Superintending Engineer (EWCL)
Type-IV/3, Transmission Staff Colony Dewa Road, Chinhat Lucknow
Increasing capacity of 33/11 KV Sub-station Biswan Town Sitapur existing from 2x5 MVA to 1x5 Plus 1x10 MVA
2023_MVVNL_780766_1
27/EWCL/2022-23
Open Tender
Electrical Works
Fixed-rate
90 days
33/11 KV Sub-station Biswan Town Distt. Sitapur
As per tender documents
2 documents required · 2 mandatory
₹1,180
A/c No. 0758002100009592, IFSC PUNB0586800
₹9,000
1 Apr 2023
3 Mar 2023
22 Mar 2023
3 Mar 2023
22 Mar 2023
3 Mar 2023
Amount
Safe loading, carriage and unloading & proper stacking of following store materials from any Electy. Store of Lucknow Zone to 33/11 KV S/S Biswan Town,Sitapur site (work site).
33 KV Lightening Arrester
MS Angles 75x75x6mm
ACSR Panther Conductor
MS Channel 100x50 mm
PVC cable1x400 sq. mm.
Dismantling & safe shifting of existing & working 33/11 KV 05 MVA T/F from plinth to suitable storage place after opening jumper and cable connections as per instruction of Site Engineer.
Repairing of Power Transformer Plinth for 10 MVA T/F.
Earthing for power T/F by way of boring and lowering of 40mm dia, 2.9 mm thick GI Pipe B class from ground upto the water level (minimum 60 feet deep) as per standard practice as per RESPO/REC Drg with making of earth pit of 300x300 mm & 1 feet deep with Cover. (All materials to be provided by Contractor).
Fabrication and grouting (1:4:8) of MS Channel 100x50mm in L Shape & in proper size and alignment to provide support through GI earthing strips (50x6)mm size for power transformer neutral including supply & fixing of flexible copper bonds for neutral earthing as per RESPO Drg. (All decentralised materials to be provided by Contractor).
Fabrication and erection of cable support made of two pieces of MS channel 100x50mm, 3.0 mtr. long joined to each other by means of 5 no. MS Flat 50x6mm pieces of size 150mm long each by welding at equal intervals as per drawing and grouting in block of size 300x300x700mm (1:4:8) complete. This includes providing of required MS Clamp made of MS Flat holding the cable including nuts & bolts and fixing of XLPE cable.
Installation of Lightening Arrestors : Assembling, installation & mounting of 3 No.(1set) L.A. on the L.A Structure/complete with making earth connections (separate) with GI Strip 50x6mm. The work includes fabrication for fixing if required. (All decentralised materials to be provided by Contractor).
Painting of all structures and equipments with good quality ISI Mark one coat of red oxide primer & two coats of Aluminium Paint. (All materials to be provided by Contractor).
Supply and laying of following size Copper Control Cable through underground/cable trench/trenching SGR interlinking through proper connections to T/F Control panel/protection board/Battery and Battery Charger/Bunch joints, Relay 33/11KV T/F junction Box/33KV VCB, CTs etc. as per site conditions:
4x2.5 Sq.mm
Supply and fixing of Control Cable Trey
Fixing of Single Core PVC Cable, 1x240/400/630 sq.mm. & fixing between Transformer incoming 3x300 Sq.mm XLPE Cable and Transformer 11 KV/LV Side Bushing connector for reducing of tension at LV Side Bushing.
Supply and Installation of 24 Volt Battery and it charger with connections to existing control circuit complete in all respects.
SINLESS ELECRICAL CO. PVT. LTD.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .