| 1 | L1₹18.5 LAccepted-AOC NORTH BEYPORE CALICUT 15 KERALA | KOZHIKODE | KERALA | 612906 | L1 | Accepted-AOC L1 | |
| 2 | L2₹19.5 L+₹93,321.40 (5.04%)Rejected-AOC | L2 | Rejected-AOC L2 |
| Sl No | Description | Qty | Unit | gopakumar.kv L1 | ASWATHI ELECTRICALS L2 |
|---|---|---|---|---|---|
| 1.00Electrification | |||||
| 1.00 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS
PVC insulated copper conductor single core cable etc as required.Group C | 5 | point | 1,480 ₹7,400 Lowest | 1,550 ₹7,750 |
| 1.00 | 1.55.3:Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C | 3 | point | 850 ₹2,550 Lowest | 900 ₹2,700 |
| 1.00 | OD59355/2025-2026:Supply, conveyance, installation, testing and commissioning of recess-mounted LED panel luminaire of size 600 × 600 mm (2 ft × 2 ft) for indoor application, having minimum luminous flux 3600 lumens, rated efficacy not less than 120 lm/W, power consumption about 30 W, power factor ≥ 0.90, CCT 6500 K, CRI ≥ 80, beam angle about 120°, and surge protection up to 4 kV (common and differential mode), with steel housing, opal / polycarbonate diffuser and IP20 protection. The luminaire shall have a rated life of minimum 50,000 hours (L70B50) and shall be suitable for recessed mounting in modular false ceiling. The scope shall include cutting of ceiling wherever required and making good after installation, complete in all respects.
Make: Philips RC380B LED36S-6500 G6 L60W60 PSU OD or equivalent, approved by the Engineer-in-Charge. | 36 | each | 4,850 ₹1,74,600 Lowest | 5,400 ₹1,94,400 |
| 1.00 | OD185139/2025-2026:Supply, Conveyance, installation, testing and commissioning of led recess mounting type LED 300*300 mm(1x1) Luminaire having light output not less than 1800 Lumens with System efficacy> 100 Lumen/Watt . Luminaire Housing Shall be made from single piece CRCA body without welding to avoid rusting and Prismatic diffuser to reduce glare. The Luminaire should be having minimum 30000 Burning hours with CRI ?80, SDCM<5 and Co-related color temperature (CCT) of 6500K.The luminaire must have 2.5KV surge protection integrated in driver, Ripple<5%,UGR<19, PF?0.95, Total harmonic distortion THD?10%,EMI/EMC Compliant and Operating voltage range 140-270V with High voltage cutoff@325 ± 15V with Auto restart feature. Luminaire and driver shall be separately BIS approved of same make . Type Test certificate and Bis certificate need to be submitted for approvals
make PHILIPS, TYPE: RC360B LED18S-6500 L30W30 PSU OD SG, /equivalent | 12 | each | 2,100 ₹25,200 Lowest | 2,200 ₹26,400 |
| 1.00 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply | 27 | each | 2,200 ₹59,400 Lowest | 2,250 ₹60,750 |
| 1.01 | OD59663/2025-2026:Supply, conveyance, installation, testing and commissioning of 450 mm sweep wall mounting fan, fully metal body, suitable for continuous indoor operation, complete with all accessories and mounting hardware, including down-rod/bracket, safety clamp and electrical connections, finished and commissioned in all respects. Make: Orient ? Tornado Wall II or equivalent, approved by the Engineer-in-Charge. | 11 | each | 4,500 ₹49,500 | 4,450 ₹48,950 Lowest |
| 1.01 | 1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) | 24 | each | 300 ₹7,200 Lowest | 315 ₹7,560 |
| 1.01 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) | 3 | each | 320 ₹960 Lowest | 349 ₹1,047 |
| 1.01 | 1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) | 1 | each | 400 ₹400 Lowest | 424 ₹424 |
Tender Value
₹18.6 L
EMD Value
₹50,000
Closing Date
9 Mar 2026, 4:00 pmClosed
Executive Engineer
PWD ELECTRICAL DIVISION KOZHIKODE
GENERAL Setting up of Seminar hall Providing Centralised online facility centre Model poly Vadakara General Electrical Work
2026_PWD_843484_1
PWD/BLDG/18871/2025-2026
Open Tender
Electrical Works
Item Rate
KOZHIKODE
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹50,000
25 Jun 2026
4 Mar 2026
11 Mar 2026
4 Mar 2026
9 Mar 2026
4 Mar 2026
Electrification
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.55.3:Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
OD59355/2025-2026:Supply, conveyance, installation, testing and commissioning of recess-mounted LED panel luminaire of size 600 × 600 mm (2 ft × 2 ft) for indoor application, having minimum luminous flux 3600 lumens, rated efficacy not less than 120 lm/W, power consumption about 30 W, power factor ≥ 0.90, CCT 6500 K, CRI ≥ 80, beam angle about 120°, and surge protection up to 4 kV (common and differential mode), with steel housing, opal / polycarbonate diffuser and IP20 protection. The luminaire shall have a rated life of minimum 50,000 hours (L70B50) and shall be suitable for recessed mounting in modular false ceiling. The scope shall include cutting of ceiling wherever required and making good after installation, complete in all respects. Make: Philips RC380B LED36S-6500 G6 L60W60 PSU OD or equivalent, approved by the Engineer-in-Charge.
OD185139/2025-2026:Supply, Conveyance, installation, testing and commissioning of led recess mounting type LED 300*300 mm(1x1) Luminaire having light output not less than 1800 Lumens with System efficacy> 100 Lumen/Watt . Luminaire Housing Shall be made from single piece CRCA body without welding to avoid rusting and Prismatic diffuser to reduce glare. The Luminaire should be having minimum 30000 Burning hours with CRI ?80, SDCM<5 and Co-related color temperature (CCT) of 6500K.The luminaire must have 2.5KV surge protection integrated in driver, Ripple<5%,UGR<19, PF?0.95, Total harmonic distortion THD?10%,EMI/EMC Compliant and Operating voltage range 140-270V with High voltage cutoff@325 ± 15V with Auto restart feature. Luminaire and driver shall be separately BIS approved of same make . Type Test certificate and Bis certificate need to be submitted for approvals make PHILIPS, TYPE: RC360B LED18S-6500 L30W30 PSU OD SG, /equivalent
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD59663/2025-2026:Supply, conveyance, installation, testing and commissioning of 450 mm sweep wall mounting fan, fully metal body, suitable for continuous indoor operation, complete with all accessories and mounting hardware, including down-rod/bracket, safety clamp and electrical connections, finished and commissioned in all respects. Make: Orient ? Tornado Wall II or equivalent, approved by the Engineer-in-Charge.
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.56:Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface
90.10.1.6:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )8 module moulded plastic box on surface
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.28.4:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
1.28.5:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.57:Supplying & fixing suitable size Gl box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. lCD
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
1.17.33:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 6 sq. mm
90.12.24.3:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.6 Sq mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.10:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Joint cover
90.9.2.2:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable devider
90.9.2.3:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree
90.9.2.4:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 degree
90.9.2.5:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree
90.9.2.7:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat cross
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.1.2:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree
90.9.1.3:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 Degree /Tee
90.9.1.4:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree
90.9.1.5:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal coupler
90.9.1.6:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat Cross
90.9.1.7:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.1.9:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Joint cover
90.9.2.13:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.4 to 5 module mounting box
90.11.1.16:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.12:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+24) - three phase double cover (IP 42/43)
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, Double door
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
OD62660/2025-2026:Supplying and fixing 4P sheet steel enclosure suitable for fixing RCCB/Isolator on surface/ recess complete with all accessories,good the damages,colour washing etc. as required.
90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.12:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
2.2.14:Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 125 Amp, 36 KA
OD192267/2025-2026:Supplying, Testing, Commissioning and Fixing OF 3 Phase 4 Pole 100A Isolation duty MCCB of following rating in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD160597/2025-2026:MCCB Accessories- supply and fixing spreader terminals for MCCB up to 125amps 8 pieces L &T cat no CM97921OOOO or Techno commercial equivalent approved by engineer in charge
OD160598/2025-2026:MCCB Accessories Supply and fixing spreader links for MCCB from 125A to 250 A, 4 pole MCCB -(8 pieces) in the existing MCCB L&T cat number CM92007OOOO or Techno commercial equivalent approved by engineer in charge
2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
OD76704/2025-2026:Supply and providing and fixing 63 A TPN disconnector fuse switch unit in sheet steel enclosure with ISI marked HRC fuses on wall/angle iron frame including drilling holes in frame, making connections, etc. as required.
OD160378/2025-2026:Supply, providing and fixing 160A, 4 pole On-Load Change Over Switches unit inside the CRCA cubicle box including drilling holes in cubicle panel, making connections, etc. as required.
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
90.12.7.30:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm
90.12.7.31:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.24:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.25:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
4.1.3:Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD160386/2025-2026:Supply and fixing 125/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT
OD73208/2025-2026:Supply and fixing 150/5 A, 5 VA, accuracy class 1, Tape wound Metering CT
OD73212/2025-2026:Supply & fixing Digital Multi function meter to read: V, A, F, PF-3 phase accuracy class 1 LED in the panel assembly and giving connections as required
OD147537/2025-2026:Supply and fixing Earth fault relay upto 125-200A with CBCT.
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
OD73213/2025-2026:Supply and fixing LED indicators for all voltage ranges- Red, Yellow, Blue colour.
OD181301/2025-2026:Supplying and fixing 160 A HRC Fuse with HRC Fuse link with connections, in existing meter board
OD181302/2025-2026:Supplying and fixing 100 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board
OD79647/2025-2026:Supply, installation, testing and commissioning of tubular type lead-acid battery, suitable for UPS application, 12 V, 100 Ah (C20 rated), complete with battery rack, DC interconnecting cables, battery inter-links, terminals and all accessories required for installation and commissioning. The scope shall also include supply of approved battery-grade distilled water . The battery shall carry a minimum warranty of four (4) years. Make: Exide / Quanta / Panasonic / or techno-commercially equivalent, approved by the Engineer-in-Charge.
OD79648/2025-2026:Supply, installation, testing and commissioning of a 15 kVA, 240 V true-online UPS, IGBT based, microprocessor controlled, double-conversion VFI (VFI-SS-111) technology, configurable for three-phase input and three-phase output, suitable for indoor installation (minimum IP-20), with pure sine-wave output and rack / tower configuration. The UPS shall have input power factor > 0.99, high efficiency (up to 96%), wide input voltage and frequency operating range, low input current distortion, auto-bypass and maintenance bypass facility, emergency power-off (EPO), comprehensive protections against overload, short-circuit, over-voltage and internal faults, and automatic battery charging . The UPS shall be provided with a user-friendly LCD display for real-time indication of input/output parameters, load and alarm status, and suitable size battery stand .The UPS shall conformg to ISO 9001:2008, 14001: 2004, CE Certifications & EN/IEC 62040- 1, EN/IEC 62040-2 & EN/IEC 62040-3 standards and EN/IEC 620404/PEP Certification. Minimum three (3) years on-site warranty shall be provided for the UPS. Make: Numeric-Legrand / Delta/Eaton or equivalent approved by the Engineer-in-Charge.
OD161013/2025-2026:Charges for dismantling the existing EI, complete, making good the damages of walls and conveying the dismantled materials to concerned store/section store.
OD181214/2025-2026:Labour charges for dismantling and re-clamping the existing 6*6 sq mm Cu wire from LLDB to SSB by using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , color washing etc. as required.
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD183687/2025-2026:Providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system
OD183688/2025-2026:Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate
OD183689/2025-2026:Supply and providing 12x3mm brass nut and bolt etc. as required
OD183690/2025-2026:Supply and providing 25x3mm brass nut and bolt etc. as required.
OD192188/2025-2026:Din Rail (4+0) Surge Protection Device Class B+C/ Type 1+2 Tested as per IEC 61643 Part 11:2016 . Total Impulse current-10 KA (10/350µ sec) & Total Max Discharge current 200 KA (8/20µ sec), Voltage protection level <1.5 kV . The Surge Protection Devices should have TOV safefail for 120 Min : 442 V . Protective Elements are MOV & GDT & the Protection Modes for : L & N to PE . Short- Circuit Current rating (Isccr) ? 25kA/50 kA Back up fuse required more than 200AgG/gL. Health Status Indication required in all cartridge. Total Response time <25 nano sec . Make : Raycap / Erico / Weidmuller
OD192203/2025-2026:Charges for dismantling the existing EI, complete, making good the damages of walls and conveying the dismantled materials to concerned store/section store.
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1423882.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.04 MB
viewsbd.pdf
Tender Documents • 2.39 MB
BOQ_1423882.xls
BOQ • 0.39 MB
SPECIFIC_CONDITIONS_Electrical.pdf
Tender Documents • 0.19 MB
051254964754.pdf
Tender Documents • 0.18 MB
datecorrection.pdf
PDF • 0.18 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .