Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.8 LAccepted-Finance 223 3 S V ROAD RAMKRISHNA PALLY TAKI ROAD P O BARASAT KOLKATA 700124 | KOLKATA | NORTH 24 PARGANAS | WEST BENGAL | 700124 | L1 | Accepted-Finance Lowest Bidder | |
| 2 | L2₹17.7 L+₹1.9 L (11.9%)Rejected-Finance 223 3 S V ROAD RAMKRISHNAPALLY BARASAT DIST NORTH 24 PARGANAS PIN 700124 | BARASAT | NORTH 24 PARGANAS | WEST BENGAL | 700124 | L2 | Rejected-Finance Not L1 | |
| 3 | L3₹20.1 L+₹4.3 L (27.1%)Rejected-Finance 41 16 DUM DUM ROAD KOLKATA 700074 | KOLKATA | KOLKATA | WEST BENGAL | 700074 | L3 | Rejected-Finance Not L1 |
Tender Value
Refer Docs
EMD Value
₹32,000
Closing Date
10 Sept 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Assistant Engineer,PWD, Banga Bhawan
Banga Bhawan 3 Hailey Road New Delhi
2024_PWD_736146_1
2024_PWD_736146_2
04/BBES of AE of Banga Bhawan of 2024-2025
Open Tender
Miscellaneous Services
Item Rate
30 days
Banga Bhawan New Delhi
Please refer Tender documents.
4 documents required · 4 mandatory
₹32,000
Yes
Banga Bhawan New Delhi
17 Sept 2024
23 Aug 2024
12 Sept 2024
23 Aug 2024
10 Sept 2024
23 Aug 2024
24 Aug 2024
Amount
Supply, Installation, Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in this estimate along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software.(Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/Ravel/ NOTOFIRE).(Necessary OEM licensed software and/or dongle for pogramming (addition/alteration) of the fire al;arm control panel with lifetime validity has to be provided by L1 bidder, before handover.)
Supply, Installation, Developing GUI including necessary Programming, testing & commissioning of OEM licensed GUI based Fire Monitoring Software, compatiable with above FACP and other devices and SITC of server / PC having minimum specification given below - (Make:same as FACP) i) Monitoring of single or network panels ii) Management of 500 Devices.( with lifetime license) iii) Client server Architecture with simultaneous connection of upto 5 Clients including 2 Web Clients. iv) User friendly operation. v) Capability of importing floor plans in wide variety of formats e.g. Autocad, BMP, JPEG, WMF etc. vi)Instant Popup with location name for any Fire or Fault occurance and highlighting respective detectors on the Floor plan. vii) Event logging ( all Fire & fault event and actions) having search, backup and pointing capabilities. viii) Zoom capability in the Graphical display (Floor plan) ix) Capability of sending SMS alert on at last 5 mobile nos (pre-assigned) x) Zone wise isolation facility. Minimum technical Specification of PC / Server (Make: Dell/HP) i)Processor - Intel core i7 12th Generation ii) RAM - 32 GB DDR4 RAM iii) HDD - 256 GB SSD and 2TB HDD iv) Graphics card with dedicated RAM v) Minimum 2 nos USB 3.0 and 2 nos USB 2.0 ports, 2 nos HDMI ports vii) Driver / Conveter (Hardware & Software) required for connection with the FACP and WAN connection. vii) Driver / Conveter (Hardware & Software) required for connection with the FACP and WAN connection viii) Licensed Operating system and other necessary software required for full function of Fire monitoring system. ix) Capability of 24X7 operation.
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/NOTOFIRE/ Ravel )
Supply, Installation, Testing & Commissioning of Addressable Intelligent Heat detector (EN54/ LPCB approved) with two inbuilt optical smoke sensors with backward & forward scattering light angles as well as additional heat detector sensor with decentralize intelligence, Photothermal type with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards). (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls/ Edward/ Secutron/ Securiton/ Apollo / Morley/ Eaton/ GST/Ravel/ NOTOFIRE)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls/ Edward/ Secutron/ Securiton/ Apollo / Morley/ Eaton/ GST/Ravel/ NOTOFIRE)
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 75 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP42 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/Ravel/ NOTOFIRE)
Supply, Installation, Testing & Commissioning of Addressable Monitor Modules ( VDS / UL /ERTL/ LPCB / FM approved ) for monitoring Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output including all necessary accessories, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/Ravel/NOTOFIRE)
Supplying, installation, testing and commissioning of LED type Response Indicator (VDS/ UL/ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls/ Edward/ Secutron/ Securiton/ Apollo / Morley/ Eaton/ GST/ Ravel/ System Sensor/ NOTOFIRE/ Agni Suraksha)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab) through 20 mm dia PVC 'FR' type Rigid Conduit pipe including S & laying of the 20 mm dia PVC 'FR' type Rigid Conduit pipewith necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall.
SITC of Power Supply 230V AC to 24V DC with high efficiency, long life and high reliability, Low DC ripple, low operation temperature, good insulation property including all other accessories.(Make : Reputed) Note:1) The Fire Alarm system shall comply with latest requirements of -- (i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 , (iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand. TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done TERMS & CONDITIONS :- The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
B.S.A ENGINEERING
B.K. MUKHERJEE AND ASSOCIATES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .