Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹14,785
Closing Date
4 Aug 2026, 4:00 pm
Room No. 108, Purta Bhawan, Salt Lake
Room No. 108, Purta Bhawan, Salt Lake
Major repairing works Civil and Electrical in the Chamber of the Honble MIC and in the Chamber of the Honble MOS of School Education Department 5th Floor Bikash Bhawan, Salt Lake, Kolkata-91.------ SITC of Air Conditioning System
2026_WBPWD_5016976_1
WBPWD/EE/BED/e-NIQ-83/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
14 days
Bikash Bhavan
Please refer Tender documents.
6 documents required · 6 mandatory
₹14,785
Room No. 108, Purta Bhawan, Salt Lake
17 Jul 2026
17 Jul 2026
6 Aug 2026
24 Jul 2026
4 Aug 2026
28 Jul 2026
27 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing, and Commissioning of Window type Air conditioners of following capacities comprising copper Evaporator & Condenser Coil with factory-charged Rotary/Scroll compressors (R-32/R-410A) including FRLS type copper power cable (up to 3 m) with suitable plug top and wireless remote control with suitable battery. The system shall operate on 230V, 50Hz (±tolerance as per applicable standard), single-phase AC supply, providing cooling, dehumidification, and air circulation functions conforming to IS-1391 (Part-I ) with all amendments, and shall be capable of efficient performance at outdoor ambient temperatures up to 50°C, with a minimum 5-year OEM warranty on both the compressor and PCB. Sound level of up to 56 dB inside the room is acceptable The system shall be installed with S&F appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections including T&P & labour etc as required complete in all respect as per the direction of EIC. (Make-O General/ Mitsubishi Electric/Daikin)
Cooling Capacity- 5.0 kW (Minimum) , Minimum ISEER- 3.5, BEE level- 4 Star(min). | 6 | Nos. | - | - |
| 2 | Supply, Installation, Testing, and Commissioning of 230V, 1 phase, 50 Hz Inverter Type Ceiling suspended Cassette type Air conditioners complete with wireless Remote having the capable of performing of cooling capacity 26000 BTU/hr or 7620 W (Minimum), dehumidification, air circulation, R- 32/R-410A Green Refrigerant and variable speed inverter rotary compressor with 100% copper condenser coil with anti-corrosion coating, ISEER more than 5 and Air flow rating 990 CFM (Min) including Printed Circuit Board (PCB) with metal enclosers and min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and PCB and maintaining the noise level between 35 dB to 45 dB at inside the room is acceptable. The unit shall be in confirmation with IS 1391 Part-II 2023.The system shall be able to deliver 100% of the rated capacity upto 42 degree C and operate up to 52 degree C ambient temperature [Make-O-General/Mitsubishi Electric/ Daikin] | 4 | Nos. | - | - |
| 3 | SITC including vaccumiazation and Nitrogen of testing of following nominal size of soft/hard drawn copper refrigerent piping Split AC system, complete with fittings and including accessories, insulated with XLPE class -O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for suction and liquid lines, all accessories as per specification etc. as required.
1/4" (6.4 mm) dia (Soft drawn) Cu. Pipes (As per standard BS864 or ANSIB 16.22) incl. 19 mm thick insulation. | 42 | P/Mtr | - | - |
| 3.01 | 5/ 8" (15.88 mm.) dia (Soft drawn) Cu. Pipes (As per standard BS864 or ANSIB 16.22) mm incl. 19 mm thick insulation. [NS] | 42 | P/Mtr | - | - |
| 3.02 | S&F of additional following items for length exceeding 3.5 mtr for complete installation and commissioning of aboove AC machines. (KEI/Finolex/RR Kable)
2.5 sqmm, 3/4 core copper cable (FRLS type) | 50 | P/Mtr | - | - |
| 4 | Supply and laying PVC Drain Pipe 25mm dia nitrail rubber insulation. [Make:- Suprime/Oriplast] | 50 | mtr | - | - |
| 5 | Supply & laying Soft Drawn PVC Drain Pipe 19mm dia with proper supports & brackets as per direction EIC. [Make:- Suprime/Oriplast] | 20 | mtr | - | - |
| 6 | Dismantling of 1.5 ton/ 2.0 ton Air Conditioner unit (window type) after gas locking arrangement with necessary tools & tackels and store in safe place as per direction of EIC. | 6 | No | - | - |
| 7 | Supplying, fabrication & fixings MS U-channel of 6 mm thick of size (75mm x 40mm x 40mm) for making Base Frame/ platform for installation of outdoor unit of above mentioned AC machines incl drilling 2 nos holes in each channel, cutting holes into the wall & grouting the same with C.C. (1:1.5:3) etc. fabricated with horizontal angle of 25mm x 25mm x 6mm and supporting angle of 50mm x 50mm x 6mm in each platform. The platform should be baricaded and set for ODU machine in outer age for transmitting the load centrally through 2 nos (50mm x 50mm x 6mm) angle inserted into the wall incl. fibre sheet shade as per direction of E.I.C. The area of the platform is of suitable size as per machine configaration and load with addiquiet service access & safe to carry out the maintenance of ODU as per direction of EIC. The design of platform structure to be approved by EIC. (4 nos X 65 kg= 260 kg) | 260 | P/Kg | - | - |
| 8 | Making one set of scaffolding only for replacing glass panels, painting, uprooting plant and another repairing works of building and S&P works for external works only with 10 cm. dia bamboo as main posts at the rate of 1 metre centre to centre and 7.5 cm. dia bamboo ties @ 0.75 metre apart fitting and fixing with necessary coir, nails etc. as per direction of the Engineer-incharge.
(This item should be executed only after prior approval of the Engineer-incharge). Firstly, one number to be paid and then labour rate for shifting up to further nineteenth (19) times @ 10% each time to be considered. If necessary further after twenty times of total use, another one number new and labour rate for shifting to be considered accordingly.
a) 3.90 metre height | 15 | each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.72 MB
2911_ii.pdf
Tender Documents • 0.50 MB
BOQ_5086868.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].