Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.2 CrAdmitted-Finance 245 2 RAJPUR ROAD OPPOSITE HOTEL MADHUBAN DEHRADUN | ₹3.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹3.3 Cr+₹14.9 L (4.69%)Admitted-Finance A 3 332 SECTOR 08 ROHINI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | ₹3.3 Cr+₹14.9 L (4.69%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Modern Electric Company L1 | Creative Entrepreneurs LLP L2 |
|---|---|---|---|---|---|
| 1.00INTERNAL WIRING | |||||
| 2.00Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 3.00 | Group -C | 589 | Point | 2,120 ₹12,48,680 Lowest | 2,400 ₹14,13,600 |
| 4.00Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 5.00 | Group -C | 155 | Point | 1,256 ₹1,94,680 Lowest | 1,260 ₹1,95,300 |
| 6.00Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required | |||||
| 7.00 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire | 2,088.33 | Metre | 375.8 ₹7,84,794.41 Lowest | 380 ₹7,93,565.4 |
| 8.00 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire | 5,599.17 | Metre | 423 ₹23,68,448.91 Lowest | 450 ₹25,19,626.5 |
| 9.00 | 2 X 6 sq. mm + 1 X 4 sq. mm earth wire | 2,010 | Metre | 676 ₹13,58,760 Lowest | 680 ₹13,66,800 |
| 10.00 | 4 x 6 sq.mm + 2 x 6 sq.mm. earth wire | 390 | Metre | 1,060 ₹4,13,400 Lowest | 1,100 ₹4,29,000 |
Tender Value
₹3.2 Cr
EMD Value
₹6.5 L
Closing Date
3 Jul 2024, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
Electrification and DG works at Proposed 50 Bedded Critical Care Block Emergency Covid Response Package II (ECRP II) in Bageshwar
2024_BRID3_72259_1
915/BRIDCUL/915/24 Dated 06/06/2024
Open Tender
Electrical Works
Item Rate
540 days
Bageshwar
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹6.5 L
BRIDCUL Dehradun
2 Aug 2024
12 Jun 2024
3 Jul 2024
12 Jun 2024
3 Jul 2024
24 Jun 2024
22 Jun 2024
Amount
INTERNAL WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group -C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group -C
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 6 sq. mm + 1 X 4 sq. mm earth wire
4 x 6 sq.mm + 2 x 6 sq.mm. earth wire
4 x 10 sq.mm + 2 x 6 sq.mm. earth wire
4 x 16 sq.mm + 2 x 6 sq.mm. earth wire
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 amps modular switch, connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required
Supplying, drawing, connecting and testing of 0.5 mm dia annealed copper conductor PVC insulated PVC sheathed telephone wire in existing conduit/wire way duct etc. as required of following sizes:
2 Pair (4 core)
SITC of EPBAX system, with Welcome message / auto attendant, Pleasant Hold Music, Connects to 2 Telephone Line & 16 Extenstions complete in all respest.
Providing, laying, connecting and testing of multi-core telephone armoured cable of conductor size 0.63mm dia annealed copper conductor PVC insulated PVC sheathed jelly filled (as per DOT specification) cable along wall or ceiling or through existing pipe.
20 Pair telephone cable
5 Pair telephone cable
Providing, fixing connecting and testing of under noted size of solderless telephone tag block Krone make in surface/recess in wall required size of M.S. box with hinged lockable cover duly stove enamel painted.
5 Pair tag block
20 pair tag block
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
20mm dia PVC conduit
25mm dia PVC conduit
32mm dia PVC conduit
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required
1 or 2 Module (75mmX75mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required
Telephone socket outlet
RJ-45 Data Socket outlet
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable
Supply and fixing of Surface mounting 2x2 feet 36W LED , suitable for 24Hr Continuous Operation, 3000-6000 system lumens, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect.
Supply, installation, connecting, testing and commissioning of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 4000K and CRI>80. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.9. The luminaire housing should made of extrusion Al with a PC diffuser. The total power consumption should not exceed 21W (including driver).Including connection with 1.5 sqmm FRLS PVC insulated copper conductor.
Supply and fixing of Surface mounting round 6 Watt 10 Watt , LED Down Lighter, suitable for 24Hr Continuous Operation, 660-880 system lumens, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect.
Supply and fixing of Surface mounting round 12 Watt 16 Watt , suitable for 24Hr Continuous Operation, 100lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect.
Supply and fixing of Surface mounting square 18 Watt , suitable for 24Hr Continuous Operation, 100lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect Make : Jaguar LNRO02S018SN, Philips / Bajaj or Eq.
Supplying, fixing, connecting, testing and commissioning of Bulkhead type light fitting complete with , wire guard, holder, electronic ballast 1 x 10 W lamp including connections etc.Including connection with 1.5 sqmm FRLS PVC insulated copper conductor as required.
Supplying, fixing, connecting, testing and commissioning of LED mirror light luminaire with 10W watt complete with electronic ballast, lamp including connection etc. complete as required, Including connection with 1.5 sqmm FRLS PVC insulated copper conductor. Make Jaguar LGLZ01X010XN, Philips / BAJAJ or Eq.
Supply and fixing of LED Flood light 50 Watt , suitable for 24Hr Continuous Operation, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, CCT 3000K, complete in all respect,
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 1200 mm sweep ceiling fan
Supplying, erection, connecting, testing and commissioning of 300 mm or 12” Wall Fan complete in all respect. Make Orient , Bajaj or Eq
Supplying, erection, connecting, testing and commissioning of following size exhaust fan complete with gravity louver and connection with 3 core flexible wire as required.
200mm 1350 RPM
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required
200 A, 36KA,FPMCCB
Supplying and fixing following way ,single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way, Double Door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
6 way Double door
8 way Double door
12 way Double door
Supplying and fixing following way surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required.(Note : Vertical type MCB TP DB is normally used where 3 phase outlet are required.)
4 way (4 + 12), Double door
12 way (4 + 36), Double door
Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required Make L&T BB40400C or Eq.
40 amps TP MCB
40 amps 4P MCB
63 amps 4P MCB
100 amps 4P MCB
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB),having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. As required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Double pole
Triple pole
Triple pole and neutral
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V "C" curve TP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP sheet steel enclosure on surface/ recess for 415 V TP MCCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Main LT Panel
Same as above item but following mountings.
INCOMER:-
2 No 1600 Amp. 4P EDO ACB of 50KA (Ics=Icu) Breaking Capacity
1 No. Multi Function Meter.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set 50,50N,51,51N,27,32,49,59,86,95 CT's control.
BUS BARS:-
2000 Amps. TP&N aluminium bus bars (50 KA)
OUT GOINGS:-
1 Nos. 400 Amps. FP MCCB thermal magnetic release (35 KA)
2 Nos. 250 Amps. FP MCCB thermal magnetic release (25 KA)
3 Nos. 200 Amps. FP MCCB thermal magnetic release (25 KA)
4 Nos. 160 Amps. FP MCCB thermal magnetic release (25 KA)
1 Nos. 125 Amps. FP MCCB thermal magnetic release (25 KA)
1 Nos. 100 Amps. FP MCCB thermal magnetic release (25 KA)
3 Nos. 63 Amps. FP MCCB thermal magnetic release (25 KA)
1 Nos. 63A 4P MCB (10KA).
1 Nos. 63A DP MCB (10KA).
4 Nos. 40A 4P MCB (10KA).
UPS PANEL
Same as above item but following mountings.
INCOMER:-
1 Nos. 100 Amps. FP MCCB thermal magnetic release (25 KA)
One (1) No. of Phase Indication Lamp each incoming
BUS BARS:-
125 Amps. TP&N aluminium bus bars (25 KA)
OUT GOINGS:-
3 Nos. 40A 4P MCB (10KA).
3 Nos. 32A DP MCB (10KA).
1 Nos. 25A DP MCB (10KA).
EXTERNAL LIGHTING PANEL
INCOMING
1No. Of 63 Amps DP MCB of 10KA breaking capacity
One (1) No. of Phase Indication Lamp each incoming
BUS BAR
1 Set of 63 Amps DP Aluminium Bus Bars
OUTCOMING
25 Amps DP MCB of 10KA breaking capacity- 5 No
SUB PANEL POWER-1 LOWER GROUNDFLOOR
INCOMING
1No. Of 160 Amps FP MCCB of 25KA breaking capacity
One (1) No. of Phase Indication Lamp each incoming
BUS BAR
1 Set of 200 Amps TPN Aluminium Bus Bars
OUTCOMING
63 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 3 No
40 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 2 No
32 Amp. DP MCB of 10KA (Ics=Icu) Breaking Capacity - 2 No
SUB PANEL POWER-2 GROUND FLOOR
INCOMING
1No. Of 160 Amps FP MCCB of 25KA breaking capacity
One (1) No. of Phase Indication Lamp each incoming
BUS BAR
1 Set of 200 Amps TPN Aluminium Bus Bars
OUTCOMING
63 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 3 No
40 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 1 No
32 Amp. DP MCB of 10KA (Ics=Icu) Breaking Capacity - 2 No
SUB PANEL POWER-3 FIRST FLOOR
INCOMING
1No. Of 200 Amps FP MCCB of 25KA breaking capacity
One (1) No. of Phase Indication Lamp each incoming
BUS BAR
1 Set of 250 Amps TPN Aluminium Bus Bars
OUTCOMING
63 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 3 No
40 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 4 No
SUB PANEL POWER-4 SECOND FLOOR
INCOMING
1No. Of 160 Amps FP MCCB of 25KA breaking capacity
One (1) No. of Phase Indication Lamp each incoming
BUS BAR
1 Set of 200 Amps TPN Aluminium Bus Bars
OUTCOMING
63 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 2 No
100 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 1 No
SUB PANEL POWER-5 THIRD FLOOR
INCOMING
1No. Of 200 Amps FP MCCB of 25KA breaking capacity
One (1) No. of Phase Indication Lamp each incoming
BUS BAR
1 Set of 250 Amps TPN Aluminium Bus Bars
OUTCOMING
100 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 1 No
63 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 2 No
40 Amp. 4P MCB of 10KA (Ics=Icu) Breaking Capacity - 3 No
CAPACITOR PANEL-200 KVAR
Incoming
One (1) No 400 Amp. 4P MCCB of 36 KA Breaking capacity
BUS BAR
1 Set of 500 Amps TPN Aluminium Bus Bars
OUT GOING
02 No. 125 Amps. TP MCCB (25 KA)
02 No. 63 Amps. TP MCCB (25 KA)
02 No. 32 Amps. TP MCCB (25 KA)
02 No. 25 Amps. TP MCCB (25 KA)
Panel described as above
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Details of cost for one each
Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required.
SUB-HEAD -V- FIRE DETECTION SYSTEM
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required
Supplying, installation, testing & commissioning of addressable manual call point complete as required
Supplying, installation, testing & commissioning of addressable fire control module complete as required
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Ten Loop Panel
Supply , Installation , Testing and Commissioning of Addressable Fire Fighter's Telephone Jack with suitable module for two way communication between Remote Fire Fighter & Fire Command Center
Supply , Installation , Testing and Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center.
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required
SUB-HEAD -VI- PA SYSTEM
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required
Ceiling Mounted Speakers
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
speaker cable Two pair, 2-core, 1.5 sqmm
SUB-HEAD -VII- LV SYSTEM
Supply , Installtion , Testing and Comissioning of Landline Speaker Phone With Caller Id.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable
Supply , Installtion , Testing and Comissioning of CAT6 information outlet (I/O) for Camera at user end. Approved Makes: Belden/Siemon/Panduit/Derwiser/ Rit
Supply, Installation, Testing & Commissioning of CAT 6 UTP, LSZH Patch Cord as per ANSI/TIA/EIA 568C.2 and UL 94-V-0, ROHS Compliant, patch cord 2 Mtr for rack side switch to end user connectivity.
Supply, installation, testing and commissioning of IP IR Dome Camera , Resolution upto 2 MP , IR distance upto 20 mtrs.
Supply, installation, testing and commissioning of IP IR Bullet Camera , Resolution upto 2 MP , IR distance upto 20 mtrs.
Supply, installation, testing and commissioning of 32 channel NVR .
Supply, Installation, Testing & Commissioning of 2TB Surviellance Hard Disk.
Supply, Installation, Testing & Commissioning of 24 Port Patch Panel. Approved
Supply, Installation, Testing & Commissioning of 24 Port Patch Switch. Approved
Supply, Installation, Testing & Commissioning of 24 Port Poe Switch. Approved
Supply, Installation, Testing & Commissioning of 6U Network rack. Approved
Supply , Installtion , Testing and Comissioning of armoured 6 core Singlemode OFC cable for interfloor switches connectivity.
Supply , Installtion , Testing and Comissioning of 6 port loaded LIU with LC adaptor plates , pigtel cables etc complete as required.
Supply , Installtion , Testing and Comissioning of 24 port loaded LIU for with LC adaptor plates , pigtel cables for core switch to access switch connectivity over fiber.
Supply , Installtion , Testing and Comissioning of LC-LC singlemode fiber patch cord for LIU to switch connectivity.
Supply , Installation , Testing and commissioning of CAT 6A STP cable 23 AWG solid copper conductors for Connectivity of Hub room to End Point.
Supply , Installtion , Testing and Comissioning of CAT 6A information outlet (I/O) for Data, Voice, & Wi-Fi at user end.
Supply , Installtion , Testing and Comissioning of loaded 24 port CAT 6A jack panel for CAT6 cable termination at rack end.
Supply , Installtion , Testing and Comissioning of loaded 12 port CAT 6A jack panel for CAT6 cable termination at rack end.
Supply , Installtion , Testing and Comissioning of CAT 6A patch cord 3 feet for rack side switch to jack panel connectivity.
Supply , Installtion , Testing and Comissioning of CAT 6A patch cord 7 feet for information outlet (I/O) to end user device connectivity.
Supply , Installtion , Testing and Comissioning of 1, 2 and 4 port face plate white for I/O fixing at user side.
Supply , Installtion , Testing and Comissioning of 15U wall mount rack with fans , 2 cable managers , satationary shelf , 2 Nos. of hardware pkts.
SUB-HEAD -VIII : L.T. CABLES
Laying of one number PVC insulated and PVC sheathed / XLPE power Cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, rotective covering and refilling the trench etc as required
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required
Up to 35 sq.mm.
Above 35 sq.mm. and up to 95 sq.mm.
Above 95 sq.mm. and upto 185 sq.mm.
Above 185 sq.mm. and up to 400 sq.mm.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required
Upto 35 sq. mm (clamped with 1mm thick saddle
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment
3.5 x 300 sq.mm.
3.5 x 185 sq.mm
3.5 x 150 sq.mm
3.5 x 95 sq.mm
3.5 x 70 sq.mm
3.5 x 50 sq.mm
3.5 x 35 sq.mm
3.5 x 25 sq.mm.
4 x 10 sq.mm
2 x 16 sq.mm,
2 x 6 sq.mm,
Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required.
2 X 6 sq. mm (19mm)
2 X 16 sq. mm (22mm)
3½ X 25 sq. mm (28mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
3½ X 70 sq. mm (38mm)
3½ X 95 sq. mm (45mm)
3½ X 150 sq. mm (50mm)
3½ X 185 sq. mm (57mm)
3½ X 300 sq. mm (70mm)
4 X 10 sq. mm (25mm)
Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5 x 300 sq.mm
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5 x 300 sq.mm
3.5 x 185 sq.mm
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.
100mm dia
150 mm dia
250 mm dia
300 mm dia
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm wide x 50 mm depth x 1.6 mm thickness.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 1.6 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm wide x 50 mm depth x 1.6 mm thickness.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 1.6 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm wide x 50 mm depth x 1.6 mm thickness.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 1.6 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" (galvanisation not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required
100 mm wide x 50 mm depth x 1.6 mm thickness.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
SUB-HEAD -XI : UPS SYSTEM
Supply, installation, testing & commissioing of 40 KVA UPS at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer as per specification given in the document with following broad features.
THD(i) shall be less than 3% in the entire loading range.
UPS shall carry design output at 40 deg.
Shall have soft start and hold of for incoming supply.
Invertor capability to supply 150% load for 5 sec.
Three Phase Input and Three Phase Output. ( Input - 340V - 470V, Three Phase, 4 wire. / Output - 400-415 Volt, Three Phase, 4 Wire.)
Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells.
Battery shall be external type with rack and suitable for 30 minute backup on 100% load.
Suitable size of copper cable between UPS and battery bank shall be provided
30 Nos. Battery with Battery Rack & connector.
UPS described as above
Supplying, installation & testing of 7.0 m high octagonal GI pole with single arm as per approved sample made from 3 mm sheet steel (Grade S 355 J0) with top diameter as 75mm and bottom dia as 150mm and base plate of 240x240x16 mm with suitable slot shaped holes for mounting the same on a shallow foundation, GI weather proof junction box with 16A SP MCB, loop-in-loop out terminals for 2nos. 2Cx6 sq.mm YWY cables and 2x2.5 sq.mm copper conductor from junction box to fitting and connected accessories as required etc. Contractor to include the cost of RCC foundation for pole as per structural detail.
Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 70Watt. to 80 Watt and Confirming to IP66 protection having Company LOGO Engraved complete in all respect with 4000-5000 system lumens High Power LED with lenses, >110lm/W, PF>0.95, THD <10% at full load, CRI>70, Avg Life Class 50000Hrs@L70,fitting itself suitable for 60-65mm OD pipe
Supplying,installation,testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required.
1 output per phase and suitable for single phase supply
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required
upto 35 sq.mm.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required
up to 35 sq.mm.
Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment
Size 6 sq.mm x 2 core
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required
Size 6 sq.mm x 2 core
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required
Supplying and laying 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
SUBHEAD-XIII : TRANSFORMER (11 KV / 0.4 KV)
Supply, Installation, testing and commissioning of 800 KVA. 11/0.433 KV, 3 Phase, 50Hz, Dyn 11, Oil type, copper wound transformer with Off load tap changing arrangement on HV side in steps of +/- 2.50%, +/- 5% , having cable end boxes on HV side and 500 Amp. bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5) & as per specification attached complete in all respects as required at site.
Note:Foundation work for transformer is not included in Electrical works it will come on Civil work.
SUBHEAD-XIV : HT PANEL EQUIPMENTS
H.T. VCB (11KV) ( LOCATED IN METER ROOM)
Design, manufacturing, testing at works, supply of HT Panel as per specification and comprising of the following :-
INCOMER/OUTGOING PANEL
630 A Vacuum circuit breaker of 26.3 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, vertical isolation,vermin proof,fully interlocked horizontal drawout type having double isolation.
Manually and motor operated, spring charged( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indicator.
630 amp air insulated but encapsulated,PVC insulated Copper bus bars.
C.T. chamber with C.T.'s 10/5.
15 VA burden for protection (class 5P 10).
Following protection shall be provided:
1 Nos IDMT relay with instantaneous 2 nos. over currrent (50, 50 N) element and 1 no. instantaneous earth fault element(50-50N).(O/C setting 50%-200% and E/F setting 20%-80%)
All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.
Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.
Red - Breaker close (ON)
Green - Breaker open (OFF)
Amber - auto trip
Clear - trip circuit healthy
Blue spring charged
Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.
Terminal boxes with single gland trifucating cable box suitable for 11 KV Aluminium XLPE (E) cable of size 3C x 120 Sq. mm. for incoming/outgoing breaker.
HT Danger Plate.(as per IS specification)
2 Runs of 40 X 5 mm earth bus shall be provided for the full length of the panel.
Necessary D.C. supply healthy indication lamp (White Colour), switch with alarm.
Surge supressor as required.
DC Voltmeter, 0-10 Volt, Digital type.
HT Panel switchboard complete with all interconnections, labels, wiring etc, complete as described above in item nos.A and B and as per specifications.
Providing and fixing HT danger notice plate 250 mm x 200 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required.
Supplying and Fixing of Fire buckets, round bottom made of G.I. Sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-charge.
Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006 etc. as reqd.
Supply and fixing of fire extinguishers, ABC Type 4.00 kg. capacity(ISI Marked IS : 15683 & TAC approved) complete with initial charges and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply and fixing of CO2 type fire extinguishers, 4.50 kg. capacity(ISI Marked IS : 2878 & TAC approved) complete with initial charges and wall bracket, along with supply of all materials and labour for proper completion of work.
Supply of 3 core stranded aluminium conductor 11KV grade XLPE (E) (Cross linked Polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cable confirming to IS : 7098 (part II with latest amendments).
120 sq. mm 3 core
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required
Upto 120 sq. mm
Laying of one number XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.
Upto 120 sq. mm
Supply and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 70Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required.
Supply and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 70 Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required.
SUBHEAD - XVII :D.G. SETS
Supplying, Installation and commissioning of AMF start silent type 750KVA DG set comprising of suitable BHP diesel engine directly coupled to 3 phase 50 Hz 415 V alternator of 750 KVA rating at 0.8 power factor mounted on a common base frame, complete in all respects with all required safety devices, fittings, batteries, accessories, filters, residential type silencer, control panel, inbuilt diesel oil MS tank of 990 ltrs. capacity made of 2mm thick M.S. sheet complete with M.S. fuel piping, G.M. gate valves, supports, control cable between generating set and control panel, exhaust piping with asbestos roping, antivibration mounting pads, first filling of lubricant oil totally enclosed in air tight, dust proof, weather proof, powder coated cubical type, sound proof as per CPCB norms acoustic enclosure made of 2mm thick CRCA sheet with with heavy duty doors, lockable arrangement, sound proof insulation with high density rock/mineral polymer/fibre cloth and perforated CRCA sheets, suitable to reduce the sound level upto 75dba approx. at a distance of 1 mtrs. as per CPCB norms
AMF Panel Incoming-1600 Amps FP EDO ACB of 50KA breaking capacity and contactor same rating
SUBHEAD - XVIII :NURSE CALL SYSTEM
Supply Installation Testing & Commissioning of Bed Call Push Button with LED indication and Flexiable Cord with button , Call Reset , Call Indication, station for each Bed omni call complete as required.
Supply,Installation Testing and Commissioning of Microprocessor controller Nurses station with Numeric terminal monitor display with in built power supply , with charger enclosed in a powder coated cabinet . Having with Reset, alarm/ buzzer, Call acknowledge with battery back up, battery charger complete system as per technical specifications and as per required of following suitable configuration.omni call complte as required
SUBHEAD - XIX :LIGHTING COUNDUCTOR
Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 mtr long etc. For lightining Conductor
Providing and fixing of lightning conductor finial , made of 25mm dia 300mm long Copper tube, having single prong at top, with 85mm dia 6mm thick G.I. base plate including holes etc. complete as required.
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor and external lighting complete as required. (For Horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Creative Entrepreneurs LLP
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
sbd_ElectDgCCU_Bageshwarf.pdf
Tender Documents • 1.73 MB
BOQ_86688.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .