| # | Company | Amount | Status |
|---|---|---|---|
| 1 | ₹13.7 CrAdmitted-Finance 53 VAISHAILI ENCLAVE SECTOR 9 INDIRA NAGAR LUCKNOW | LUCKNOW | Admitted-Finance | |
| 2 | ₹14.3 CrAdmitted-Finance | Admitted-Finance | |
| 3 | ₹14.6 CrAdmitted-Finance | Admitted-Finance | |
| 4 | Rejected-Technical | Rejected-Technical Due to not attached essential documents |
| Sl No | Description | Qty | Unit | KRISHNA REFRIGERATION | Rk Tyagi Construction Pvt ltd | Pundrikaksh Developers Pvt Ltd |
|---|---|---|---|---|---|---|
| 1.00Compact Secondary substation-(CSS) | ||||||
| 1.10 | 1000 KVA, 11/.433 KV Compact Secondary substations in accordance with IEC 61330, IP compete with enclosure typically divided into three compartments, non walkable type, with cooling arrangement as may be required, complete as following :Design, engineering, manufacture, transportation,installation,testing ,supply of 11 KV (System Voltage 12 KV, BIL 95 KVp) non-extensible compact substation (CSS) with RMU , Transformer & LV cubicle and RMU configuration & ONAN Loss as per IS 1180 Lvl-II transformer configuration is given under. RMU consisting 2 Nos Load break switch shall be 630A - 21KA/3 secs and 1 No. VCB/SF6 Breaker shall be 630 A - 21KA/3secs. The CSS shall be complete with mounting of foundation, earthing, cable termination, testing and commssioning. The CSS shall be from OEM of RMU and LV euipment.
LV side of CSS shall be complete with LV enclosure , LT panel with Drawout type ACB on incomer & fixed type 4P, MCCB's on LT O/G sid OUTGOING
I/C 2000A FP, ACB = 01 Nos. R,Y,B ON/OFF / Trip Indication CT 2000 A/5A,Class 1.0,15VA Multifuction metre to show KVA / KWH / V/A / PF BUSBAR 2000A FP AL. Busbar
(Make: ABB/Crompton/Schneider/Kirlosker) | 1 | No | 61,25,000 ₹61,25,000 Lowest | 65,08,540 ₹65,08,540 | 64,18,081 ₹64,18,081 |
| 2.00DG SET | ||||||
| 2.10 | S/I/T/C of Diesel generator set of 625kVA capacity (at 40oC Ambient temperature.), with electronic governor as per specification. Also the cost shall include the freight & insurance. DG to be of prime / continuous duty application as per IS. Alternator to be provided with Class 'H' insulation & with cable termination box for LT Cables. Alternator to be provided with local isolator indoor/ outdoor type for maintenance purpose. DG set coupling to be with double bearing type, teethed gear coupling. The cost shall also include Engine Control Panel (Type: EGCP / Power Command Control) with RS 485 comm. port.
DG sets shall be suitable for auto synschronising with auto load sharing and remote monitoring & control arrangement compatible with the existing electrical system and Integrable with PLC of LT Panel with all required CT's and all gears including Electrical and Electronic controller. DG set must comply CPCB-IV Norms.
DG Set with Alternator with Integral Acoustic Enclosure shall include the following components and accessories complete Residential type Silencer Anti‐Vibration Mounts (as required) Battery and Charger Dynamo (24V, 160AH minimum with leads 990 Ltrs MS Fuel Tanks with float/ limit switch indicator for low & high fuel level. Required number of contacts to be provided for connecting the level limit switch for indication in DG Control Panel. Fuel system consisting of Connect Fuel Pipe with MS "C" Class Pipe with flange & gas welded joint & pipe fittings like valves & other accessories and breather drain pipes if required need to be provided.
(Make: Cummins /Kirlosker/ Crompton/ Koel/ Kohler / perkins / MTU) | 1 | No | 83,12,500 ₹83,12,500 Lowest | 87,10,253 ₹87,10,253 | 89,11,249 ₹89,11,249 |
| 3.00MAIN ELECTRICAL PANEL (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved | ||||||
| 3.10 | SITC of LT switchgear panels suitable for 433 V. 3 phase. 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 65kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. Panel shall have Buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover ete and having following incomming and outgoing Air Circuit Breakers, microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display. | 1 | No | 55,30,455 ₹55,30,455 Lowest | 57,95,087 ₹57,95,087 | 61,32,455 ₹61,32,455 |
| 3.20Air Circuit Breaker with microprocessor release metering & LCD display, with ready to clsoe indicator, should have capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (leu-les-lew-50 KA (1 sec). MCCB, with microprocessor release with LSIG protection functionand should not derate upto 50 degree Centrigrate as per testing guideline as per IEC 60947-2 and all the ACB upto 2500Amp ACB should have same frame size LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet. (50 KA Ics) | ||||||
| 3.30INCOMING | ||||||
| 3.402 Nos. 2000 Amp FP EDO ACB 50KA having S/C, E/F O/C protection, LCD Display having specs as per attached annexture From 1000KVA CSS having R.Y,B Phase indication Lamp with control MCB On, Off, Trip Status Indication with control MCB Inbuilt Zone Selective Interlocking function Multifunction Meter Relay : 32,27,59,87GN BUSCOUPLER 1 Nos. 2000Amp FP EDO ACB 50KA, LCD Display having spees as per attached annexture having R.Y.B Phase indication Lamp with control MCB On, Off, Trip Status Indication with control MCB AUTO OPERATION OF INCOMER/BUSCOUPLER ACB's Load Management through PLC Auto changeover, Buscoupler switching Electrial & Mechnical Interlocking. Synchonization through PLC Contactor for Synchronizing System Auto mains failure and auto load balancing, load management, auto On and Off of DG set as per load requirement. Buscoupler switching. Electrial & Mechnical Interlocking. BUSBARS 2000 Amp FP busbars of aluminium alloy as per SLD. | ||||||
| 3.50OUTGOING | ||||||
Tender Value
Refer Docs
Closing Date
3 Oct 2025, 5:00 pmClosed
DDE/M, Mandi Parishad, Lko
Kisan Mandi Bhawan, Vibhuti Khand, Gomti Nagar Lko
Rates for compact secondary substation, DG set, electrical panels, Fire Fifgting system , STP System, CCTV System, Operation and Maintenance Work at Lucknow.
2025_RKUMP_1071801_1
E/M/325/2025-531
Open Tender
Miscellaneous Works
Item Rate
Kisan Mandi Bhawan, Lko
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
Kisan Mandi Bhawan, Vibhuti Khand, Gomti Nagar Lko
4 Oct 2025
10 Sept 2025
4 Oct 2025
10 Sept 2025
3 Oct 2025
10 Sept 2025
24 Sept 2025
Compact Secondary substation-(CSS)
1000 KVA, 11/.433 KV Compact Secondary substations in accordance with IEC 61330, IP compete with enclosure typically divided into three compartments, non walkable type, with cooling arrangement as may be required, complete as following :Design, engineering, manufacture, transportation,installation,testing ,supply of 11 KV (System Voltage 12 KV, BIL 95 KVp) non-extensible compact substation (CSS) with RMU , Transformer & LV cubicle and RMU configuration & ONAN Loss as per IS 1180 Lvl-II transformer configuration is given under. RMU consisting 2 Nos Load break switch shall be 630A - 21KA/3 secs and 1 No. VCB/SF6 Breaker shall be 630 A - 21KA/3secs. The CSS shall be complete with mounting of foundation, earthing, cable termination, testing and commssioning. The CSS shall be from OEM of RMU and LV euipment. LV side of CSS shall be complete with LV enclosure , LT panel with Drawout type ACB on incomer & fixed type 4P, MCCB's on LT O/G sid OUTGOING I/C 2000A FP, ACB = 01 Nos. R,Y,B ON/OFF / Trip Indication CT 2000 A/5A,Class 1.0,15VA Multifuction metre to show KVA / KWH / V/A / PF BUSBAR 2000A FP AL. Busbar (Make: ABB/Crompton/Schneider/Kirlosker)
DG SET
S/I/T/C of Diesel generator set of 625kVA capacity (at 40oC Ambient temperature.), with electronic governor as per specification. Also the cost shall include the freight & insurance. DG to be of prime / continuous duty application as per IS. Alternator to be provided with Class 'H' insulation & with cable termination box for LT Cables. Alternator to be provided with local isolator indoor/ outdoor type for maintenance purpose. DG set coupling to be with double bearing type, teethed gear coupling. The cost shall also include Engine Control Panel (Type: EGCP / Power Command Control) with RS 485 comm. port. DG sets shall be suitable for auto synschronising with auto load sharing and remote monitoring & control arrangement compatible with the existing electrical system and Integrable with PLC of LT Panel with all required CT's and all gears including Electrical and Electronic controller. DG set must comply CPCB-IV Norms. DG Set with Alternator with Integral Acoustic Enclosure shall include the following components and accessories complete Residential type Silencer Anti‐Vibration Mounts (as required) Battery and Charger Dynamo (24V, 160AH minimum with leads 990 Ltrs MS Fuel Tanks with float/ limit switch indicator for low & high fuel level. Required number of contacts to be provided for connecting the level limit switch for indication in DG Control Panel. Fuel system consisting of Connect Fuel Pipe with MS "C" Class Pipe with flange & gas welded joint & pipe fittings like valves & other accessories and breather drain pipes if required need to be provided. (Make: Cummins /Kirlosker/ Crompton/ Koel/ Kohler / perkins / MTU)
MAIN ELECTRICAL PANEL (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
SITC of LT switchgear panels suitable for 433 V. 3 phase. 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 65kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. Panel shall have Buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover ete and having following incomming and outgoing Air Circuit Breakers, microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display.
Air Circuit Breaker with microprocessor release metering & LCD display, with ready to clsoe indicator, should have capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (leu-les-lew-50 KA (1 sec). MCCB, with microprocessor release with LSIG protection functionand should not derate upto 50 degree Centrigrate as per testing guideline as per IEC 60947-2 and all the ACB upto 2500Amp ACB should have same frame size LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet. (50 KA Ics)
INCOMING
OUTGOING
2 Nos. 800 Amp TP EDO ACB 65 KA,LCD Display having spees as per attached annexture having On, Off, Trip Status Indication with control MCB Digital Ammeter 6 Nos. 630 Amp FP MCCB 50 KA,LCD Display having spees as per attached annexture having On, Off, Trip Status Indication with control MCB Digital Ammeter 2 Nos.400 Amp FP MCCB 50 ΚΑ On, Off, Trip Status Indication with control MCB Digital Ammeter 3 Nos.315 Amp FP MCCB 50 ΚΑ On, Off, Trip Status Indication with control MCB Digital Ammeter 9 Nos. 250 Amp FP MCCB 36 ΚΑ On, Off, Trip Status Indication with control MCB Digital Ammeter 5 Nos. 200 Amp FP MCCB 36 ΚΑ On, Off, Trip Status Indication with control MCB Digital Ammeter 4 Nos. 125 Amp FP MCCB 36 ΚΑ On, Off, Trip Status Indication with control MCB Digital Ammeter 4 Nos. 100 Amp FP MCCB 30 ΚΑ On, Off, Trip Status Indication with control MCB Digital Ammeter Short Circuit Breaking capacity should not less than 30KA. RELAYS AS PER SLD
500 KVAR APFC PANEL (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
SITC of APFC panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power factor correction system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 50kA as per Single Line Diagram. The APFC Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. Panel shall have Buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers, microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display. Air Circuit Breaker with microprocessor release ge metering & LCD display, with ready to clsoe indicator, should have capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics-lcw-65 KA (1 sec). MCCB, with microprocessor release with LSIG protection function LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet. (65 KA les)
INCOMING
1 Nos. 800 Amp TP ACB 50KA R,Y,B Phase indication Lamp with control MCB On, Off, Trip Status Indication with control MCB Multifunction Meter BUSBARS 1 Nos. 1600 Amp TPN busbars of aluminium alloy as per SLD OUTGOING 14 stepped Automatic Power Factor Correction relay (APFC relay). 2 Nos. 200 Amp TP MCCB 4 Nos. 200 Amp TP MCCB 2 Nos. 50 Amp TP MCCB 2 Nos. 15 Amp TP MCCB 2 Nos. 10 Amp TP MCCB On, Off Status Indication with control 3 Nos.100 Amp MCCB TP 2 Nos. 250 Amp TP capacitor duty contractor 3 Nos. 160 Amp TP capacitor duty contractor 4 Nos. 100 Amp TP capacitor duty contractor 2 Nos. 63 Amp TP capacitor duty contractor 2 Nos. 40 Amp TP capacitor duty contractor 2 Nos. 100 KVAR super heavy duty mix dielectric low loss Capacitor suitable for non leniar loads upto 20% 3 Nos. 50 KVAR super heavy duty mix dielectric low loss Capacitor suitable for non leniar loads upto 20% 4 Nos. 25 KVAR super heavy duty mix dielectric low loss Capacitor suitable for non leniar loads upto 20%
FLOOR PANEL (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
Fabrication, Supply, Installation, Testing andcommissioning of 415V,50 Hz, 3 phase,4 wire, Self-standing/wall mounting, dust and vermin proof front operated, cubicle type distribution panel, made out of 16 SWG CRCA sheets fully compartmentalized, duly rust inhibited, degreasing, zinc phosphate, etc; siemens grey color powder coated, with hinged and earthed front doors, heavy-duty rubber gaskets, removable gland plates made out of 2 mm thick sheet steel, with appropriate rated TPN bus bars & earth bus. The bus bars should be of suitably rated aluminum, having specified normal and short circuit capacities and should be insulated with heat shrinkable color-coded PVC sleeves and DMC/SMC pillars/pillar type busbar supports. Dimensions, design, and fabrication of the entire panel should be as per Indian Standard. The panel drawings should get prior approval. Cable entry shall be according to site conditions. The panel comprising of the specific components as below
UPPER GROUND FLOOR (PANEL -I) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
LOWER GROUND FLOOR (PANEL -I) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
LOWER GROUND FLOOR (PANEL -II ) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
UPPER GROUND FLOOR (PANEL -I) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
UPPER GROUND FLOOR (PANEL -II) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
FIRST FLOOR (PANEL -I) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
FIRST FLOOR (PANEL -II) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
SECOND FLOOR (PANEL -I) (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
THIRD FLOOR (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
LIFT PANEL-1 (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
LIFT PANEL-2 (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
STP PANEL (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
PLUMBING PANEL (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
Ventilation Panel for Lower Basement (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
Supply, Installation, Testing and Commissioning of Programmable Logic controller as per the below description and the Tender technical specs: S/I/T/C of Universal Cntroller PLC with main componentslike power, processor, input & output cards, an open protocol for interface with the BMS systems. PLC to be complete as per specs installed inside the Main Switchgear MCC panel. The PLC shall have a FULL MODBus / BACnet / Eithernet interface facility with the Central BMS system. Scope to include the Gateway or converter, Communication module, HVAC software in addition to the standard features. Minimum Specifications of a Controller are as follows (but should meet the project needs): a) 10 x analogue inputs for CO or other pollutant sensors. (0-20mA, 0-5V and 0-10V input available). b) 16 x digital inputs for fan run/fault status. c) 1 x emergency alarm (i.e. fire) digital signal inputs. d) MODBUS, BACnet and other protocols for supervisory connection with BMS system. Built-in communication Modbus slave serial link by means of connection on integrated RJ45 port (Modbus master/slave serial link on integrated RJ45 port). e) 3 x analogue outputs available to speed control groups of JetVent Fans, central car park exhaust fan or supply fan. f) 3 x digital outputs to drive speed control relays (for 2 speed fans) or other systems according to pollutant concentration.
a) Programmable Logic Controller with HVAC software b) Dedicated PWM programmable output. c) Programmable Anagol Outputs/Inputs 0 - 10 V, 0 - 20 mA, 4 - 20 mA d) Display block for displaying the controller status: 4 LEDs (PWR, RUN, ERR and EXP) and 1 LED that can be used in the application. e) Connector for a removable terminal block (1) (2 terminals) for connecting the 24 V c/a supply. f) RJ11 connector marked Prg. Port for connecting a programming port g) Connector for a removable terminal block (1) (9/10 terminals), for connecting analog inputs. h) Connector for a removable terminal block (1) (16 terminals), for connecting discrete inputs. i) Connector for a removable terminal block (1) (5 terminals), for connecting analog outputs. j) RJ45 connector, marked MBS1, for connection to the Modbus™ bus. k) RJ45 connector, marked MBS2, for connection to the Modbus bus. l) Five Modbus bus and expansion bus polarization and line terminator adjustment switches. expansion bus. n) Connector for a removable terminal block (1) (2 terminals) to connect the power supply for a remote display unit TM168 GDBp(2). o) Connector for a removable terminal block (1) (5 terminals), for connecting 3 discrete relay N/C outputs. p) Connector for a removable terminal block (1) (6 terminals), for connecting 4 discrete relay N/C outputs. q) Connector for a removable terminal block (1) (3 terminals), for connecting the discrete relay C/O output. r) Display with 6 command buttons for setting the controller parameters s) logic controllers are mounted as standard on a 35 mm DIN rail.
LOWER Basement PLC - Panel (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
DOL / SD starter as per HP gratings given. Terminal block for power distribution as required. Contactor, over load relay with built in single phasing protection. Phase indicating lights and indicating light for `ON’ status.144 mm x 144 mm voltmeter and digital ammeter. Time delay relay for delayed automatic restart of motor. Wiring for microswitch for stopping the fan when fire damper closes (in case of Fire operation only).For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. MCCB/MPCB shall be Type 2 Co-ordinated with the Motor starter. Degree of Protection for the Outdoor starter panel shall be IP 55. The number of control panels shall be as follows.
MCCB suitable for, upto 7.5 HP , 4P motor with DOL starter (Car park Exhaust )
MCCB suitable for 10 HP, 4P motor with STAR DELTA starter (Car park Exhaust & Fresh Air )
TERRACE PANEL-1 (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
Common Area Lighting Panel (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
Supply and Laying of 3 core stranded Aluminium Conductor XLPE (Cross linked polyethylene) insulated PVC bedded, galvanized flat steel strip armoured cables confirming to I.S. 7098 (Part II with latest amendments) 11 KV grade at a depth of 900 mm below ground level over a cushion of 100mm thick fine rever sand all around and protected with well burnt bricks on sides and on top put across as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 240 sqmm 3 core (Make: Polycab/Havells/RR Kabel/KEI/Finolex
Supply installing testing & commissioning of out door type street light feeder pillar (Distribution Panel) compartmentalised design, dust tight & vermin proof made out of 14 gauge M.S. sheet, stove powder coated complete as required with following incomming & outgoing as per detail below. Incoming 100 Amp. 10 KA FP MCCB 1 No Suitable contractor and timer for down & dusk 100 Amp. TPN Alu. Bus bar Outgoing 25 Amp. 10KA SP MCB 6 No. (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved
Supply and Installation of PROFILE LIGHTS WITH LED STRIP indoor, 24W / 5meter (4" THICK)including driver and necessary fixing accessories as required (Make: Wipro/Trilux/Philips/LT/Havells/ Bajaj)
Supply of fire buckets 4 No. in each set duly filled with fine sand and fixed on an angle iron frame as per requirement of local authorities. Fire buckets shall be painted red from outside and white from inside with additional handle at the bottom and suitable for outdoor installation.
Supply of tool kit with 1 pair 11 KV rubber hand gloves as directed by Engineer Incharge.
Providing Safety mat made of elastomeric polymers Material (Class B) 1.2 M wide with thickness 2.5 mm to withstand 12KV dielectric strength AS PER relevant IS Code
Exhaust and Fresh Air Fan Sections : Supply, Installation, Testing & Commisioning of AMCA Certified (For Air and Sound Performance) tube axial flow fans of different capacities in standard GI/M.S. contruction as mentioned below. Entire fan model and AMCA Seal shall apear in techncial submittal of fan. All the fans shall be synthetic enamel painted/ hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at fan inlet. The electric motor coupler shall be IE-02 squirrel cage induction type conforming to IS-325, IP-55 rated with class `H' insulation. Motor shall be of high temperature resistance "Class H Smoke Spill" 250°C for 2 hours. Fans shall be EN 12101-3 Certified and CE/UL Listed for high temperature. Motor make shall be same as that mentioned on the fire certificate. Fan efficiency should not be less than 65%, and noise level should not be more than 70 db @ 3 m distance when measured under hemisperical reverberant room conditions. Quoted price shall be inclusive of sound attenuator at the outlet of the fan as shown in the approved shop drawings, all accessories like bird screens, vibration isolators,mounting brackets/feet/ duly enamel painted M.S structure etc. Fans mentioned as outdoor type shall be good for outdoor installation with proper cowl and mounting arrangement as per approved shop drawings. Fans shall be as per specifications and design drawings. Axial Flow Fans shall follow the design parameters as mentioned below: (Make- Kruger / greenheck / flaktwood / zeco /LTI /Nicotra /Systemair / Witt-India / airflow
25000 cfm at 50 mm static (For Basement+LGF Fr.)
22000 cfm at 50 mm static (For Basement Fr.)
19000 cfm at 50 mm static (For Basement+LGF Ex.)
16000 cfm at 50 mm static (For Basement Ex.)
2000 cfm at 30 mm static (For Pump Room)
4500 cfm at 30 mm static (For Chiller Room)
3500 cfm at 30 mm static (For Electrical Room)
Terrace Floor 9500 cfm at 30 mm static (For Staircase)
9000 cfm at 30 mm static (For Staircase)
6500 cfm at 30 mm static (For Liftwell)
6000 cfm at 30 mm static (For Liftwell)
2000 cfm at 30 mm static (For Liftwell)
Final CFD Analysis report should be done by Original Equipment manufacturer inorder to get actual jet fan quantity and jet fan positioning.
Supply, Installation, Testing and Commissioning of Logic Supervisory Controllers . The System should have Inbuilt Graphic Software to view the Basement Ventilation system including Sensors feedback, Actual reading, Fan command and running status through Graphic software.
Variable Frequency Drive (Make: Siemens/Schnieder/Danfoss/ABB/Fuji/Allen Bradley/Honeywell) Supply, Installation, Testing & Commissioning of variable frequency drives for following Tube axial fan. Variable frequency drives shall be provided with necessary temperature sensors and controllers complete with control wiring in all respect as required and as per the specifications. The VFD shall exhibit IP-55 protection. The drives shall be suitable for the following motor rating. VFDs shall be housed in AHU/ FAN panels.
Jet Fans (Make: Kruger /Coolvent / united air-tech / constorium / witt-India / Fanair / ventilair / marut-air) S/I/T/C of Ductless Ventilation System / Jet Fans as per the specifications and layouts, suitable for Normal Ventilation and Smoke Extraction Application in case of emergency i.e. 250 to 300 Deg C for 2 Hrs operation. The Dia of jet fans shall be 315 mm. Each fan shall be complete with motor and impeller. The complete fan shall be certified as tested for 300 Deg C for 2 hours operation. The Motor shall be suitable for operation on 415±10% Volts, 50 Hz, 3 Phase AC power supply. (For Car Parking of Basement)
CO Sensor (Make: Danfoss/Honeywell/Siemens) Supply, Installation, Testing and Commissioning of CO-Sensors at Basement Floor Car Parking
Ducted Inline Type Exhaust fans : (Make: Greekheck / Zeco / LTI/Witt India/Airflow / Pineair / Ostberg / kruger / Flaktwood / systemair) Supply,installation,testing and commissioning of ducted Inline type exhaust fans complete with motor ,fan, exhaust Louvers as per drawings and specifications. of following sizes :
150 mm dia (free discharge)
100 mm dia (free discharge)
Bird Screen S / I / testing & balancing of factory made Bird screen made out of galvanized steel mesh in 20G having diamond pattern with GSS flanges and necessary cross bracings suitable for Fresh/ Exhaust air fans on terrace, complete as per specification & approved shop drawings.Vendor to comply all Tender Specifications.
Canvas Cloth Supply, Installation, Testing and Commissioning of flexible canvass cloth connection at oulet of each Ducted Indoor Unit with zipper to facilitate temperature measurement
Charges for making opening in RCC Slab and repairing of the same for Ducting and Piping. Upto 1sqm size
Charges for making opeing in walls for passing the Supply & Return Air Ducting and Piping
upto 0.50 Sqm size
from 0.51 Sqm to 1.00 Sqm size
Supply, installation, testing and commissioning of 5 MP Varifocal Bullet camera, ONVIF 2.6+ (Profile S, Profile G, Profile T), 1/2.7" CMOS, 2.8 mm-12 mm Varifocal motorized lens with autofocus, triple stream with mainstream support 5 MP, H.264/H.265 (Baseline / Main / High), 0.24 lux (Color) and 0.01 lux (Mono) with IR, 72 dB True DWDR, BBLC, AGC, Slow Shutter, Privacy Masks, 3-Axis mounting, Exposure mode 1/5-1/20000 (Auto) & 1/5-1/20000 (Manual), SD Card support ≤256Gb, Smart Functions like Perimeter Intrusion Detection, Line Crossing Detection, Stationary Object Detection, Pedestrian (Human)/Vehicle Detection, Cross Counting, Heat Map, Customers Detection, Queue Length Detection, 4 IR LED + 4 White LED, IR Distance up to ≤50, Auto IR Cut Filter, IP66, PoE Class/W =0/12, DC12V, 0.8А, Alarm I/O, Audio I/O, -40 - +60, CBR, VBR, and CE, FCC Certified. Make Honeywell /Partizan / Bosch / Axis
Supply, installation, testing, and commissioning of 5 MP Varifocal Dome camera, ONVIF 2.6+ (Profile S, Profile G, Profile T), 1/2.7" CMOS, 2.7mm-13.5mm Varifocal motorized lens with autofocus, triple stream with mainstream support 5 MP, H.264/H.265 (Baseline / Main / High), 0.24 lux (Color) and 0.04 lux (Mono) with IR, 120dB True WDR, BLC, AGC, Slow Shutter, Privacy Masks, 3-Axis mounting, Exposure mode 1/5-1/20000 (Auto) & 1/5-1/20000 (Manual), SD Card support ≤256Gb, Smart Functions like Perimeter Intrusion Detection, Line Crossing Detection, Stationary Object Detection, Pedestrian Detection, Face Detection, Cross Counting, Face Recognition, IR LED (2, Array LED), IR Distance up to ≤50, Auto IR Cut Filter IP66, IK10, PoE Class/W =0/12, DC12V, 0.8А, Alarm I/O, Audio I/O, -40 - +60, CBR, VBR, and CE, FCC Certified. Make Honeywell /Impulse/Pelco/ Bosch / Axis
Supply, installation, testing, and commissioning of 64 Channel NVR, Recording speed- 64 channels 8.0Mp@25fps, 2xEthernet 10/100/1000Mbit. Audio in: 1xRCA. Alarm in: 16 Output: Video out: 3xHDMI, 1xVGA. Audio out: 1xRCA. Alarm out: 4, 8xSATA up to 12Tb (not included), 1xUSB 2.0, 2xUSB 3.0, RS-485, ONVIF, H.264/H.265, FTP,Accessories: built-in power adapter AC220V, mouse,Dimensions: 440x460x89 mm,Software support: (PC/Android/iOS), Web interface (IE), Smart Functions: Face Detection, Pedestrian Detection, Vehicle Detection, Cross Counting, Heat Map, Crowd Density Detection, Perimeter Intrusion Detection, Line Crossing Detection, Queue Length Detection, License Plate Detection, Rare Sound Detection. Certification: BIS, CE, FCC; Country of Origin: Europe. Make Honeywell /Impulse/Pelco/ Bosch / Axis
Supply, installation, testing, and commissioning of Advanced software for Windows OS to control big CCTV systems containing multiple recorders and IP cameras. Make Honeywell /Impulse/Pelco/ Bosch / Axis/same as CCTV camera
Supplly, configuration, and implementation of camera channel licenses on VMS Software. Make Same as CCTV camera
Supply, Installation, Testing & Commissioning of 8TB Surveillance Hard Disk. Make Seagate/WD/Toshiba
Supply, Installation, Testing & Commissioning of 24-Port Gigabit PoE+ Smart Switch with 2 SFP Ports Make Netgear / Planet / Cisco
Supply, Installation, Testing & Commissioning of SFP Transceiver 1000 BASE-T Copper RJ45 GBIC Make Netgear / Planet / Cisco
Supply, Installation, Testing & Commissioning of 8-port Multi-Gigabit Smart Switchwith 10G Copper / Fiber Uplinks. Make Netgear / Planet / Cisco
Supply, Installation, Testing & Commissioning of 16-port Multi-Gigabit Smart Switchwith 10G Copper / Fiber Uplinks. Make Netgear / Planet / Cisco
Supply, Installation, Testing and Commissioning of 55" LED Display. Make LG / Panasonic/ Samsung
Supply, Installation, Testing and Commissioning of Workstation PC with standard configuration, Keyboard: 12 function keys; Chassis: Workstation; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 1TB, 7200 RPM 3.5" SATA 6Gb/s Hard Drive; Operating system: Windows 10 Professional 64 Bit or latest with monitor, 22" LED Monitor. Make HP/CoreIP / Dell
S/I/T/C of Single Face Plate for mounting IO with required back box. Make Legrand/Digisol/Derwiser/Commscope
S/I/T/C of Cat6 Information Outlet (IO) Make Legrand /Digisol/Derwiser/Commscope
S/I/T/C of CAT6 UTP RJ-45 Patch Cords Solid Conductor 3ft Make Legrand / Digisol / Derwiser/Commscope
S/I/T/C of Unloaded CAT6 jack panel Make Legrand/Digisol/Derwiser/Commscope
S/I/T/C of 4 pair, U/UTP, 24 AWG solid copper CAT6 cable Make Legrand/Digisol/Derwiser/Commscope
S/I/T/C of Rack 6U, 600 x 500 mm pole mount welded section side integrated network rack Make Legrand/Dynamic Rack/Commscope
Supply, Testing, and Comissioning of 24U (600W/800D) floor mount rack with 1 Nos. Front Glass Door - 24U - 600W - Cam Lock - Ventilation - Duscky Fine Tex. - Assembly, 1 Nos. Rear Door - 24U - 600W - Cam Lock - Square Slot Ventilation - Duscky Fine Tex. - Assembly, 1 Nos. 3 Inch Castor Set, Four Fans, 4 Nos. Metal Cable Manager - 01U - Plastic Cable Loop's Mountable - Black Fine Tex. - Assembly, 3 Nos. Mounting Hardware Packet { Containg 1 Nos Each Of 3 } - 20 Set, 1 Nos. Power Distribution Unit - 06/16 Amp Indian-Standard - 10 Socket - Single Pole / Screw Mountable / 16 Amp MCB / Alternating Current - 16 Amp 3 Pin Plug with Power Cable 2.5 sq.mm 3 meter Length, 2 Nos. Metal Cable Channel - 100 mm Width - 800 mm Height - Pastal Fine Tex. - Assembly, 1 Nos. Earthing Strip - 150mm - Nickel Plating - Assembly, and IP20. Make Legrand/Dynamic Rack/Commscope
Supply and Installation weather proof lockable cabinet of size not less than 900X600X450 mm made out of 20gauge MS (as per BOQ) powder coated sheet of fully welded construction with hinged double front door partially glazed (3 mm glass panel).with locking arrangement, stove enamelled fire red paint (shade No. 536 of IS:5) including necessary locking arrangement and shall be painted with one coat of primer and two coats of synthetic enamel paint of approved shade. (External Cabinet).
Providing and fixing angle iron (40 mm x 40 mm x 5 mm) MS door frame with 16 G MS sheet, 900x2100 door capable of accommodating fire hose reel, landing valve, hose pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate.
Providing, fixing, testing and commissioning of Air vessel of 400mm dia for pressurization of fire system complete with valves at outlet / drain to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, outside with one coat of primer & two coats of synthetic enamel paint of approved shade complete as required to operate commonly main fire pump, sprinkler pump & jockey pump at drop of pressure, automatically at required pressure setting. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge. working pressure:- 7 kg/sqcm test pressure: 10 kg/sqcm (Make: Lifeguard/Chawla/Firex/Getech/Newage)
Providing fixing, testing & commissioning of Draw out connection 100 mm
Providing fixing, testing & commissioning of Foot Valve connection 150 mm
Providing fixing, testing & commissioning of Foot Valve connection 100 mm
Providing, fixing, testing & commissioning of Air release valve with 15mm dia (Make: Kirloskar/Audco/Advance/Zoloto/Sant)
Providing and fixing 25 mm dia inspection & testing assembly with Test valve, union with corrosion resistant orifice & connection to drain
S/I/T/C of ball valves with screwed ends confirming to IS 1703 -1977 with unions, etc.including all the necessary fixing materials complete. (Make: Kirloskar/Audco/Advance/Zoloto/Sant)
Providing, fixing, testing & commissioning of resilient rubber bellows single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as (Make: Resisto easy-flexo / d. wren)
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
Providing and fixing Fire related signages printed on photoluminescent U1000 aluminium sheet of 1.0 mm (+-10%) containing Lumigen II as base chemical, covered under UV stablized coating and of appropriate size including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects as directed by Engineer-in-charge.
Providing and fixing of emergency exit light.
Providing and fixing mechanical foam type (ISI marked) fire extinguishers consisting of welded M.S. cylindrical body squeeze lever discharge valve 30 cm long high pressure discharge hose, discharge nozzle, suspension bracket as per ISI marked finished externally with red enamel paint and fixed to wall with brackets complete with internal charger. Capacity 50 lit.(Trolley mounted) (Make: Cease Fire / Lifeguard / Omex / Minimax/ Kalpex / Safeguard)
SITC of Intelligent Addressable, Supervised Monitor Module monitoring Potential-free, Normally Open Dry Contact input. The Monitor Module shall have operating temperature range from 0°C to 70°C and a humidity tolerance of up to 93% RH, Non-Condensing with weatherproof enclosure
S/I/T/C of Fully automatic(by Level Controllers with sensing probes) MBBR Technology based Sewage Treatment Plant process below and above ground with sewage and effluent handling capacity as given below. The STP shall be designed as water retaining structures in RCC or MS structure including necessary chemical dosing as required by the manufacturer's design. All the equipment, piping, pumps, blowers and electrical to be housed in a plant room nearby. Inlet, outlet overflow, vent, M.S. cover, drain channel with M.S. gratings sumps if required to be provided as per the site condition. (The total system to be designed as a Trunky project which includes detailed design engineering of civil/ structural /Biological/ Electro-Mechanical and treated effluent should meet the acceptable parameter. The STP shall be designed based on the following Inflow parameters: * PH : 6.5 - 8.5 * BODs : 300-400 * S. Solids : 200 - 450 Mg/l * COD : 600 - 800 mg/L * Oil & Grease : 50-100 mg/L * PH : 6.0 - 8.5 * BODs :less than 20 mg/l * S. Solids :Less than 20 mg/l * COD :Less than 100 mg/l * Oil & Grease :Less than 5 mg/l
Associated civil work for STP including foundation of pumps & equipment, M S structural work etc. is included in this scope Supply of all required Civil & Mechanical/Electrical shop drawings to be prepared by the contractor and approved by Project Manager. Contractor shall include all electrical mechanical items as required to operate the system automatically/ manually and also include in his rates level controller, electrical wiring cables earthing main control panel and connection to be various equipment’s, other accessories complete as required. Only main power supply with the earthing to be STP main control panel shall be provided by the owner through other agencies. STP should follow all the concern Indian CPCB and Local norms and to be got approved from statuatory authority. Bypass arrangement shall be provided as shown in the drawings such that equalization tank pump can be used to pumpout sewage to external manhole incase of maintenance of STP. A S.T.P OF CAP - 65 KLD.
Domestic Water Pump (Hydro pneumatic System With Variable Speed Pumps) Providing, fixing and testing of packaged fixed drive type skid mounted hydro pneumatic system comprising of :- Vertical, inline multistage centrifugal pumping set with stainless steel SS-304 stage casing and SS-304 impellers with stainless steel SS-316L shaft as per IEC standards and GJL250 cast iron suction & discharge casing, connected to TEFC ventilated induction motor of 2 pole, 2900rpm, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply No. of Pumps: 3 (2 Working +1Standby)=1 set Pressure vessel of non corrosive FRP composite construction lined with NSF and/or FDA listed material, like high density polyethylene with fully replaceable polyurethane. Air cell burst pressure of minimum of 5 times the vessel operating pressure and cycle tested for 2,50,000 cycles. No. and capacity of Pressure Vessel – 01 Nos. x 200 Ltrs (Make: Lubi/Crompton/KSB)
Control Panel with programmable logic controller (PLC) for cyclic operation of pumps. Pump working sequence should change after every operation. Contractor overload relays and MCBs should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low level trip, health supply should be provided in the panel along with the ammeter & voltmeter. Control panel should also consist of cooling fan. Pressure switches bellow type fitted with micro switch and having maximum pressure and differential scale should confirming BS-6134 standards and IP55 protection class. Stainless steel suction and delivery header, ball valve on each pump on section delivery side, non return valves, Y stainer complete in all respect. Ball valves to be used should be Hot Pressed brass OT-58 with stainless steel ball and P.T.F.E seal and O-Ring. NRVs to be used should be with Springs and O-Ring arrangement. Complete set system to be mounted on a common base frame and shall follow following duty. For Domestic Water Supply Set of Two Pumps( 1Working+ 1 Standby) Capacity : app. 450 lpm Head : app. 60 m
Annunciation and indication panel Minimum 4 level Multi level indicators with magnetic type sensor probes complete Supplying, installing, testing and commissioning of annunciation and indication panel with interlocking arrangement complete in accordance to specification for level controller etc with control cabling from field to MCC as required. The system shall be complete to ensure automatic operation of pump in accordance to water level in respective tanks. Providing & fixing level controllers for water pumps to start/stop the pump at set level. Including wiring, cabling from pump to panel & all other accessories as required to operate the system automatically Providing & fixing pressure switch for water pumps to start/stop the filter feed pump at set pressure. Including wiring, cabling from pump to panel & all other accessories as required to operate the system automatically.
Operation cost for 1st year including 2 electricians, 2 electrical helpers and 1 mechanical Operator all operating / working round the clock (24 Hours)
Operation cost for 2nd year including 2 electricians, 2 electrical helpers and 1 mechanical Operator all operating / working round the clock (24 Hours)
Operation cost for 3rd year including 2 electricians, 2 electrical helpers and 1 mechanical Operator all operating / working round the clock (24 Hours)
Operation cost for 4th year including 2 electricians, 2 electrical helpers and 1 mechanical Operator all operating / working round the clock (24 Hours)
Operation cost for 5th year including 2 electricians, 2 electrical helpers and 1 mechanical Operator all operating / working round the clock (24 Hours)
Comprehensive maintenance contract for 2nd year of all electrical and mechanical equipments/machines.and sub equipments.
Comprehensive maintenance contract for 3rd year of all electrical and mechanical equipments/machines and sub equipments.
Comprehensive maintenance contract for 4th year of all electrical and mechanical equipments/machines and sub equipments.
Comprehensive maintenance contract for 5th year of all electrical and mechanical equipments/machines and sub equipments.
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .