Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹24,205
Closing Date
29 Jun 2026, 1:00 pm
Executive Engineer
Saktinagar District Hospital Campus Krishnanagar
SITC of new Split AC at the ANM (R ) within the campus of COM and JNM Hospital under Kalyani Electrical Sub-Division at Kalyani, Nadia.
2026_WBPWD_5015375_1
WBPWD/EE/NED/NIQ/e-T/04/ (1st Call)26-27
Open Tender
ELECTRICAL WORKS ORG
15 days
Saktinagar District Hospital Campus Krishnanagar
Please refer Tender documents.
6 documents required · 6 mandatory
₹24,205
Nadia Electrical Division PWD
11 Jun 2026
11 Jun 2026
1 Jul 2026
11 Jun 2026
29 Jun 2026
15 Jun 2026
15 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing, and Commissioning of air-cooled Hi-Wall split type air conditioners of following Cooling Capacity, Air Flow Rate and Minimum ISEER: 5.0, BEE level - 4-Star (min) comprising Indoor and Outdoor Units with factory charged Rotary/Scroll compressors (R-32/R-410A) including surface/concealed copper refrigerant piping insulated with closed-cell elastomeric nitrile rubber insulation and wrapping tape (up to 3 m), FRLS type copper power cable (up to 3.5 m) (Make: RR Kabel Ltd./Finolex/Havells) with suitable plug top (Make: Anchor), 3 meters of drain pipe, and wireless remote control with suitable battery. The system shall operate on a 230 V, 50 Hz (± tolerance as per the applicable standard), single-phase AC supply, providing cooling, dehumidification, and air circulation functions, conforming to IS-1391 (Part-II) with all amendments. It shall be capable of efficient performance at outdoor ambient temperatures up to 50° C, with a minimum 5-year OEM warranty on both the compressor and PCB. The system shall be installed with S&F appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections, including T&P & labour, etc., as required, complete in all respects as per the direction of EIC (Make: MITSUBISHI ELECTRIC / Daikin / O-General / Carrier)
Cooling Capacity: 5.2 KW (Minimum) and Air Flow Rate: 600 CFM (Minimum) | 4 | Sets | - | - | item1 |
| 1.1 | Cooling Capacity: 6.1 KW (Minimum) and Air Flow Rate: 800 CFM (Minimum) | 12 | Sets | - | - | item2 |
| 2 | Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 12 | Mtr | - | - | item3 |
| 2.1 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 36 | Mtr | - | - | item4 |
| 2.2 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 48 | Mtr | - | - | item5 |
| 3 | S & F of the following additional items for length exceeding 3.5 mtr for complete installation and commissioning of the above AC machines. i) 2.5 sq. mm, 3/4 core copper cable (FRLS type) (Make: RR Kabel/Finolex/Havells). | 80 | Mtr | - | - | item6 |
| 4 | Supply & laying Soft Drawn PVC Drain Pipe exceeding 3 mtr of 19 mm dia with proper supports & brackets as per direction EIC. (Make: Suprime/Oriplast) | 80 | Mtr | - | - | item7 |
| 5 | Supply & Fixing 'FR' type Heat resistant 3" Insulation tape for Heat resistant | 240 | Mtr | - | - | item8 |
| 6 | Taken down the Indoor & Outdoor Unit of Split type AC Machines (1.5/2 ton) from its existing installation place and refitting the same at authorities noted place within the campus of ANM(R ) Training School COM&JNM Hospital after servicing & repairing as required. | 3 | Nos | - | - | item9 |
| 7 | Supplying and fixing 415 V, 63 A TPN SFU (Make: L&T/Havells/ABB/Siemens) with sheet steel enclosure on angle iron frame on wall with nuts, bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. [SOR:D-3/4(a)] | 2 | Nos | - | - | item10 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.19 MB
BOQ_5084150.xls
BOQ • 0.29 MB
form2911.pdf
Tender Documents • 0.50 MB
Download all tender documents and submit your bid