Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.4 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹24.4 L+₹4.7 L (23.9%)Rejected-Finance 164 ASRAF KHAN CHAWANI OPP HARTMAN COLLEGE BAREILLY UP 243001 | BAREILLY | BAREILLY | UP | 243001 | L2 | Rejected-Finance Being High Bid | |
| 3 | L3₹28.5 L+₹8.7 L (44.3%)Rejected-Finance | L3 | Rejected-Finance Being High Bid | |
| 4 | L4₹29.4 L+₹9.6 L (48.8%)Rejected-Finance | L4 | Rejected-Finance Being High Bid | |
| 5 | L5₹31.0 L+₹11.3 L (57.1%)Rejected-Finance | L5 | Rejected-Finance Being High Bid |
Tender Value
₹49.0 L
EMD Value
₹97,980
Closing Date
27 Feb 2024, 6:00 pmClosed
CWE Office BAREILLY
HQ CWE, MES, STATION ROAD BAREILLY
CA NO CWE BLY/ GE (W) /78 OF 2023-24 REPAIR/MAINT OF APFC PANEL, EARTHING, LIGHTING ARRESTER, ELECTRIC CABLING FOR CERTAIN LOCATION AND OTHER CONNECTED WORKS UNDER GE (WEST) BAREILLY
2024_MES_638462_1
8100/B/794/E8
Open Tender
Civil Works
Works
180 days
Bareilly
AS PER NIT
6 documents required · 6 mandatory
₹500
GE West Bareilly
₹97,980
Yes
23 Mar 2024
20 Jan 2024
29 Feb 2024
20 Jan 2024
27 Feb 2024
13 Feb 2024
Amount
Taking/out old Unsv copper/GI/Alminium strip of any description from its oroginal position complete all as specified and directed.
Taking/out old Unsv air terminal of any description from its oroginal position complete all as specified and directed.
Taking/out old Unsv test terminal block of any description from its oroginal position complete all as specified and directed.
Supply and fixing Air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and directed.
Supply and fixing Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed.
Supply and fixing Copper strip 20 x 3.15 mm with saddles and fixing screws etc.for roof conductors and down conductors above ground complete all as specified and directed.
Supply and fixing copper strip 32x6 mm with burried in to ground for ring conductor and necessary jointiong work shall be carried out by brazing work complete all as specified and directed.
Supply and fixing Galvanised strip 32x6 mm with burried in to ground for ring conductor and necessary jointiong work shall be carried out by brazing work complete all as specified and directed.
Supply and fixing Aluminium strip 25x3 mm with burried in to ground for ring conductor and necessary jointiong work shall be carried out by brazing work complete all as specified and directed.
Earthing complete with using copper plate plate electrode 60×60cm×3.15 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to copper strip of size 20x3 mm by means of bolts nuts, check nuts and washers of SS/ brass all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed..
S&F in replacement of MCCB DPX 630 MCCB with electronic Sg (Lsig) with protection unit 415 Volts 4 pole 630 Amps 50 Hz with breaking capacity 50 KA alongwith spreader terminal with including lugs/thimbles of suitable size in existing panels complete all as specified and directed. (Note :- Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.)
All as per Item Ser No 11 here-in-before but of MCCB 400 Amps 4 pole 50 Hz 415 V, 50 KA complete all as specified and directed.
All as per Item Ser No 11 here-in-before but of MCCB 320 Amps 4 pole 50 Hz 415 V, 36 KA complete all as specified and directed.
All as per Item Ser No 11 here-in-before but of MCCB 250 Amps 4 pole 36 Hz 415 V, 25 KA complete all as specified and directed.
All as per Item Ser No 11 here-in-before but of MCCB 160 Amps 4 pole 50 Hz 415 V, 25 KA complete all as specified and directed.
All as per Item Ser No11 here-in-before but of MCCB 100 Amps 4 pole 50 Hz 415 V, 25 KA complete all as specified and directed.
M& L for replacement of Air circuit breaker 4 pole with microprocessor release of capacity 800 Amps 50 kA 415 V, DMX SP 2500 with manual operation , neutral overload protection OFF-50% -100% by removing out the existing after taking proper electric shut down and commissioning the same incl all minor parts as reqd for fixing new ACB complete all as specified and directed.
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles complete all as specified and directed.
Returning, filling in, including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed.
Removing of excavated soft/loose soil not exc 50 m & depositing where as directed at a level n.exc 1.5 m above from starting point completed all as specified and directed.
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches, punning complete all as specified and directed (Note:- Punning thickness of 18 cm will be considered for payment.)
M & L for brick protection to cable using old size fly ash bricks, laid flat/length wise perpendicular to the axis of cable complete all as specified and directed.
Laying only old bricks for protection of cable complete all as specified and directed.
Supply and laying in replacement of XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor 1100 volt grade, laid in trenches/ducts, fixed on wall/inside panel, drawn through pipe of cross sectional area 240 Sq mm 3.5 core complete all as specified and directed. ( Note :- Rate deemed to be inclusive of connection including cable glands and lugs.)
All as per Ser item No 24 here-in-before but 185 Sq mm 3.5 core complete all as specified and directed.
All as per Ser item No 24 here-in-before but 150 Sq mm 3.5 core complete all as specified and directed.
All as per Ser item No 24 here-in-before but 120 Sq mm 3.5 core complete all as specified and directed.
All as per Ser item No 24 here-in-before but 95 Sq mm 3.5 core complete all as specified and directed.
All as per Ser item No 24 here-in-before but 25 Sq mm 4 core complete all as specified and directed.
Taking up, down LT UG cable and relaying only serviceable LT UG Cable of any size and discription including necessary cable lugs complete all as specified and directed. (Note :- All relevent items like excavation, earth work etc shall be paid and measured seperately)
M&L for PCC type B1, 1:2:4 (using 20 mm graded satone aggregate) as in coping to the poles complete all as specified and directed.
S & F in replacement GI pipe light grade of following dia for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed. (a) 50 mm dia complete all as specified and directed.
(b) all as per item No. 32 but of size 80 mm dia complete all as specified and directed.
(c) all as per item No. 32 but of size 100 mm dia complete all as specified and directed.
M&L for earthing complete with galvanised iron steel earth plate of size 600 x 600 x 3.15 mm thick burried directly in ground (earth pit not less 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below ground level connected to thick electrode and 32x6 mm GI strip as earthing by means of nuts bolts check nuts and washers made of galvanised iron or steel earth strip protected by galvanised iron pipe 40 mm bore (medium grade) and connected to main switch board or main control board as directed and including concrete pit in PCC (1:3:6) type C1 precast RCC cover slab 54 x 54 cm x 5 cm with reinforcement with 8 mm TMT bars @ 150 C/C with one handle and funnel for watering charcoal or coke and salt in alternate layers & necessary earth work in soft/loose soil complete all as shwon in electrical plate No 3 of SSR Part-I including testing on completion all as specified and directed.
M&L for replcement of Intelligent power factor controller1001-108-90V/550 Vac complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of CT suitable for APFC panel of cap 200A/5A Cl 1.5 VA complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of super heavy duty MPP capacitors gas filled suuare type of cap 10 kVAr complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of super heavy duty MPP capacitors gas filled suuare type of cap 15 kVAr complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of super heavy duty MPP capacitors gas filled suuare type of cap 20 kVAr complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of super heavy duty MPP capacitors gas filled suuare type of cap 25 kVAr complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of super heavy duty MPP capacitors gas filled suuare type of cap 30 kVAr complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of MCB triple pole 415 V for AC application 40 Amps C curve 10 kA complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of MCB triple pole 415 V for AC application 32 Amps, C curve, 10 kA complete with all necessary connection and remoing of old existing complete all as specified and directed.
M&L for replcement of MCB triple pole 415 V for AC application 63 Amps, C curve, 10 kA complete with all necessary connection and remoing of old existing complete all as specified and directed.
Disconnection of electric connection from APFC Panel of any size dressing of cable including replacement of burnt out aluminium lugs and fixing with new lugs, nuts bolt etc complete including all inter connection with copper cable suitable current rating including painting of Panels incl welding work if reqd complete with inner & outer with two coats of synthetic enamelled paint over a coat of primer including excavation & earth work required for taking out & refixing the incoming and out going cable etc complete all as directed. ( Note :-Replacement of unserviceable accessories ie capacitors, MCCBs etc shall be measured and paid separately under relevent items.)
Supply, installation, commissioning and testing in replacement of APFC panel of capacity 120 KVAR ( 25 KVAR X 2, 20 KVAR X 2, 10 KVAR X 2, 5KVAR X 2,)( FAFA) powder coated factory made outdoor type of suitable size made of CRCA sheet made from min 3.15 mm thick sheet CPRI manufactures with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay complete panel prewired with suitable size of copper cable not less than 2.5 sqmm and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate.Panel comprising with following:- (a) Incoming MCCB 4 pole 250 Amp 35 KA alongwith Spreader terminals with adjustable thermal setting – 01 Nos (b) Multifunctional 4 in 1 meter like Amp,Voltage, frequency, powerfactor as per capacity of panel = 01 No. (c) Phase Indicator Lamp RYB with sheds LED Type - 01 Set of three (d) Capacitor MPPH type with suitable size 3 phase power contactors and with individual 3 pole 415 volt MCBs of suitable capacity including indication lamp of each capacitor. (e) Microprocessor based 3 phase current transformer sencing relay 8 stage = 01 No( for operating of capacitor bank) (f) Auto/Manually switch of capacitor bank (g) PCC 1:2:4 for installation of panel
Supply, installation, commissioning and testing in replacement of APFC panel of capacity 150 KVAR( 25 KVAR X 2, 20 KVAR X 3, 10 KVAR X 3, 5 KVAR X 2,) ( JAT HOUSE) powder coated factory made outdoor type of suitable size made of CRCA sheet made from min 3.15 mm thick sheet CPRI manufactures with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay complete panel prewired with suitable size of copper cable not less than 2.5 sqmm and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate.Panel comprising with following:- (a) Incoming MCCB 4 pole 350 Amp 35 KA alongwith Spreader terminals with adjustable thermal setting – 01 Nos (b) Multifunctional 4 in 1 meter like Amp,Voltage, frequency, powerfactor as per capacity of panel = 01 No. (c) Phase Indicator Lamp RYB with sheds LED Type - 01 Set of three (d) Capacitor MPPH type with suitable size 3 phase power contactors and with individual 3 pole 415 volt MCBs of suitable capacity including indication lamp of each capacitor. (e) Microprocessor based 3 phase current transformer sencing relay 8 stage = 01 No( for operating of capacitor bank) (f) Auto/Manually switch of capacitor bank (g) PCC 1:2:4 for installation of panel
indiatraders
LEEJA ENTERPRISES
Baba Amar Nath Enterprises
S.S.ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .