Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹93,700
Closing Date
31 Aug 2026, 3:00 pm5d left
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Vadodara Division: Electrical works in connection with improvement to allied facilities of various existing Track Machine sidings over BRC Division.
BRC-EL-P-02-2541-26-27-R~WR
BRC-EL-P-02-2541-26-27-R
Open
Works - General
6 Months
Vadodara, Gujarat
₹0
₹93,700
7 Aug 2026
7 Aug 2026
17 Aug 2026
78 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | Above/ Below/Par | ||
| — | — | — | 42,45,003 | ||
| — | 95.00 | — | — | ||
| Wiring of light/fan/exhaust fan points in concealed manner with modular accessories - The price shall cover for concealed wiring of light/fan/exhaust fan point with 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. | — | — | — | 38,760 | |
| — | 13.00 | — | — | ||
| Providing plug point 6 Amp in concealed manner on existing board with modular accessories - The price shall cover for providing plug point with modular type universal socket and switch, 6 Amp, 230 Volt, AC on existing board. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. | — | — | — | 1,261 | |
| — | 5.00 | — | — | ||
| Providing plug point 6 Amp in concealed manner on separate board with modular accessories - The price shall cover for providing plug point board with modular type universal socket and switch, 6 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/ MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make. | — | — | — | 1,675 | |
| — | 8.00 | — | — | ||
| Providing plug point 16 Amp in concealed manner on separate board with modular accessories - The price shall cover for providing power plug point with modular type universal socket and switch, 16 Amp, 230 Volt, AC on separate board with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of plug point with 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make. | — | — | — | 3,568 | |
| — | 1.00 | — | — | ||
| Providing board with two switches and two socket, 6 Amps in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 6 Amp - 2 Nos and universal socket, 6 Amp - 2 Nos) with modular type universal five-pin socket and switch, 6 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make. | — | — | — | 237 | |
| — | 3.00 | — | — | ||
| Providing board with four switches and four sockets, 6 Amp in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 6 Amp - 4 Nos and universal socket, 6 Amp - 4 Nos) with modular type universal five-pin socket and switch, 6 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make. | — | — | — | 1,353 | |
| — | 395.00 | — | — | ||
| Concealed wiring of sub-main with 2.5 sq. mm in PVC conduit - The price shall cover for concealed wiring of sub main with two-wire single core 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit. | — | — | — | 35,155 | |
| — | 120.00 | — | — | ||
| Concealed wiring of sub-main with 2.5 sq. mm in existing PVC conduit - The price shall cover for wiring of two wire sub-main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in existing PVC conduit. | — | — | — | 9,120 | |
| — | 250.00 | — | — | ||
| Concealed wiring of sub-main with 4.0 sq. mm in PVC conduit - The price shall cover for concealed wiring of sub main with two-wire single core 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit. | — | — | — | 27,250 | |
| — | 19.00 | — | — | ||
| Providing Electronic fan regulator, modular type - The price shall cover for supply, fixing, testing and commissioning of hum-free modular type electronic fan regulator suitable for 80/100-Watt ceiling fan of step type with 'OFF' position, surface/flush type on existing board and its connection from existing supply. Miniature switch type regulators shall not be accepted. The regulator shall be of Anchor-Roma/Cona/ Leader/Crabtree/Legrand/C&S/HPL/Indo Asian/Havells/Standard/Bentec/Elleys/Precision make. | — | — | — | 5,301 | |
| — | 19.00 | — | — | ||
| Fixing, testing and commissioning of ceiling fan - The price shall cover for fixing, testing and commissioning of ceiling fan on existing hook and its connection by FRPVC insulated, flexible copper cord, 1100Volt grade, 24/0.20mm from existing ceiling rose with earth connection. A suitable suspension clamp made from G.I. flat of 40 x 6 mm with MS 'S' shaped hook of diameter not less than 10 mm shall be provided as per site requirement if fan hook is not available and is included in the scope of work. The ceiling fans shall be supplied by railways at site in-charge's office/store. | — | — | — | 3,287 | |
| — | 9.00 | — | — | ||
| Providing Exhaust fan 300 mm sweep/heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 300 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of make Crompton Greaves/GEC/ Almonard/Usha/Bajaj. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade. | — | — | — | 13,149 | |
| — | 10.00 | — | — | ||
| Providing Ray Roll plug and socket, 20 Amp with MCB DP, 16/20 Amp in weather proof box - The price shall cover for supply, erection, testing and commissioning of power plug board with one MCB DP 16/20 Amp, ray-roll socket 16/20 Amp and LED indication lamp in weather proof MS enclosure. The MCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/Schneider/Havells make. The MS enclosure shall be properly earthed. | — | — | — | 12,060 | |
| — | 6.00 | — | — | ||
| Providing lighting control board with MCB DP, 32 Amp - 1 No, Time Switch, 16 Amp - 1 No and Single-Phase Contactor, 32 Amp - 1 No - The price shall cover for supply, fixing, testing and commissioning of lighting control board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The board shall be equipped with MCB DP, 10 KA breaking capacity, 32 Amp rating - 1 No, Time switch, 16 Amp - 1 No and Single phase contactor of rating 32 Amp - 1 No. The MCB shall be of ABB/L&T/HPL/GE/ MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make, the contactor shall be of L&T/BCH/C&S/CGL/ Schneider/Siemens make and Digital Time Switch "CRONO" of L&T make or similar of Siemens/Minilec make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 25,266 | |
| — | 3.00 | — | — | ||
| Providing Distribution Board with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 25 Amp - 1 No and outgoing MCB SP, 6/10/16 Amp - 4 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer MCB DP 16/32 Amp - 1 No, RCBO, two-pole, 30 mA sensitivity, 25 Amp - 1 No and outgoing MCB SP, 6/10/16 Amp - 4 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi- stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 15,453 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of SFU, four-pole, 125 Amp with outdoor type MS - The price shall cover for supply, fixing, testing and commissioning of Switch dis-connector fuse unit four-pole, 415 Volt, 125 Amp with backup HRC fuse of 125 Amp capacity, AC-23A duty conforming to IEC 60947/IS 13947 in sheet steel modular enclosure or pre-fabricated double-door enclosure of same make as the Switch dis-connector fuse unit as far as possible. The enclosure should be suitable for outdoor installation conforming to IP: 65 protection. The SFU shall be of ABB/L&T/HPL/GE/MDS/Siemens/ BCH/C&S/Schneider/CGL/Havells make. | — | — | — | 5,852 | |
| — | 1.00 | — | — | ||
| Providing Distribution Board with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 25 Amp - 1 No and outgoing MCB SP, 6/10/16 Amp - 6 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer MCB DP 16/32 Amp - 1 No, RCBO, two-pole, 30 mA sensitivity, 25 Amp - 1 No and outgoing MCB SP, 6/10/16 Amp - 6 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi- stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 5,906 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of MCCB, four-pole, 125 Amp in existing panel - The price shall cover for supply, fixing, testing and commissioning of MCCB, four-pole, 125 Amp, with thermal-magnetic release range 100 - 125 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The MCCB shall be supplied with spreader terminals and rotary handle and shall be installed in the existing panel. The MCCB should be compatible with the existing panel. | — | — | — | 7,046 | |
| — | 2.00 | — | — | ||
| Providing Distribution Board, outdoor type, double door, with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 1 No and MCB DP, 16/20/32 Amp - 4 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 1 No and MCB DP, 16/20/32 Amp - 4 Nos. The MCBs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 14,574 | |
| — | 16.00 | — | — | ||
| Supply, fixing, testing and commissioning of three-phase, 415 Volt, 63 Amp, heavy duty, power panel with MCCB, three-pole, 63 Amp - 1 No, three-phase, 440 Volt, 63 Amp power plug - 1 No, MCB DP, 20 Amp - 1 No and single-phase, 230 Volt, 20 Amp ray-roll plug and socket - 1 No in outdoor type MS enclosure - The price shall cover for supply, fixing, testing and commissioning of three-phase, 415 Volt, 63 Amp, heavy duty, power panel fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The board shall fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories - (i) MCCB, three-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS: 13947 (part 2) / IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T (Hagar)/GE/MDS/Siemens/ BCH/C&S/HPL /Schneider/Havells make --- 1 No (ii) MCB DP, 10 KA breaking capacity, 20 Amp of ABB/L&T (Hagar)/HPL/GE/MDS/Siemens/BCH/C&S/ CGL/Schneider/Havells make --- 1 No (iii) Three-phase, 440 Volt power plug and five-pin socket, 63 Amp of BCH make, Cat. No. DS6A7A1 or similar model of L&T/SIEMENS/HPL --- 1 No (iv) Single phase, 250 Volt power plug and three-pin socket, 20 Amp of BCH make, Cat. No. MPSEU202 or similar model of L&T/SIEMENS/HPL --- 1No (v) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (vi) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) with protection fuses of L&T/C&S/BCH make --- 1 Set (vii) Cable glands of required sizes --- LOT (viii) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (ix) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos (x) The enclosure shall be internally wired by suitable size FRPVC insulated, single core flexible copper multi-stranded wires with crimped copper lugs. The price shall also cover for fixing testing and commissioning of the enclosure securely on cover shed pillars/rails/wall with necessary M.S. clamps, nuts, bolts etc. The drawing, design of plug socket, switchgears with make and model shall be got approved from site-engineer before fabrication and supply. | — | — | — | 1,58,368 | |
| — | 2.00 | — | — | ||
| Providing Distribution Board with incomer MCCB, four-pole, 63 Amp - 1 No, RCBO, four-pole, 40 Amp - 1 No and outgoing MCB TPN, 32 Amp - 2 Nos and MCB DP, 16/32 Amp - 6 Nos - The price shall cover for fabrication, supply, fixing, testing and commissioning of outdoor type LT distribution board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The board shall fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/accessories - (a) Incomer - MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/Schneider make --- 1 No RCBO, four-pole, 30 mA sensitivity, 40 Amp capacity of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/ Schneider make --- 1 No (b) Outgoing - MCB TPN, 10 KA breaking capacity, 32 Amp of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/Schneider make ---- 2 Nos MCB DP, 10 KA breaking capacity, 16/32 Amp of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/ Schneider make ---- 6 Nos (c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) with protection fuses of L&T/C&S/BCH make --- 1 Set (e) Cable glands of required sizes --- LOT (f) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (g) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos | — | — | — | 56,768 | |
| — | 1.00 | — | — | ||
| Providing Distribution Board, outdoor type, double-door, wall/floor mounted with incomer MCCB, four-pole, 125 Amp - 1 No and outgoing MCCB, four-pole, 63 Amp - 4 Nos, MCCB, four-pole, 63 Amp - 4 Nos, MCB TPN, 32 Amp - 10 Nos and MCB DP, 10 Amp - 4 Nos with multifunctional energy meter, indication lamp and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of outdoor type LT distribution board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The board shall fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories - (a) Incomer - MCCB, four-pole, 125 Amp, with thermal-magnetic release range 100 - 125 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/Schneider/Havells make --- 1 No (b) Outgoing - MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/Schneider/Havells make --- 4 Nos MCB TPN, 10 KA breaking capacity, 32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 10 Nos MCB DP, 10 KA breaking capacity, 10 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 4 Nos (c) Digital multifunction meter for measurement of Voltage, Current, Frequency, KW, PF, KVAR, KVA, KVAH, KWH, KVARH with required capacity of CT. The multifunctional meter shall be of L&T/Siemens/ Schneider/HPL/Secure Meters Ltd/Anchor/Panasonic/El measure make --- 1 No (d) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (e) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) with protection fuses --- 1 Set (f) Cable glands of required sizes --- LOT (g) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (h) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos | — | — | — | 96,880 | |
| — | 1554.00 | — | — | ||
| Digging of cable trench 450/600 mm wide and 900 mm deep in all types of soil including hard, rocky etc. - The price shall cover for digging of 450/600 mm wide and 900 mm deep trench in all types of soil including soft, rocky as per cable route plan and filling back the trench after laying of cables. This also includes clearing of roots of trees and bushes and other temporary obstructions on the selected route. | — | — | — | 2,00,466 | |
| — | 800.00 | — | — | ||
| Digging of cable trench 100 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of cable in 50 mm HDPE pipe - The price shall cover for digging of cable trench of size 100 x 200 mm deep in concrete/tar road/platform surface and its refilling/ plastering after laying of cable in 50 mm diameter HDPE pipe of Tijaria/Himalyan/Koncept/Poddar/Unique/ Dutron/Reliance/Baba/Shivam make in existing trench. Supply and laying of HDPE pipe, 50 mm diameter is included in the scope of work. | — | — | — | 3,24,800 | |
| — | 3500.00 | — | — | ||
| Supply and laying of DWC pipe, 63 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 63 mm diameter of Tijaria/Himalyan/Koncept/Poddar/Unique/ Dutron/Reliance/Baba/Shivam make. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively. The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 2,94,000 | |
| — | 149.00 | — | — | ||
| Supply and laying of HDPE pipe, 110 mm diameter by pushing method under track/road - The price shall cover for supply of HDPE (High Density Polyethylene) pipe of 110 mm nominal diameter as per IS 4984-1995 of make Tijaria/Himalyan/Koncept/Poddar/Unique with accessories required for laying such as coupler, bend etc. as per details given in Annexure-XXI of tender document. The price shall also cover for laying the HDPE pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 2,25,288 | |
| — | 3740.00 | — | — | ||
| Laying of cable in trench - The price shall cover for laying, testing and commissioning of LTUG armoured cable in existing trench/pipe and its connection at both ends. The cable shall be tested with 500 Volt Megger earth tester before laying it in the trench. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to this office as well as site in-charge after laying of cable. Cables shall be supplied by railways at site engineer's stores. | — | — | — | 78,540 | |
| — | 151.00 | — | — | ||
| Laying of cable on wall/cover shed/existing tray with MS clamp - The price shall cover for laying, testing and commissioning of LTUG armoured cable on wall/cover shed/in existing tray and its connection at both ends. The cable shall be tested with 500 Volt Megger before laying it in the tray. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to site engineer and Divisional Office after laying of cable. Cables shall be supplied by railways at site engineer's stores. | — | — | — | 4,983 | |
| — | 300.00 | — | — | ||
| Providing three-core, flexible copper wire, 24/0.2 mm, conforming to IS: 694, 1100 Volt grade for connection to LED fittings - The price shall cover for supply and connection of three-core, flexible copper wire of size 24/0.20 mm, ISI marked, PVC insulated, conforming to IS: 694, 1100 Volt grade from the existing overhead line/catenary/junction box to LED street light fitting as per site conditions. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit. | — | — | — | 9,300 | |
| — | 200.00 | — | — | ||
| Supply and laying of flexible copper cable, three-core 1.5 sq mm - The price shall cover for supply and laying of XLPE sheathed and insulated, LTUG cable, three-core, 1.5 sq. mm, stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/ Nicco/Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable. | — | — | — | 18,800 | |
| — | 60.00 | — | — | ||
| Supply, fixing, testing and commissioning of 5.0 meter height G.I. street light octagonal pole, single arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0 meter height single arm, G.I. street light octagonal pole as per the specifications mentioned in Annexure-XXI of tender document. | — | — | — | 7,34,760 | |
| — | 25.00 | — | — | ||
| Supply, fixing, testing and commissioning of 5.0 meter height G.I. street light octagonal pole, double arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0 meter height double arm, G.I. street light octagonal pole as per the specifications mentioned in Annexure-XXI of tender document. | — | — | — | 3,86,625 | |
| — | 3.00 | — | — | ||
| Supply, installation, testing and commissioning of battery charging rectifier set for input of 415 Volt, three phase, 50 Hz AC and output 110 to 150 Volt, DC at 200 Amp, cell capacity 120 AH for TL coaches - The price shall cover for supply, installation, testing and commissioning of battery charging rectifier set for input of 415 Volt, three-phase, 50 Hz AC and output 110 to 150 Volt, DC at 200 Amp, cell capacity 120 AH for TL coaches as per specifications given in Annexure-XXI of tender document. | — | — | — | 10,15,653 | |
| — | 7.00 | — | — | ||
| Fabrication, supply, fixing and commissioning of 110 Volt battery charging terminals to be mounted on rail posts - The price shall cover for fabrication, supply, fixing and commissioning of 110 Volt battery charging terminals and design shall be as per sample drawing available in Sr. DEE (Power) Vadodara office. Only two cables shall be tapped from the outgoing terminal of the battery charger and looping of the charging terminals should be in alignment. The looping shall take place at the charging terminals only. Cables shall be terminated/looped at the charging terminals with crimped sockets, nuts, bolts, washers etc. and proper capacity of DC MCB shall be provided on positive and negative terminals. The battery charging terminals shall be securely mounted on rail poles. The 110 Volt charging terminals shall be painted with yellow enamel paint. The cable shall be properly clamped to the pipe. 110 Volt DC and symbol for '+' and '-' for identification of polarity shall be painted on the charging terminal. | — | — | — | 8,897 | |
| — | 2500.00 | — | — | ||
| Providing G.I. Earth wire, 8 SWG in PVC sleeve along with cable - The price shall cover for supply and laying of soft G.I. wire of 8 SWG covered with black coloured PVC sleeve of superior quality and laid along with PVC LTUG cable properly fixed and connecting earthing terminals of each panel. | — | — | — | 55,000 | |
| — | 33.00 | — | — | ||
| Providing maintenance free earthing - The price shall cover for providing maintenance free earthing as per the following specifications - 1. High tensile-low carbon steel rod having diameter not less than 17 mm complying with requirements of BS 4360 Grade 43A or EN10025:2-004 S275JR, molecularly bonded by 99.99% pure high conductivity copper on outer surface with copper coating thickness of 250 micron or more, Length 3000 mm (minimum). Certificates from NABL approved labs shall be submitted with test results. 2. Copper earth bus-bar of size 250 mm x 50 mm x 6 mm having electrical conductivity of 101% IACS, minimum 99.9% copper content shall be exothermically welded to rod with 4 holes of 12 mm diameter (two on each side) for connecting earthing conductor. 3. Earth Enhancement compound should have characteristics as mentioned in the RDSO specifications. It should have low resistivity preferably below 0.2 Ohm-meter, supplied in sealed bags (minimum 75 kg per pit for 5' x 5' x 10' size pit and minimum 50 kg per pit for 300 mm bore type pit. The bags shall be marked with manufacturer's name or trade name, quality, Batch No. and date of manufacture. Certificates from NABL approved labs shall be submitted with test results, for at least following parameters - i) Composition of Earth Enhancement compound ii) Resistivity - < 2 Ohm-meter iii) pH value - > 7 but < 9 iv) Moisture retaining capacity - > 10% at 105 degrees Celsius v) Water solubility - < 5% 4. Backfill material - Good quality soil or excavated soil free from sand, gravel and stones shall be used for backfilling. 5. Earth pit of size 5 feet x 5 feet x 10 feet or min 300 mm bore up to 10 feet using earth auger shall be made. 6. Inspection chamber - A concrete box of 300 x 300 x 300 mm (inside dimensions) and 50 mm thickness of wall, with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approximately 50 mm thick with pulling hooks shall be provided to cover the earth pit. PVC sleeve shall be provided in concrete wall to take out earthing connections. 7. On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background. 8. Instead of copper bus- bar and strips mentioned in the drawing, a GI main bus-bar of minimum size 300 mm x 75 mm x 8 mm to be installed on nearby wall etc. It shall be connected to earthing with two GI strips of 50 mm x 6 mm size each, up to a distance of 10 meters from earth bus-bar (minimum 3 meters x 2 Nos GI strips to be supplied). 9. Earthing shall generally be carried out in accordance with the requirement of I.E. Rules, 1956, as amended from time to time and shall confirm to IS: 3043 of 1987 with latest amendment. 10. The earth value shall be measured and recorded at the site by painting on earth pit or nearest wall along with date of testing. It shall be less than 2 Ohms and neutral to earth voltage shall be less than 3 Volt. 11. Earthing performance after a year of installation shall be jointly checked and measured. It should be less than 2 Ohm. 12. General arrangement of the earth system shall be as per the drawing given in Annexure-XXI of tender document. | — | — | — | 3,49,602 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocument-BRC-EL-P-02-2541-26-27-RNEWGCC.pdf
ATTACHMENT
RailwayBoardsletterNo.2018_CE-I_CT_9dated04.06.18.pdf
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf for cable
ATTACHMENT
BankGuaranteeverification.pdf
ATTACHMENT
TechSpecsofEnergyEfficientLEDBasedLuminaire.pdf
ATTACHMENT
WesternRailwaysSpecificationsforACBLTPanelsMCCBandMCB.pdf
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].