Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹68.6 LAccepted-AOC 2 209 1 NANGAVARAM ROAD PERUGAMANI POST SRIRANGAM TALUK TIRUCHIRAPPALLI | TIRUCHIRAPPALLI | TAMIL NADU | 620001 | L1 | Accepted-AOC 1st lowest | |
| 2 | L2₹75.0 L+₹6.4 L (9.36%)Rejected-Finance NO 43 AVINASHI ROAD GOLD WINS CIVIL AERODROME POST COIMBATORE 641 014 | COIMBATORE | TAMIL NADU | 641014 | L2 | Rejected-Finance 2nd lowest | |
| 3 | L3₹75.6 L+₹7.0 L (10.3%)Rejected-Finance 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L3 | Rejected-Finance 3rd lowest | |
| 4 | Not Admitted-Fee/PreQual/Technical/Finance | - | Not Admitted-Fee/PreQual/Technical/Finance Others-Insufficient document | |
| 5 | Not Admitted-Fee/PreQual/Technical/Finance NO 31 A ANNA NAGAR SUBRAMANIYAPURAM TRICHY 20 | TRICHY | TRICHY | TAMIL NADU | 620020 | - | Not Admitted-Fee/PreQual/Technical/Finance Others-Insufficient document |
Tender Value
₹72.4 L
EMD Value
₹46,200
Closing Date
21 Feb 2024, 3:00 pmClosed
Superintending Engineer
Office of the Superintending Engineer, P.W.D., Buildings (C and M), Circle, Trichy-1
Provision of Internal and External Electrification to the 59 Class room building in Government Model Girls Higher Secondary School at Mannachanallur in Trichy District.
2024_PWD_425493_1
Tn.No.33SE/Dt.06.02.2024
Open Tender
Electrical Works
Lump-sum
150 days
Mannachanallur
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹46,200
7 Mar 2024
15 Feb 2024
21 Feb 2024
15 Feb 2024
21 Feb 2024
15 Feb 2024
Amount
Wiring with 2x1.5sqmm (22/0.3) PVC insulated SC unsheathed Cu. Conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with PVC accessories in flush with wall with 1 module white cover plate with frame (Plastic) with 1 module flush mounting box (GI) and 6A 1way SP 1module switch and making good of the concealed portion with suitable colour for PVC concealed light / Fan Point (For electronic regulator) (5 Points Per Coil) (Make:Crabtree/Legrand/Hager/Equivalent)
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with PVC accessories with suitable Module GI switch box in flush with wall with 1 no. 6A one way module switch and 1 no. 6A 3/2 pin module socket with module front plate with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with painting of suitable colour for concealed PVC pipe Plug point ( 8 points / Coil) Higher End
Supply and fixing of single box type 4’20W LED fitting with LED with TW round blocks on wall or ceiling with PVC unsheathed Copper leads from terminals to the fitting. (Hire end) (Make:Philips/Havells/Equivalent)
Supply and fixing of 1200mm (48") A.C ceiling fan Crompton High speed (Higher End) complete with Fan step regulator 100w 2 module in suitable 1/2 module metal flush type box covered with 2 module white cover plate (Higher End) with 300mm down rod on the existing fan clamp. (Make : Crompton / Usha )
Supply and fixing of 30W solar street light with 50mm dia GI pipe (Class 'B') with 1 No. 50mm GI bend complete on the existing post/wall with MS clamps and aluminium painting.(HIGHER END) (Make : Philips / Crompton/Havells )
Supply and fixing of LED Flood light 150W with Integrated Driver (Higher End) complete with MS angle with PVC unsheathed Copper leads from terminals to the fitting.
Supply and fixing of 1 no.6/16A two module socket , 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End (Make: Crabtree/ Legrand/ Hager/equ)
Supply and fixing of 3nos.6A two module 5 pin socket , 3 nos. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End (Make:Crabtree/ Legrand/ Hager/ equ)
Supply and Run of 2 of 2.5 sq.mm. (36/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour.
Renewal by Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB switch as incoming and 6 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End
Supply and run of 2 of 4 sqmm (56/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14SWG TC wire and making good of the concealed portion with suitable colour .
Supply and fixng of TNEB meter board suitable for 3 phase 100A service connection made up of suitable angle iron frame work of size 2 feet x 1-1/2 feet using angle iron of size 1-1/2" x 1-1/2" x 1/4" rigidly fixed on wall covered with hylem sheet of size 2 feet x 1-1/2 feet of 12mm thickness with necessary bolts and nuts supports and supply and fixing of 3 Nos. 100A fuse units (500V), 1 No. neutral link, copper earth flat of size 1" x 1/4" with inter connection of EB meter to fuse units by 16 Sq.mm PVC insulated copper wire with earth connection complete (30 Class Room building - 1No. 20 Class Room building - 1No.)
Supply and fixing of 100A TPN sheet steel double break switch with HRC fuses and neutral on suitable angle iron frame work with MS cable entry boxes and with earth connection only
Supply and fixing of 4 way Horizontal Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A 4P MCB switch as incoming and 12 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End
Supply and run of 4 of 4 sqmm (56/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14SWG TC wire and making good of the concealed portion with suitable colour .
Supply and laying of 4 x 16 sq.mm PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good.
Supply and clamping of 4 x 16 sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps.
Supply and fixing of brass cable gland for 4 x 16 sq.mm. PVC armoured LTUG cable with earth connection.
Supply and providing cable end termination of 4 x 16 sq. mm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Supply and fixing of vertical type 4 way triple pole MCB DB with metal door cover with IP 42 protection in sheet steel enclosure with 1No. 63A 4 pole MCB as incoming 3Nos. 32A TP MCB and 3Nos. 6 A to 32 A SP MCB as outgoing in flush with wall and making good of the concealed portion with earth connection. The MCB DB and MCB's should be with the ISI mark (Higher End)
Supply and laying of 2 x 10 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 metre layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good.
Supply and clamping of 2 x 10 sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps.
Supply and fixing of brass cable gland for 2 x 10sq.mm. PVC armoured LTUG cable with earth connection.
Supply and providing cable end termination of 2 x 10 sq. mm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Supply and laying of 31/2 x 25 sq.mm PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good.
Supply and clamping of 31/2 x 25 sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps.
Supply and fixing of brass cable gland for 31/2 x 25 sq.mm. PVC armoured LTUG cable with earth connection.
Supply and providing cable end termination of 31/2 x 25 sq. mm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Supply and laying of 31/2 x 50 sq.mm PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good.
Supply and clamping of 3 ½ x 50 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps.
Supply and fixing of brass cable gland for 3½ x 50 sqmm PVC armoured LTUG cable with earth connection
Supply and providing cable end termination of 3 ½ x 50 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete
Supply, Installation, Testing, Commissioning and Handing over of 10 Kwp Roof mounted Solar PV System Scheme complete as detailed below. Design, Engineering, Manufacturing, Procurement, Supply of materials to project site, project management, installation of mechanical equipment, cabling & appurtenances, instrumentation and electrical system and other equipment, as detailed in this section. Scope of the proposal a)Solar Modules (Crystalline Silicon type mono perc half cut -as per MNRE specifications) b)Mounting Structure (Design to Trichy ambient condition) c) Inverter, distribution boards, junction boxes, cables d)Earthing for Solar modules and inverter. e) Lightning Protection f) Installation and commissioning TECHNICAL SPECIFICATIONS 1. SOLAR PV MODULES AND ARRAY SITC of On grid Solar PV Modules of the crystalline silicon type- mono perc Half cut,Conforming to MNRE specification mounted on Aluminium frame(minimum thickness 35 mm) With minimum module efficiency of 20%, manufactured in India.As per latest edition of IEC PV module qualification test or equivalent BIS standards Crystalline Silicon. Matching IEC 61215/IS14286 and IEC 61730 Part-1 & Part 2 standards or equivalent BIS. With neccessary MC4 connectors (IP66) ,Interconnecting between panels using solar dc cable of min 4 sqmm and installation on exsisting structure .Solar crystalline modules of minimum 540 Wp or above wattage. With Protective devices against surges at the PV module.Along with Low voltage drop bypass diods . Solar Panels should be tested in the IEC authorized test centers. The rated output tolerance should be + 3 % . 10 years of product warranty 25 Years of linear power output warranty (90% of rated output at the end of 10years and 80% of rated output at the end of 25 years ) • Makes- Havells, Panasonic, Bosch,TATA
7.OPERATION AND MAINTENANCE MANUAL An Operation and Maintenance Manual, in English and Tamil, should be provided with the solar PV power plants. The following minimum details must be provided in the Manual: About Photo Voltaic & PV Module Clear instructions about mounting of PV module. About electronics used in DO's and DONT's, Clear instructions on regular maintenance and Trouble Shooting of the power plants. Name & address of the person or Centre to be contacted in case of failure or complaint.The equipment/materials and the whole system should be operated by trained personnel of the purchaser after giving training. The periodical maintenance, cleaning of the Solar Panels should be done by the firm/Supplier/Contractor for a period of five years. 8.Grid – Tie Solar PV System i)Solar PV Modules ii)Structure for mounting modules iii)Drive iv)Cabling to PV module to drive v)Installation and Commissioning 9.WARRANTY (i) Solar panel at 90% efficiency - 10 years (ii) Solar panel at 80% efficiency - 25 years (iii) Inverter - 10 years WARRANTIES & GUARANTIEES: The goods supplied under this contract are new, unused, of the most recent or latest technology and incorporate all recent improvements in design and materials. This warrantee will also be covering the rectification of any and all defects in the design of equipment, materials and workmanship including spare parts for the guarantee period specified by MNRE/ TEDA from the date of commissioning. All the Guarantees / Warrantees of the different components will be transferred to Owner of the project. (Make :-Tata Power/Havells/Panasonic/Bosch).
Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm, with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry .
Supply and Run of 1 of No.8 SWG hard drawn copper in suitable PVC rigid pipe concealed in wall ceiling and making good of the concealed portion with suitable colour.
Supply and run of 25 mm x 6mm GI flat Down Condutor with necessary clamps / supports on wall / floor / ground for earth connection.
UNIVERSAL CIRCUITS
rv electricals
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .