| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹17.2 LAccepted-AOC | ₹17.2 L | 1 | Accepted-AOC L1 |
| 2 | 2₹20.3 L+₹3.1 L (18.0%)Rejected-AOC | ₹20.3 L+₹3.1 L (18.0%) | 2 | Rejected-AOC L2 |
| 3 | 3₹22.6 L+₹5.5 L (31.8%)Rejected-AOC | ₹22.6 L+₹5.5 L (31.8%) | 3 | Rejected-AOC L3 |
| 4 | 4₹27.8 L+₹10.6 L (61.8%)Rejected-AOC | ₹27.8 L+₹10.6 L (61.8%) | 4 | Rejected-AOC L4 |
| Sl No | Description | Qty | Unit | DSK ELECTRIC POWER L1 | Leela Electricpower Services Pvt.Ltd L4 | ABM Electricals L3 | MICRON ELEC-TECH L2 |
|---|---|---|---|---|---|---|---|
| 1.00Electrical Panel Works | |||||||
| 2.00STP MAIN INCOMER LT PANEL | |||||||
| 2.01 | Fabrication Supply, installation, testing and commissioning of 250A, LT, floor mounted type, dust and vermin proof, free standing, cubical type construction, made out 14SWG thick CRCA sheet fully compartmentalised with top bus duct/trunking entry with necessary connectors and bottom cable entry for outgoing, duly rust inhibited, degreased, zinc phosphated and powder coating painted with approved colour and quality, complete with hinged and earthed front doors, name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made of 3mm thick sheet steel with CT Digital ammeters with cast resin type CTs and Digital Voltmeter with selector switch or Multifunction meters, indication lamps,high conductivity wrought aluminium busbars with SMC supports, heat shrinkable sleeves etc. all connections and inter-connections, electrical interlocks, including mounting the following switch gears as per SLD with IP54. The panel shall be CPRI tested and shall comply with IEC 61439-1 & IEC 61439-2.
Switchgear components (MCCB/MCB/contactors/relays/meters) shall be , with relevant IS/IEC compliance. | 1 | set | 4,30,000 ₹4,30,000 Lowest | 7,83,703 ₹7,83,703 | 4,50,000 ₹4,50,000 | 5,35,000 ₹5,35,000 |
| 2.02Incomer: | |||||||
| 2.03SITC of 250A, 36kA or above, microprocessor-based, 4P MCCB with variable settings, along with all accessories including spreader links and extended rotary handle in existing panel.- 1No | |||||||
| 2.04Advanced Multifunction meter- Cl 1-1 Nos (Three-phase, 4-wire, 425 V, 50 Hz system, true-RMS digital type meter with the following features: Measures and displays VLL, VLN, A, Hz, kW, kVA, kVAR, PF, Wh, VAh, VARh, VAF, instantaneous and cumulative parameters.Provides High/Low recording of voltage (L-L & L-N), current, power factor, frequency and power parameters with time stamping through in-built Real-Time Clock (RTC). Displays Voltage & Current Total Harmonic Distortion (THD) and individual harmonics up to the 31st order for both voltage and current.Meter shall have programmable CT/PT ratios, auto-scaling, and user-configurable demand interval (1 to 60 min) for kW/kVA demand calculation. Provides maximum demand indication and load-profile/data-logging memory for energy and demand parameters.Supports RTC-based demand management and seamless integration with EMS / SCADA / BMS systems through RS-485 serial communication port using industry-standard Modbus RTU protocol (DLMS optional).Shall include password protection, tamper and event logging, and battery-backed RTC ensuring data retention during power failure.Meter shall be Class 0.5 S accuracy for active energy as per IEC 62053-22 / IS 14697, and conform to relevant IEC/IS standards for multifunction energy meters. The unit shall have a back-lit LCD display, programmable parameters via front keys or software, and be suitable for panel mounting (96 × 96 mm) with auxiliary supply 230 V AC ± 20 %.) | |||||||
| 2.05Earth leakage relay of 300mA, 3 Sec - 1 No | |||||||
| 2.06CBCT (Core Balance Current Transformer) for ELR | |||||||
| 2.07250/5A ,10 VA,Cast resin type ,CL:0.5 ,CT-3 Nos | |||||||
| 2.08Outgoings: | |||||||
Tender Value
₹17.8 L
EMD Value
₹44,500
Closing Date
8 Jul 2026, 3:00 pmClosed
Chief Executive Officer
Park Centre, Technopark Phase I Campus
250 KLD STP and RO Plant Electrification Works, Technopark Phase I Campus
2026_ETPK_856742_2
ETPK/PH-I/2026-27/E-08
Open Tender
Electrical Works
Item Rate
90 days
Technopark Phase I Campus
Please refer Tender documents.
2 documents required · 2 mandatory
₹4,200
₹44,500
13 Aug 2026
30 Jun 2026
9 Jul 2026
30 Jun 2026
8 Jul 2026
30 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Electrical Panel Works | |||||
| 2STP MAIN INCOMER LT PANEL | |||||
| 2.01 | Fabrication Supply, installation, testing and commissioning of 250A, LT, floor mounted type, dust and vermin proof, free standing, cubical type construction, made out 14SWG thick CRCA sheet fully compartmentalised with top bus duct/trunking entry with necessary connectors and bottom cable entry for outgoing, duly rust inhibited, degreased, zinc phosphated and powder coating painted with approved colour and quality, complete with hinged and earthed front doors, name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made of 3mm thick sheet steel with CT Digital ammeters with cast resin type CTs and Digital Voltmeter with selector switch or Multifunction meters, indication lamps,high conductivity wrought aluminium busbars with SMC supports, heat shrinkable sleeves etc. all connections and inter-connections, electrical interlocks, including mounting the following switch gears as per SLD with IP54. The panel shall be CPRI tested and shall comply with IEC 61439-1 & IEC 61439-2.
Switchgear components (MCCB/MCB/contactors/relays/meters) shall be , with relevant IS/IEC compliance. | - | set | 2 | - |
| 2.02 | Incomer: | - | - | - | - |
| 2.03 | SITC of 250A, 36kA or above, microprocessor-based, 4P MCCB with variable settings, along with all accessories including spreader links and extended rotary handle in existing panel.- 1No | - | - | - | - |
| 2.04 | Advanced Multifunction meter- Cl 1-1 Nos
(Three-phase, 4-wire, 425 V, 50 Hz system, true-RMS digital type meter with the following features:
Measures and displays VLL, VLN, A, Hz, kW, kVA, kVAR, PF, Wh, VAh, VARh, VAF, instantaneous and cumulative parameters.Provides High/Low recording of voltage (L-L & L-N), current, power factor, frequency and power parameters with time stamping through in-built Real-Time Clock (RTC).
Displays Voltage & Current Total Harmonic Distortion (THD) and individual harmonics up to the 31st order for both voltage and current.Meter shall have programmable CT/PT ratios, auto-scaling, and user-configurable demand interval (1 to 60 min) for kW/kVA demand calculation.
Provides maximum demand indication and load-profile/data-logging memory for energy and demand parameters.Supports RTC-based demand management and seamless integration with EMS / SCADA / BMS systems through RS-485 serial communication port using industry-standard Modbus RTU protocol (DLMS optional).Shall include password protection, tamper and event logging, and battery-backed RTC ensuring data retention during power failure.Meter shall be Class 0.5 S accuracy for active energy as per IEC 62053-22 / IS 14697, and conform to relevant IEC/IS standards for multifunction energy meters.
The unit shall have a back-lit LCD display, programmable parameters via front keys or software, and be suitable for panel mounting (96 × 96 mm) with auxiliary supply 230 V AC ± 20 %.) | - | - | - | - |
| 2.05 | Earth leakage relay of 300mA, 3 Sec - 1 No | - | - | - | - |
| 2.06 | CBCT (Core Balance Current Transformer) for ELR | - | - | - | - |
| 2.07 | 250/5A ,10 VA,Cast resin type ,CL:0.5 ,CT-3 Nos | - | - | - | - |
| 2.08 | Outgoings: | - | - | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1450922.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.42 MB
Tenderdoc.pdf
Tender Documents • 1.48 MB
BOQ_1450922.xls
BOQ • 0.43 MB
NIT.pdf
Other Document • 0.40 MB
Tech_Corri1.pdf
PDF • 0.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .