Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.8 LAccepted-AOC KARUKAPPILLY THATTATHUKUDIYIL BUILDING KOLENCHERY 682311 | KOLENCHERY | ERNAKULAM | KERALA | 682311 | L1 | Accepted-AOC First Lowest | |
| 2 | L2₹16.3 L+₹45,869.69 (2.90%)Rejected-AOC CHAKKALAKKAL H KOTTAT P O | L2 | Rejected-AOC Second Lowest | |
| 3 | L3₹16.4 L+₹56,238.56 (3.56%)Rejected-AOC | L3 | Rejected-AOC Third Lowest |
Tender Value
₹16.4 L
EMD Value
₹40,917
Closing Date
29 Aug 2022, 3:00 pmClosed
Regional Engineer
REGIONAL ENGINEER KERALA STATE NIRMITHI KENDRA COCHIN DEVASWOM BOARD BUILDING ROUND NORTH THRISSUR 1 PH No 04872322654 8111882867
Electrification works for DRRF Unit Glass waste sorting facility and existing building
2022_KSNK_504334_1
KSNK/TECH/THRS/CDVT-123R2/2022
Open Tender
Electrical Works
Item Rate
30 days
Velakkode Estate
Refer NIT
5 documents required · 5 mandatory
₹2,500
₹40,917
Yes
27 Sept 2022
20 Aug 2022
31 Aug 2022
20 Aug 2022
29 Aug 2022
20 Aug 2022
20 Aug 2022 - 29 Aug 2022
Amount
90.2.2.8 : Supply and wiring points according to IS 732-1989 through the existing conduit with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (Group B/ RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - medium point
90.2.2.9; Twin control light point with 6A, 3 plate ceiling rose -Medium point
90.2.2.10; Single control light point without ceiling rose - Medium point
90.2.2.11; Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Medium point
90.2.2.18 ;Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator - Long point.
90.2.2.12 ;Call bell point with 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end - Medium point
90.2.2.13 ;Combined plug point with 6 A, 5 pin plug socket controlled by 6 A switch in the same switch board as that of light points.
90.2.2.14 ;Independent Plug - Medium Point
90.3.20.3 : Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
90.3.21.3 : Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture
90.3.21.4 : Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 2X20W LED Lamp with box type fixture
Supply Conveyance, installation, testing and commissioning of 40W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
Supply Conveyance, installation, testing and commissioning of 70W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
1.58 : Supplying and fixing PVC batten/ angle holder including connection etc. as required.
Supply and providing the following types and power rated lamps in the existing fittings as required.7/9W LED
od ; Supply and fixing shades of the following types of shades on existing batten / pendent/bracket fittings as required
1.22 ;Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required.150 mm X 75 mm X 60 mm deep
90.5.1.3. ;Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
90.3.18.2 ;Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.- 32 mm dia with clamps made from 20 x 3 mm MS flat
90.3.18.3 ;40 mm dia with clamps made from 20 x 3 mm MS flat
90.15.4.1 ; Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.1 ; Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.1 ; Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
od ;Supply and fixing LED Bulk Head fitting 12W (LukerLBKDVSL-12/equivlent make to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required.
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), 300mm down rod , 2 number canopies, shackele kit, Copper winding, 3 number blades and all remaining accessories including safety pin, nut bolts, washers suitable for 230V/240V single phase AC supply etc. complete as required
1.48 ; Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to th
90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.4.9 : Charges for cutting holes suitable for accommodating exhaust fans 305mm sweep to 450mm including plastering colour washing etc. as required.
90.4.10 ; Conveyance, installation , testing and commissioning of exhaust fans of size up to 450mm in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
od- Supply installation of 150mm sweep Light duty Exhaust fan in plastic body with self opening lowers working on 230V single phase AC
od ;Supply of 380mm heavy duty 900rpm almonord/equivlent make exhaust fan complete with standard acesaries etc as required
90.4.6 ;Conveyance, installation, testing and commissioning of wall mounting fans of all types using mounting brackets supplied along with the fan.
od ;Supply of wall mounted heavy duty 450 mm Air circulator ,1440 rpm having discharge of 9000M3/miniute complete with accessories etc as required
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4Module
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch(group controle )
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.33- Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
90.6.10.1 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm
90.6.10.2 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm
90.6.10.3 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required32 mm
90.9.9.1 ;Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.9.1 ;Supply and fixing100x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100x50mm Cable Management System with base and lid
Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 2 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 3 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 4 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 6 Run
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 8 Run
1.17.2 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm
1.17.4 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm
1.17.11 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.17.13 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm
1.17.15 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.20 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
1.17.22 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.31 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
90.6.4.54 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 10 sq. mm
90.16.2.4Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.40mm
90.11.1.16 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43
90.11.1.11 ;Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
od8298/2021_2022 : Supplying and fixing 4P sheet steel enclosure on surface/ recess complete with connections, testing and commissioning etc. as required.
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
od ;Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof 8 way three phase enclosure of SMDB, double door including 250A copper /brass bus bar,with provision for 4 pole MCCB as incommer and TP MCCB as out going etc. fixed on wall/floor using suitable anchor bolts, making good the damages, colour washing etc. as required.
od ;Supply and providing cable alley (top&bottam ) 8 way double door
od ;Supply and providing metering module 8 way double door with multi function meter ,phase indication lamp space for ELR etc as required
od ;Supply and providing bottom cable box suitable for 8 way double door
od ;Supply and providing corner box suitable for 8 way double door
90.14.2.2 : Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.5 : Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.1.1.1Supply and fixing one number earth fault Relay up to 125A with CBCT.
90.14.11.12 : MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
od1347681/2021_2022S& F spreader terminal upto 125A MCCB
S & F Enameled Danger Notice Board of size 250 x 200 mm. with inscriptions ( both in English andMalayalam) and conventional Skull and Bone in Red colour.
90.14.24.1 :1 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
90.14.24.5 : 5 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
90.14.24.3 : 3 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
od253718/2020_2021 : Supplying, installing, testing and commissioning of following capacity TPN with enclosure box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing wall /frame work .<br> 32 A TPN SDF with 25A HRC fuse
od253718/2020_2021 : Supplying, installing, testing and commissioning of following capacity TPN with enclosure box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing wall /frame work .<br> 63 A TPN SDF with 40/50A HRC fuse
od Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1 sq mm 1 run as controle wiring
90.12.7.39 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required..4 core 6 sq mm with factory made clamp (7.5HP motor )
90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp(V DB&15hp,glass unit,existing building)
90.12.7.41 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp(20hp )
90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 4 sq mm with factory made clamp (2/3 HP motor )
90.12.7.29 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm with factory made clamp
90.12.5.40 ; Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
90.12.5.40 ; Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5core 95 sq mm
90.12.9.2 ; Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.12.9.3 ;Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size77/63 mm or nearest size
9.1.1 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4/6 sq. mm
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4x10 sq. mm (35mm)
9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 95 sq. mm (35mm)
od : Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required(.4sqmm-16 sq mm with 12 mm wide x 1 mm thick clip)
od : Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required.(25 sq - 95sq mm with 20 mm wide x 1.20 mm thick clip)
Supply of 1 H.P,Single phase open well submersible motor pumpset suitable for operation of 230V,50Hz a.c. supply having 8 mtrs to 22 mtrs head range , capable of discharge 12600/Hr of clear water at 16 Mtrs head (Kilosker KOSM 123/equivlant make Akash/Texmo/Deccan) etc as requird .
Supply and providing submersible motor controller suitable for 1 H.P.Submersible motor pump wihtin built water level controle including Ammeter,Volt meter etc L&Tmake MR-G2W/equivlent make .
od Supply and providing 25/32 mm heavy duty duro flex/canoflex PVC flexible pipe as delivery pipe
od ; Supply and providing special make SS connector with steel clamp suitable for 25/32 mm PVC fexible pipe.
od ; Supply and providing 32 mm dia . G.I. pipe ( B class) complete with standard accessaries including clamping on wall etc as delivery line
od ; Supply and providing 32 mm dia brass ball valve (Zoloto /kirlosker/equivlent )
od ; Supply and providing 32 mm dia brass reflex/nonreturn valve Zoloto /kirlosker/equivlent )
od ; Supply and providing 16 mm submarine blue make Polypropelyne Rope for hanging the motor pump
od ;Charges for installation of 1 H.P. ,3 phase submersible motor pumpset into well after connecting the delivery pipes, and lead cable to motor and hanging the unit on rope and setting into trouble free operation and conducting trail run satisfactorily.
Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.4 sq mm
90.6.5.11 Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm(For WLC probe)
90.16.1.1 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.1.2 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.4 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 4.00 mm copper conductor ( 8 SWG)
90.16.5.1 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.2 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.4 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00mm (8 SWG)
od17351/2021_2022 : Supply and providing brass bolt and nut 12x3mm
od17355/2021_2022 : Supply and providing brass bolt and nut 25x6mm
4.1.4 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
4.1.6 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.450 mm width X 50 mm depth X 1.6 mm thickness
5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
od; Supply and provding test joint for earthing system using 2 nos of the following strips including cutting andbending to shape ,drilling necessary holes and fixing to the watering pipe etc as required .2x25x6 mm GI strip
5.15; Supply and providing25x6 mm GI strip as earth lead including cutting and bending to shape ,drilling necessary holes and fixing etc as required
90.16.3.2Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required 25 x 3 mm GI strip
90.16.4.3 Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run)25 x 6 mm GI strip
1.49 Numbering of ceiling fan /light fittingetc with white em=namel paint etc as required
od; Supplying and installation of supports, anchor bolts etc made out of suitable flats etc as required including painting with 2 coats of synthetic enamel paintsize single section MS angle,
14.2 : Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres.
14.7 : Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.11 : Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12.1 : Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
od Supply and providing 6 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps includingfixing it to wall as required
od Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of redoxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with finesand, painting the bracket/ floor stand including making good the damages, colour washing etc. as
od Supply and providing First Aid Chart ( Shock Treatment Chart ) PVC laminated /duly framed and placedin a conspicuous location for clear vision.
od Supply and providing 2 mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 towithstand 3.3 KV dielectric strength.
90.14.1.1 Fabrication, supply, conveyance, installation of feeder pillor box using 2.00mm CRCA sheet, powder coated floor mounting, dust and vermin proof, cubicle type KSEB meter box for fixing KSEB meter,Cutouts,neutral link, TPN etc. Fabrication of fully partitioned, dust and vermin proof enclosure for metering CT including seperate locking arrangemnts, vision providion for metering facilities,panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, hinged doors for switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. An additional canopy for the board should also be provided .The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.
2.1.5 Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.160A TP&N
od Supply and providing 160A DIN type fuse unit with 125A HRC fuse (L&T SK91051/equivlent make
Supply and providing 100A N/L mounted on DMC/ SMC base
Preparing completion & test certificates for KSEB connection
GTIS TELECOM AND CIVIL CONTRACTORS PVT LTD
BIJU JOSE
Bidder Name
Power Care Electrical
GTIS TELECOM AND CIVIL CONTRACTORS PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .