Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.7 LAccepted-AOC 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | ₹38.7 L Quoted ₹39.0 L | L1 | Accepted-AOC L1 |
| 2 | L2₹44.9 L+₹5.8 L (14.9%)Rejected-Finance 101 VRAJ APARTMENT OPP POLICE HEAD QUARTERS SARU SECTION ROAD JAMNAGAR 381008 | JAMNAGAR | 381008 | ₹44.9 L+₹5.8 L (14.9%) | L2 | Rejected-Finance L2 |
| 3 | L3₹50.2 L+₹11.1 L (28.5%)Rejected-Finance | ₹50.2 L+₹11.1 L (28.5%) | L3 | Rejected-Finance L3 |
| 4 | L4₹51.9 L+₹12.9 L (33.0%)Rejected-Finance | ₹51.9 L+₹12.9 L (33.0%) | L4 | Rejected-Finance L4 |
| 5 | L5₹53.6 L+₹14.5 L (37.2%)Rejected-Finance SHREE SHYAM SADAN 10 2 PARAS SOCIETY PANCHVATI JAMNAGAR GUJARAT 361008 | JAMNAGAR | GUJARAT | 361008 | ₹53.6 L+₹14.5 L (37.2%) | L5 | Rejected-Finance L5 |
Tender Value
Refer Docs
EMD Value
₹94,000
Closing Date
3 Nov 2020, 6:00 pmClosed
Lt Col Bhamre Kiran S
Military Engineer Service Garrison Engineer (AF) No.1 Air Force Station No.1 Jamnagar 361 003
REPAIR MAINTENANCE OF RMU (RING MAIN UNIT) CSSVCBS AND CONNECTED WORKS AT AF STATION JAMNAGAR
2020_MES_385280_1
8760/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Jamnagar
Please refer tender documents
6 documents required · 6 mandatory
₹500
GE (AF) Jamnagar No. 1
₹94,000
Yes
5 Jan 2021
10 Oct 2020
4 Nov 2020
10 Oct 2020
3 Nov 2020
27 Oct 2020
Amount
Preventive maintenance for indoor and outdoor type RMU (safeplus or safering type) comprising preventive maintenance activities and repairing the RMU during breakdown / emergency and routine testing all as specified below:- Note:- Quoted rates shall be deemed to include for the following:- (i) Preventive maintenance shall be carried out one time in year. (ii) Contractor shall also responsible for repairing the RMU during any breakdown / emergency. (with in contract period deemed including coated rates) (iii) routine testing shall be carried out once in a year. (iv) Contractor shall also responsible for gas required for refilling of RMU
A. The following scope of work shall be included under preventive maintenance :-
(a) Condition monitoring as per the scope defined:-
Condition based & Predictive maintenance.
Preventive maintenance.
Breakdown maintenance.
Overhauling, reconditioning & testing of existing equipment.
Failure analysis for major breakdown
(b) Performance Health Check-up
Checking of CB & Isolator mechanical & electrical operation Closing & tripping
Checking of Breaker close & open operation.
Mechanism Critical setting & adjustment shall be done.
Lubrication of mechanical critical part of Circuit breaker.
Lubrication of spring charging mechanism.
Operational Movement & alignment.
Alignment of open cable doors.
Physical healthiness of switches, indication lamp, auxiliary relay etc.
Bus bar tightness, bus joint healthiness checks & contact resistance check.
(c) Routine Tests (performed once in a year)
Testing of protection relays.
CB contact resistance, contact condition the pole.
Interrupter health check by HV test
(d) Reports:
Relay test report
Breaker test report
CT/PT test report
Failure reports of major failure-Which includes failure mechanism analysis & remedies Interpretation of condition monitoring data.
B. Check list for breaker preventive maintenance :-
Mimic diagram checking YES / NO
Spring Charging of HT breaker -by manual operation YES / NO
Spring Charging of HT breaker -by motor if available YES / NO
All limit switch operation healthiness for motorized module YES / NO
Closing of breaker by push button YES / NO
Opening of breaker by push button YES / NO
BKR on/ off indication sticker YES / NO
Disconnector closing and opening YES / NO
Disconnector Earth switch closing and opening checking YES / NO
Disconnector ON/Off indication sticker YES / NO
Remote close of BKR if closing coil available YES / NO
Remote opening of BKR by series trip coil YES / NO
Remote opening of BKR by shut trip coil if available YES / NO
Padlock Movement of Disconnector and Breaker YES / NO
Interlock between breaker On condition and Disconnector YES / NO
Interlock between BKR OFF condition and Disconnector YES / NO
Cable door interlock with Earth switch on/off condition YES / NO
Handle locater of Disconnecter healthiness YES / NO
Interlock of cable door with respect to BKR and disconnector YES / NO
Relay self power battery healthiness - if self power YES / NO
Relay display healthiness YES / NO
Remote Closing - if available YES / NO
Series trip coil healthiness. YES / NO
Remote tripping of relay YES / NO
Shunt trip coil healthiness/ remote tripping YES / NO
termination boots position / termination bushing cover YES / NO
Proper Termination boot earthing for 22/33 KV YES / NO
Termination Tightness ( 30/ 50 Nm) YES / NO
Terminated cable support condition YES / NO
Cable gland sealing checking YES / NO
VPIS healthiness OK YES / NO
CT ratio installed in BKR compartment YES / NO
CT connection tightness YES / NO
Cable boot fixing healthiness YES / NO
cable boot earthing for 22 KV and 33 KV YES / NO
Cable support YES / NO
Cable Gland provision YES / NO
C. Check list for RMU preventive Maintenance :-
Grouting of Frame/ channel on foundation tightened YES / NO
Earthing connection of RMU YES / NO
Outer Visual inspection of RMU YES / NO
Sealing of RMU / any opening for insertion RMU . YES / NO
SF6 gas level indication position in zone YES / NO
DC power pack operation healthiness - 24 V YES / NO
Battery 24 V Dc healthiness YES / NO
230 V AC supply requirement / availability YES / NO
Coupling Box Cover fixing if RMU extensible and coupled YES / NO
Coupling Bus bar tightness YES / NO
Coupling boot earthing YES / NO
Not any opening on box up YES / NO
Electrical testing status YES
D.Operational check points for isolator / cable switch Module :-
Operational Check Points for Isolator Module
Mimic diagram checking YES / NO
Isolator / cable switch on/off manual operation by handle YES / NO
Isolator / cable switch on/off operation by motor operation if available (Locally ) YES / NO
Isolator / cable switch on operation by motor operation if available ( Remotely ) YES / NO
Isolator / cable switch off operation by motor operation if available ( Remotely ) YES / NO
All limit switch operation healthiness for motorized Rmu YES / NO
Padlock Movement of Isolator / Cable switch YES / NO
Isolator on/ off indication sticker YES / NO
Earth switch Operation YES / NO
cable door opening and closing smoothness YES / NO
Cable door interlock with Earth switch on/off condition YES / NO
Handle locater of Disconnecter healthiness YES / NO
VPIS healthiness YES / NO
Termination tightness YES / NO
Cable boot fixing healthiness YES / NO
cable boot earthing for 22 KV and 33 KV YES / NO
Cable support YES / NO
Cable Gland provision YES / NO
(i) RMU of make ABB & Crompton are installed at site. Preventive maintenance, repairing the RMU during breakdown / emergency and routine testing shall be carried out through authorised representative of OEM
(ii) Spare parts required for Preventive maintenance, repairing the RMU during breakdown / emergency will be measured & paid separately as supply & fix in repair. Make of spare part shall be as recommended by the OEM.
(iii) Contractor shall submit necessary documentary evidence that Preventive maintenance, repairing the RMU during breakdown / emergency and routine testing has been performed by the OEM
(vi) RMU any type any way including VCB, load break switch and metering unit will be measured as one unit for payment.
(v) After Preventive maintenance, repairing the RMU during breakdown / emergency RMU shall be tested as directed by the Engineer-in-Charge and test result in triplicate copy shall be submitted to Engineer-in-Charge
Preventive maintenance for 160-400 KVA compact substation (CSS) comprising transformer, RMU / VCB, LT Panel / APFC Panel by performing preventive maintenance activities and repairing the CSS during breakdown / emergency and routine testing all as specified below:-
Note:- Quoted rates shall be deemed to include for the following:- (i) Preventive maintenance shall be carried out one time in year. (ii) Contractor shall also responsible for repairing the CSS during any breakdown / emergency (with in contract period deemed including coated rates) (iii) routine testing shall be carried out once in a year. (iv) Dehydration/filtration/oil filling carried out by contractor. (iv) Dehydration/filtration/oil filling carried out by contractor
Checking of ckt. breaker mechanical & electrical operation closing & tripping.
Checking of CSS & earth s/w close & open operation.
Mechanism critical setting and adjustment shall be done.
Lubrication of mechanical critical parts of circuit breaker shall be done.
Lubrication of spring mechanism shall be carried out.
Checking the movement and interlocks of RMU with VCB & isolator.
Checking of alignment of open cable doors.
Physical healthiness of switches, indication lamp, aux relays.
Bus bar tightness , bus joint healthiness checks by torque wrench and contact resistance check.
Any other service point observed
Planning & updating maintenance
Routine testing of CSS
Testing of protection relay by secondary injection test.
Routine testing of transformer.
Check the trip operation of the breaker through relay
Primary injection test on CTs.
Contact resistance testing on breaker and bus joints
Ratio check of potential transformer
Checked the open delta voltage ( if applicable)
Megger & HV test
B. Check list for CSS preventive Maintenance :-
(a) Common check point :-
Visual Inspection of CSS
Visual Inspection of side wall of CSS
Earthing pith connection checking
Earthing pith Healthiness verification-ground resistance
Opening and Closing of HT door
Opening and Closing of Metering Door
Opening and Closing of Trafo door -1
Opening and Closing of Trafo door -2
Opening and Closing of LT door
Operation Healthiness HT door limit switch
Operation Healthiness Trfo door limit switch -1- HT tripping /alarm
Operation Healthiness Trafo door limit switch -2- HT tripping / alarm
Operation Healthiness LT door limit switch
(c) Operational checking point of HT panel :-
SF6 gas level indication - position in zone
DC power pack operation healthiness
Battery 24 V Dc healthiness
Spring Charging of HT breaker -by manual operation
Spring Charging of HT breaker -by motor operation if available
Closing of breaker by push button
Opening of breaker by push button
Off load Isolator closing and opening
Earth switch closing and opening checking
Interlock between breaker and off load isolator
Interlock between Earth switch and off load isolator
Interlock of earth switch and BKR cable door
ON load isolator operation of closing and opening by manual
ON load isolator operation of closing and opening by motor if available
ON load isolator earth switch operation
ON load Isolator Interlock of earth switch and cable door
Individual opening and closing of cable door -ON load iso later
Individual opening and closing of cable door -Breaker-3
Earthing tightness checking of HT Breaker.
Termination Tightness verification of all three HT module
Ensure - for proper Gland plate, Cable support , termination boot.
Ensure - cable bushing must be unloaded
Tripping coil healthily in operation
Remote tripping of HT breaker.
Relay self power battery checking.
Relay trip test operation checking
Reading in measurement checking / healthiness of relay by testing .
VPIS healthiness
Transformer protection Relay working
Earth Fault indicator testing / resetting
All Padlock checking of RMU
(d) Transformer Check Points :-
Visual inspection of transformer
Check oil leakage if oil type
Check oil level in transformer if oil type
Visual inspection of bushing & bolt.
Insulation resistance of Trafo cable
Insulation resistance of Transformer
Tightness of HT bushing
Tightness of Bus bar
Transformer earthing
CSS body earthing
Hooter operation healthiness checking
Pressure relief Valve healthiness
Pressure relief Valve and HT tripping/alarm verification if provided
WTI reading verification
WTI operation tripping / alarm checking
OTI reading verification
OTI operation tripping / alarm checking
Tap change over operation healthiness.
Transformer compartment lamp
Proper HT Cable support
GI earthing strip supporting Insulator condition
(e) LT compartment Check Points :-
Manual operation of ACB - charging ,
Manual closing and opening.
Charging of ACB by Motor if available
Tightness off all bus bar
Earthing connection verification.
Indication Lamp of Phase
LT BKR / ACB indication ( alarm / trip) & Protection relay working- LT
(i) CSS of make ABB are installed at site. Preventive maintenance, repairing the CSS during breakdown / emergency and routine testing shall be carried out through authorised representative of OEM
(ii) Spare parts required for Preventive maintenance, repairing the CSS during breakdown / emergency will be measured & paid separately as supply & fix in repair. Make of spare part shall be as recommended by the OEM.
(iii) Contractor shall submit necessary documentary evidence that Preventive maintenance, repairing the CSS during breakdown / emergency and routine testing has been performed by the OEM
(iv) After Preventive maintenance, repairing the CSS during breakdown / emergency CSS shall be tested as directed by the Engineer-in-Charge and test result in triplicate copy shall be submitted to Engineer-in-Charge
Following spare part shall be used for SAFEPLUS RING MAIN UNIT
S&F in repair Bushing 400 Series Bolted Type item Code NHP201699R1
S&F in repair O Ring 72 x 6 BUSHING 400 SERIES BOLTED item Code NHP402076P15
S&F in repair SHAFT FOR OPERATING HANDEL item code NHP304961P1
S&F in repair 2PA Mechanism w/o hex rod item code NHP101985R002
S&F in repair TRIP COIL SAFEO FORCE AMPL WIC & ASHDA item code 1VDP000142R1
S&F in repair Linkage between K and A item code NHP201703R1
S&F in repair PUSH BUTTON RED W/ LABEL "O" item code 1SFA616199R1104
S&F in repair PUSH BUTTON GREEN W/LABEL "I" item code 1SFA616199R1106
S&F in repair BRACKET 'A' Mechanism hldg 2 push buttons item code NHP201536P1
S&F in repair Opening Finger, Manual Operating_D item code 2RAA011099A0001
S&F in repair Closing Finger, Manual Operating_C item code 2RAA011100A0001
S&F in repair BRACKET for 'K' Mechanism item code NHP201495P1
S&F in repair BRACKET FOR CT MTG RMU RHS item code NHP304233P1
S&F in repair 24 kV VPIS cord item code PTMVT120702-01
S&F in repair Capacitor Unit, VPIS, 9-15kV without cord item code YN1V400916-587
S&F in repair PRESSURE REFILLING EQUIPMENT( KAR-6) item code IN54280001-K
S&F in repair RONIS KEY WITH HARDWARE item code 4200669056.9005
S&F in repair RONIS LOCK & KEY FOR RMU WITH KEY A item code 4200040617.1001
S&F in repair RONIS KEY INTERLOCK OF LBS WITH KEY C item code 4200130305.9001
S&F in repair RONIS INTERLOCK EL11P OF LBS WITH KEY B item code 4200033538.9005
S&F in repair Fuse Holder Assembly item code NHP201487R001
S&F in repair TERMINAL PROTECTOR SILCAB (RAYCHEM) for 11kV item code 1VYN303050-060
S&F in repair T SHROUD (NEW) for 11kV item code 1VYN403250-92N
S&F in repair Reducer Stud for Cable Bushing_A 128 item code 2REA024265P0001
S & F in repair Trip Coil Only Y1 Control Volt 24 VDC item code NHP304453R1
S & F in repair Close Coil Only Y2 Control Volt 24 VDC item code NHP304453R6
S & F in repair O Ring 65 x 5 For LBS Mech Bushing item code NHP402076P24
S & F in repair Spring charging Motor with Gear 24 V DC item code NHP201491R1
S & F in repair WIKA make Manometer+Gas density switch item code YN1V400929-420
S & F in repair ELECTRONIC MOTOR KIT FOR C MODULE-MGVCL item code 4200901778.9004
S & F in repair STANDARD MOTORISED KIT FOR V MODULE item code YN1V400922-023
S & F in repair BRACKET-FOR RMU (New Indication) item code NHP304264P1
S & F in repair Position indicator item code 1VDP001531P001
S & F in repair Indicator local item code 1VDP002477P001
S & F in repair Shaft item code 1VDP002579P001
S & F in repair Indicator Flag C-module OFF item code 1VYN403050-496
S & F in repair Indicator Flag C-module ON item code 1VYN403050-498
S & F in repair Indicator Flag C-module PLAIN item no 1VYN403050-499
S & F in repair Manometer+Gas density switch(CO contact) item code 4200800466.5012
S & F in repair STANDARD MOTORISED KIT FOR C MODULE item code YN1V400922-022
S & F in repair BATTERY -12VDC ,12AH item code 1VYN401350-173
S & F in repair Capacitor Unit,VPIS 15-24kV without cord item code YN1V400916-588
S & F in repair S series bushings item code 2REA020480A0001
S & F in repair O ring for S series bushing item code 3WEA010283P0001
Following spare part shall be used for SAFELINK RING MAIN UNIT
S & F in repair GEARED MOTOR 24VDC (MS) item code No 1VCR012079G0001
S & F in repair SHUNT CLOSING RELEASE -MC 24VDC item code no 1VCR004291G0001
S & F in repair VD4 MC Closing Coil (48V AC-DC)) item code no 1VCR004291G0003
S & F in repair SHUNT CLOSING RELEASE 110VDC/AC -MC item code No 1VCR004291G0005
S & F in repair MC Closing Coil(220-250V DC/220-250V AC) item code no 1VCR004291G0007
S & F in repair Tripping coil of VD4 24 VDC item code no 1VCR004289G0001
S & F in repair SHUNT OPENING RELEASE 110DC/AC -M01 item code no 1VCR004289G0005
S & F in repair Open. Coil Mo1 (220-250V DC/220-250V AC) item code no 1VCR004289G0007
S & F in repair MO2 Assy. (24Vcc)(Additional Trip) item code no 1VCR002985G0001
S & F in repair AUX.SWITCH 2NO+3NC PLUG CONN.,FORK TYPE item code no GCE7002397R0122
S & F in repair AUX.SWITCH 3NO+2NC PLUG CONN.,FORK TYPE item code no GCE7002397R0121
S & F in repair BKR Auxiliary Switch Assy._C item code no 2REA016209A0001
S & F in repair Closing spring signalling item code no 510831-802
S & F in repair SWITCH ELEMENT S826 E/L item code no NZN000859P11
S & F in repair Auxiliary Switch Assembly_A item code no 2REA009781A0001
S & F in repair DisconnectorMechanism assembly item code no 2REA016749A0001
S & F in repair Ring switch mechanism RH item code no 2REA009811A0004
S & F in repair Ring switch mechanism LH item code no 2REA014003A0001
S & F in repair Bushing+Contact Knives Assembly RH_B item code no 2REA010249A0001
S & F in repair Bushing+Contact Knives Assembly LH_B item code no2REA010249A0002
v S & F in repair TP bushing assembly item code no 2REA010376A0002
S & F in repair T-off cable bushing item code no 2REA009169A0001
S & F in repair Capacitor Unit, VPIS, 9-15 kV With Cord item code no YN1V400916-587
S & F in repair VPIS Cable Switch L1-0.7, L2-0.6, L3-0.5 item code no 2REA014974P0002
S & F in repair VPIS CableT-Off L1-1.36,L2-1.255,L3-1.15 item code no 2REA014974P0001
S & F in repair ABB RELAY TYPE REJ 603-REJ603BB401NN3XE item code no YN1V400919-532
S & F in repair Operating Handle Assembly_C item code no 2REA017122A0001
S & F in repair OPERATION COUNTER item code no 510753-802
S & F in repair OPENING SOLENOID ASSEMBLY_B item code no 2REA016775A0001
S & F in repair GAS SPRING FRONT DOOR_03 item code no 308(A)-02
S & F in repair Manometer assembly item code no 2REA013719P0001
S & F in repair Mamometer with density switch assembly item code no 2REA013719P0002
Note for all the items of BOQ:- Item Code No given for spear part are of make ABB contractor may use spare part of other make as approved by the OEM.
Note for all the items of BOQ:- If any above HT/LT Equipment and connected items become breakdown, the contractor shall locate the problem/fault at site within 12 hours on intimation by JE/Engineer-In-Charge and ensure that the fault is rectified within 24 to 48 Hours , failing which an amount of Rs 200 /- per hour will be recovered as penal recovery from any payment due to the contractor after expiry of 48 hours.)
M/s SK Traders
Sukhi Electricals
Nitesh Enterprise
vijay infraprojects pvt ltd
Parth Infrastructure Pvt. Ltd.
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .