s) of work proposed to be executed by the subcontractor(s), and shall be submitted along with the offer for considering subletting of that scope of work towards fulfilment of technical eligibility. Such subcontractor must fulfill technical eligibility criteria as follows: The subcontractor shall have successfully completed at least one work similar to work proposed for subcontract, costing not less than 35% value of work to be subletted, in last 5 years, ending last day of month previous to the one in which tender is invited through a works contract. Note: for subletting of work costing up to Rs 50 lakh, no previous work experience of subcontractor shall be asked for by the Railway.
In case after award of contract or during execution of work it becomes necessary for contractor to change subcontractor, the same shall be done with subcontractor(s) fulfilling the requirements as per clause 7 of the Standard General Conditions of Contract, with prior approval of Chief Engineer in writing. Note for Item 10.1: Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organisation, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to the date of closing of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
Defination of Similar Work :- (i) Supply, erection, testing and commissioning of water pumping installation.(ii) repair or maintenance of different pumps having capacity 15000 GPH or more(iii) AMC of different pumps having capacity 15000 GPH or more(iv) Supply, erection, testing and commissioning of LT/HT panels
5 conditions · 1 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Tenderers are requested to go through the following documents which are available in upload/View Documents in Home Page of IREPS portal for works tenders before submitting the e-tender. 1. General Instruction for E-Tenders on works contract--Chapter-I 2. Special Condition-General-Chapter-II
1. I/We have visited the works site and I/We am/are aware of the site conditions. 2. We have read the tender Notice[NIT] details, Tender document along with all the conditions attached/referred to, in this tender document, and agree to abide by the said conditions. 3. We are aware of the fact that the railway reserves the right to amend the scope and value of the contract and to reject[or accept] this offer without assigning any financial liability.
The tender document uploaded as "TenderDocument.pdf" should be read in conjunction with the terms and conditions and should read and followed before quoting the tender.
Augmentation of pumping system and allied infrastructure at Barkakana in Dhanbad division.
EL-20-OPEN-2026-27~ECR
EL-20-OPEN-2026-27
Open
Works - General
12 Months
Dhanbad, Jharkhand
₹0
₹1.2 L
18 Sept 2026
18 Sept 2026
28 Sept 2026
39 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 59,59,562.09 | ||
| — | 6.00 | — | — | ||
| Provision (Supply and erection) of Earthing station (RI-7021) as per Drg.No. ETI/ OHE/P/ 7020 or latest (The price shall cover supply and erection of an earth electrode (RI 7021) as per drawing no. ETI/OHE/P/7020. The price shall also cover the provision of a protective concrete Box with removable MS cover. The material should confirm to ACTM vol. II Part II Para 7.1.1 with figure A 3.01. The price shall cover the testing of earth value and painting the value on the earth pit. The earth electrode shall normally be of mild steel galvanized perforated pipe of not less than 44 mm nominal bore and about 3 meter length provided with a spike at one end and welded lug suitable for connecting directly Earth wire/MS flat of required size at other end. The connection of Earth wire/M S flats to each electrode shall be made through M S links by bolted joints, fasteners to be supplied by the contractor. The earth surrounding the electrode shall be chemically treated by alternate layers of fine charcoal and salt at least 150 mm all around. The item should be procured from approved supplier of CORE or RDSO, duly inspected by either RITES or Railway Representative deputed by Sr. Div. Elect..Engineer (G)/ Dhanbad.) | — | — | — | 19,216.62 | |
| — | 900.00 | — | — | ||
| Providing and fixing 06 SWG / 5.0 MM dia GI wire on surface or in recess for loop earthing of street light poles, connection from earth pit to main junction board/panel, connecting different earth pits etc. Connection and Looping of earth wire to be done with suitable fasteners, nuts bolts and washer as required. | — | — | — | 5,931 | |
| — | 4.00 | — | — | ||
| Making of Earthing pit 15' deep with Copper plate of size 600 mm x 600 mm x 3.15 mm with its top from ground level complete with 20 mm dia GI pipe fitted with alternate layers charcoal and salt at least 150 mm thick around, funnel for watering and one earthing lead 20 mm x 5 mm copper strip in GI pipe 30 mm medium gauge, masonry/housing with CI hinged cover plate with locking arrangement complete in all respect. (Copper strip up to ground level to be supplied). (The price shall cover the provision of masonry/housing with CI hinged cover plate with locking arrangement complete in all respect. The price shall cover the testing of earth value and painting the value on the earth pit. The connection of Earth wire/M S/copper strip to each electrode shall be made through copper strip links by bolted joints, fasteners to be supplied by the contractor. The earth surrounding the electrode shall be chemically treated by alternate layers of fine charcoal and salt at least 150 mm all around ) | — | — | — | 24,612.2 | |
| — | 1.00 | — | — | ||
| Installation, testing, commissioning and Supply of V S pump - Motor Set (Vertical Turbine Pump-Motor Set), Make-WPIL,GRW or any other make approved by RailwaySpecification of pump - 50000 GPH x 250 feet head, No of stages-6/8, Water lubricated with Suitable surface discharge assembly with Flanged discharge outlet of water lubricated threaded column and shaft assembly, Complete bowl assembly with strainer, SS line shaft, suitable for sump depth - 40feet, Speed - 1460 rpm. complete in all respect.Specification of Motor - Vertical Hollow Shaft Squirrel cage Induction SPDP Motor 80 kW / 110 HP, Operating at a Synchronous Speed of 1500 rpm, suitable for 3-phase 50Hz, 415 + 10% volts AC power supply, Star Delta Starting and provided with non- reversable rachet and thrust bearing to take pump thrust as per IS:325-1978, complete in all respect.Installation of the Pump set includes minor Civil works for foundation, grouting, fixing of base plate, leveling & alignment etc. | — | — | — | 17,16,852.8 | |
| — | 2.00 | — | — | ||
| Installation, testing and commissioning & supply of HS Pump motor set 15000 GPH x 250 ft. head, 1- stage, Impeller CHS-210 FG 260, Shaft-CSIS- 1570 hot-RLD 40C8- tem (Deg-C) Ambient capacity 68. 19M3/Hr NPSHR Flooded efficiency -58%, Motor Rating: 30 KW nominal RPM- 1470, horizontal foot mounted TEFC sq. cage induction motor with class '1' insulation SI duty, & IP- 55 protection IS- 325, Power supply: 415V + 10%, 50 HZ + 5%, 3- Phase, AC (Make: Kirloskar, KSB, Beacon, Grundfos) Installation of the Pump set includes minor Civil works for foundation, grouting, fixing of base plate, leveling & alignment etc. | — | — | — | 5,31,997.44 | |
| — | 3.00 | — | — | ||
| Installation, testing, commissioning and Supply of HS Pump Motor Set DSM 100/36, Make - Kirloskar, 30000 GPH , head- 250feet, double stage, with Impeller CI IS 210-FG260, Shaft-CS IS 1570-HOT RLD 40C8, Casing-CI IS 210-FG260, Suction / delivery size - 125mm/100mm Motor Rating: 45 kW / 60 HP, Efficiency : 72%, Horizontal foot mounted TEFC Sq.cage induction motor with F class insulation, S1 duty & IP 55 Protection, IS325, Power Supply 3-Phase AC 415V+ 10%, 50 HZ, Nominal RPM- 1470, 4Pole Complete with Base plate and foundation bolts, coupling & coupling guard, Sluice Valve-1 no, Non Return Vlave- 1 no. Installation of the Pump set includes minor Civil works for foundation, grouting, fixing of base plate, leveling & alignment etc. | — | — | — | 15,66,800.01 | |
| — | 2.00 | — | — | ||
| Installation, testing, commissioning and Supply o f Automatic Star/Delta starter capacity 150/170HP containing 200A power contactor havells/BCH make with over load relay setting range 100 to 150, CT mounted with all protection like under voltage, single phasing preenter, suitable copper busbar, ammeter, voltmeter 0-500V on/off, push button, LED indication RYB, 320Amp TPN switch with internal wiring complete set and suitable CT selector switch both for volt & ammeter with box( Make-Havells, L&T, BCH. Encloser Make-S.S Company | — | — | — | 1,93,544 | |
| — | 3.00 | — | — | ||
| Installation, testing, commissioning and Supply of Automatic star delta starter capacity 100 HP, 415 V, AC with all protection containing Voltmeter, Ammeter, Dry running preventer, Single phase preventer and over load protection through current sensing with suitable relay, indication lamp, TPN MCCB of suitable rating, suitable CT etc. including wiring and suitable Busbar complete in all respect panel board. make Havells/ BCH/ L&T/ CG/Siemens | — | — | — | 2,94,205.56 | |
| — | 2.00 | — | — | ||
| Installation, testing, commissioning and Supply of Fully Automatic Star Delta Starter 80/75 HP, Relay Range 66-110 Amp for Motor Rating AC-3 Duty, 415V, 50Hz, 3-phase, in Sheet enclosure, with all protection containing Voltmeter, Ammeter, Dry running preventer, Single phase preventer and over load protection through current sensing, indication lamp, TPN MCCB of suitable rating, suitable CT etc. including wiring and suitable Busbar complete in all respect panel board. make Havells/ BCH/ L&T/ CG/Siemens | — | — | — | 1,25,993.12 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing & commissioning of Floor mounted LT Panel (415V AC, 3Ph, 4-wire, 50 Hz with IS tolerance) consisting with MCCB-400A 4P,50KA, with Microprocessor Based release - 1 set as Incoming and MCCB-200A,4P,50KA, with TM Release - 4 Sets, MCCB-100A,4P, with TM Release - 2 Sets as outgoing. Degree of protection: IP-54, made of CRCA steel sheet (load bearing member- 2mm thick, non load bearing member - 1.6mm thick, gland plate - 3mm thick), Powder coated paint finish with necessary surface pretreatment @40<45@70 microns), Copper Busbar for phase & neutral - 50mm x 10mm size and for earth - 50mm x 6mm size, covered with PVC coloured coated heat shrinks sleeves, Bottom cable entry with glands, (Make: LT Panel- Authorised system house of L&T, C&S, Schnaider, MCCB & its accessories - L&T, C&S, Schnaider, CT, Indicating lamps, Selector switches etc - ISI Approved) Details of incoming / outgoing feeders as follows:Incoming: MCCB-400A , 4P,50KA, with Microprocessor Based release MTX2.0, DN3-400N with DN3-630 Spreader Terminals-4 pole for DN dsine MCCB-External, Aux 1 C/O +TAC 1 C/O -Right for DU/DN2, DN3,DN4 dsine MCCB-internal, DU/DN3 Extended rotary Handle for Dn dsine MCCB- External, Resin cast Current transformer 400/5A 15VA, CL-1.0, Metering (03 Nos), Multifunction LED meter with RS485, 90-300V, AC/DC, AC-1,size-96x96, LED Ammeter 1Ph, AC-1,80-300V Ac, Size- 96x96, LED Voltmeter 1Ph, AC-1,80-300V Ac, Size-96x96, Ammeter Slector Switch, 6A, 4 position line current with off with CT, OFF-R-Y-B, Voltmeter selector switch10A, Voltage between phasses with off 4 position, LED indicating lamp Gen next 16mm, suitable for operating at,240V Ac (Red, Yellow, & Blue), MCB 6A, 2P, 10KA, c-curve -01No, MCB 6A, 3P,10KA, c-curve -01 No, MCB 4A, 3P,10KA, c-curve MCB-01 No = 1 Set Outgoing: MCCB-200A, 4P, 50KA, dsine MCCB with TM Release, DN2-250N, with Acc Spreader Terminal DN 2 -250A 4P for MCCB-External, Ti panel, Aux 1 C/O + TAC 1 C/O- Right, for DU/DN2, DN3, DN3, DN4 dsine MCCB internal, DN2, Extended Rotary Handle for DN dsine MCCB External, Resin cast Current Transformer 200/5A,10VA, CL-1.0,Metering (03 Nos), LED Ammeter, 1Ph, Ac-1, 80-300V AC, Size-96x96, Ammeter Slector Switch, 4 Position line current 6A, with off with CT, OFF-R-Y-B, LED indicating lamp Gen next 16mm, suitable for operating at,240V Ac (Red, Yellow, & Blue), MCB 6A, 2p, 10KA, C-Curve = 04 Sets Outgoing: MCCB-100A, 4P, dsine MCCB with TM Release, DN2-250N, with Acc Spreader Terminal DN 2 -250A 4P for MCCB-External, Ti panel, Aux 1 C/O + TAC 1 C/O- Right, for DU/DN2, DN3, DN3, DN4 dsine MCCB internal, DN2, Extended Rotary Handle for DN dsine MCCB External, Resin cast Current Transformer 100/5A,10VA, CL-1.0,Metering (03 Nos), LED Ammeter, 1Ph, Ac-1, 80-300V AC, Size-96x96, Ammeter Slector Switch, 4 Position line current 6A, with off with CT, OFF-R-Y-B, LED indicating lamp Gen next 16mm, suitable for operating at,240V Ac (Red, Yellow, & Blue), MCB 6A, 2p, 10KA, C-Curve = 02 Sets | — | — | — | 3,84,982.74 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing & commissioning of Floor mounted LT Panel (415V AC, 3Ph, 4-wire, 50 Hz with IS tolerance) consisting with MCCB-630A 4P,50KA, with Microprocessor Based release - 1 set as Incoming and MCCB-250A,4P,50KA, with TM Release - 4 Sets, MCCB-200A,4P,50KA, with TM Release - 4 Sets as outgoing. Degree of protection: IP-54, made of CRCA steel sheet (load bearing member- 2mm thick, non load bearing member - 1.6mm thick, gland plate - 3mm thick), Powder coated paint finish with necessary surface pretreatment @40<45@70 microns), Copper Busbar for phase & neutral - 50mm x 10mm size and for earth - 50mm x 6mm size, covered with PVC coloured coated heat shrinks sleeves, Bottom cable entry with glands, (Make: LT Panel- Authorised system house of L&T, C&S, Schnaider, MCCB & its accessories - L&T, C&S, Schnaider, CT, Indicating lamps, Selector switches etc - ISI Approved) Details of incoming / outgoing feeders as follows:Incoming-: MCCB-630A , 4P,50KA, with Microprocessor Based release MTX2.0, DN3-630N with DN3-630 Spreader Terminals-4 pole for DN dsine MCCB-External, Aux 1 C/O +TAC 1 C/O -Right for DU/DN2, DN3,DN4 dsine MCCB-internal, DU/DN3 Extended rotary Handle for Dn dsine MCCB- External, Resin cast Current transformer 600/5A 15VA, CL-1.0, Metering (03 Nos), Multifunction LED meter with RS485, 90-300V, AC/DC, AC-1,size-96x96, LED Ammeter 1Ph, AC-1,80-300V Ac, Size- 96x96, LED Voltmeter 1Ph, AC-1,80-300V Ac, Size-96x96, Ammeter Slector Switch, 6A, 4 position line current with off with CT, OFF-R-Y-B, Voltmeter selector switch10A, Voltage between phasses with off 4 position, LED indicating lamp Gen next 16mm, suitable for operating at,240V Ac (Red, Yellow, & Blue), MCB 6A, 2P, 10KA, c-curve -01No, MCB 6A, 3P,10KA, c-curve -01 No, MCB 4A, 3P,10KA, c-curve MCB-01 No = 1 Set Outgoing: MCCB-200A, 4P, 50KA, dsine MCCB with TM Release, DN2-250N, with Acc Spreader Terminal DN 2 -250A 4P for MCCB-External, Ti panel, Aux 1 C/O + TAC 1 C/O- Right, for DU/DN2, DN3, DN3, DN4 dsine MCCB internal, DN2, Extended Rotary Handle for DN dsine MCCB External, Resin cast Current Transformer 200/5A,10VA, CL-1.0,Metering (03 Nos), LED Ammeter, 1Ph, Ac-1, 80-300V AC, Size-96x96, Ammeter Slector Switch, 4 Position line current 6A, with off with CT, OFF-R-Y-B, LED indicating lamp Gen next 16mm, suitable for operating at,240V Ac (Red, Yellow, & Blue), MCB 6A, 2p, 10KA, C-Curve = 04 Sets Outgoing: MCCB-250A, 4P, 50KA, dsine MCCB with TM Release, DN2-250N, with Acc Spreader Terminal DN 2 -250A 4P for MCCB-External, Ti panel, Aux 1 C/O + TAC 1 C/O- Right, for DU/DN2, DN3, DN3, DN4 dsine MCCB internal, DN2, Extended Rotary Handle for DN dsine MCCB External, Resin cast Current Transformer 250/5A,10VA, CL-1.0,Metering (03 Nos), LED Ammeter, 1Ph, Ac-1, 80-300V AC, Size-96x96, Ammeter Slector Switch, 4 Position line current 6A, with off with CT, OFF-R-Y-B, LED indicating lamp Gen next 16mm, suitable for operating at,240V Ac (Red, Yellow, & Blue), MCB 6A, 2p, 10KA, C-Curve = 04 Sets | — | — | — | 6,58,606.67 | |
| — | 2.00 | — | — | ||
| Fixing, connection, testing & Supply of Off load Change Over switch 400 A, 4 Pole . (Fixing of Change over switch to be done as per the site requirement and connection to be done with suitable supply of PVC flexiable pipe) make-HAVELLS,Standard, Indoasian, ABB,C&S ,L&T. | — | — | — | 50,832.28 | |
| — | 2.00 | — | — | ||
| Testing, commissioning, installation & Supply of Off load Change Over switch 800 A, 4 Pole .Fixing to be done as per the site requirement under supervision of site incharge including connection with crimping of cable ends with aluminium lugs of required sizes (make-HAVELLS,C&S, Standard or L&T.) | — | — | — | 1,04,597.5 | |
| — | 170.00 | — | — | ||
| ISI marked four core circular armoured cross linked polyethylene (XLPE) LT insulateed cable. PVC outer sheathed armoured with galvanised round steel wire or steel strip and with aluminium conducter suitable for rated voltage 1100 volts, grade conforming to IS:7098 [part-1]- 1988 with admt. no. 1,2 and 3 [reaffirmed 2005] size 4*120 sq. mm. The firm will have to submit type test report as per IS from NABl accredited lab alongwith the tender. Type test report should not be more than 10 years old on the date of bid opening. | — | — | — | 96,730 | |
| — | 150.00 | — | — | ||
| ISI marked four core circular armoured cross linked polyethylene (XLPE) LT insulateed cable. PVC outer sheathed armoured with galvanised round steel wire or steel strip and with aluminium conducter suitable for rated voltage 1100 volts, grade conforming to IS:7098 [part-1]- 1988 with admt. no. 1,2 and 3 [reaffirmed 2005] size 4*185 sq. mm. The firm will have to submit type test report as per IS from NABl accredited lab alongwith the tender. Type test report should not be more than 10 years old on the date of bid opening. | — | — | — | 1,51,279.5 | |
| — | 120.00 | — | — | ||
| Trenching, laying and back filling of XLPE cable as per Sr.DEE(G)/DHN's drg. No. EL/486-01 (cable will be supplied by the Railway) | — | — | — | 7,495.2 | |
| — | 100.00 | — | — | ||
| Laying and fixing PVC/XLPE cables of different sizes ranging from 25 sq mm to 120 sq mm on surface of the wall (normally concealed)/steel structure as per the requirement of site with proper clamping arrangement as required at every 1/2 metre. (Cable will be supplied by Railway) | — | — | — | 4,917 | |
| — | 1.00 | — | — | ||
| Supply and Installation of Chain Pulley Block of Capacity: 5 Ton with 6 m long chain, Load Chain dia. 10 mm, No. of fall: 2, Nos. of Load Chain: 02, Make: Indef, BEMCO, KEPRO or similar. | — | — | — | 13,630.85 | |
| — | 0.10 | — | — | ||
| Supply, fabrication, laying, welding and connection of GI Flat of size 25/32/40 mm x 6mm from earth pit with GI nut Bolt suitable size. | — | — | — | 7,337.6 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocuments.pdf
ATTACHMENT
GCCApril-2022.pdf
ATTACHMENT
GCCCorrectionslip1to11_compressed.pdf GCC Correction slip
ATTACHMENT
GCCCorrectionslip1to11_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .